multiplus_faq [2019-12-17 13:15] guy_stewartmultiplus_faq [2020-10-06 02:15] – [3.1 Derating of the power factor] guy_stewart
Line 52: Line 52:
  
  
-==== Software Changes ====+==== Software Settings ====
  
  
Line 181: Line 181:
 This leading or lagging power factor will have the effect of demanding more kVa from the generator for the same or less DC Watts delivered to the batteries. You may need to further reduce the DC Current Limit in the Charger tab of VEConfigure if the generator continues to overload after changing this setting. This leading or lagging power factor will have the effect of demanding more kVa from the generator for the same or less DC Watts delivered to the batteries. You may need to further reduce the DC Current Limit in the Charger tab of VEConfigure if the generator continues to overload after changing this setting.
  
-Effectively, the total charge current possible will be less that the rated maximum charge current output of the charger (under normal conditions) when weak AC is disabled.+Effectively, when Weak AC is enabled, the total charge current possible will be less that the rated maximum charge current output of the charger (under normal conditions).
  
  
Line 200: Line 200:
 ====== Still not connecting? ====== ====== Still not connecting? ======
  
-If the unit is still not connecting, switch the Multi over to Charger only mode. +If the unit is still not connecting,  
 + 
 +Check the VE.Bus Monitor and AC Input Connection timer 
 + 
 +{{::veconfige_107016584.png?direct|}} 
 + 
 +With Multi firmwares xxyy460 and up, VEConfig will indicate why the AC Input is rejected and will also show an indication of the remaining waiting time as a blue bar. 
 + 
 +After the waiting time the unit will connect to AC input provided that there is no assistant which prevents the unit from connecting to grid and that the required relay test is performed. 
 + 
 +Switch the Multi over to Charger only mode. 
  
 Try with a different generator. Try with a different generator.