Line 200: Line 200:
 ====== Still not connecting? ====== ====== Still not connecting? ======
  
-If the unit is still not connecting, switch the Multi over to Charger only mode. +If the unit is still not connecting,  
 + 
 +Check the VE.Bus Monitor and AC Input Connection timer 
 + 
 +{{::veconfige_107016584.png?direct|}} 
 + 
 +With Multi firmwares xxyy460 and up, VEConfig will indicate why the AC Input is rejected and will also show an indication of the remaining waiting time as a blue bar. 
 + 
 +After the waiting time the unit will connect to AC input provided that there is no assistant which prevents the unit from connecting to grid and that the required relay test is performed. 
 + 
 +Switch the Multi over to Charger only mode. 
  
 Try with a different generator. Try with a different generator.