multiplus_faq
Differences
This shows you the differences between two versions of the page.
Both sides previous revisionPrevious revisionNext revision | Previous revisionLast revisionBoth sides next revision | ||
multiplus_faq [2019-12-01 23:50] – updated ve-configure to veconfigure guy_stewart | multiplus_faq [2022-10-31 11:51] – mvader | ||
---|---|---|---|
Line 10: | Line 10: | ||
- | Some generators are more suitable than others for use with inverter/ | + | Some generators are more suitable than others for use with inverter/ |
For example; some things to look for when selecting a generator is a high quality alternator and AVR (auto voltage regulation). | For example; some things to look for when selecting a generator is a high quality alternator and AVR (auto voltage regulation). | ||
Line 35: | Line 35: | ||
If your generator is smaller than the recommended size for your inverter/ | If your generator is smaller than the recommended size for your inverter/ | ||
+ | If you do want an inverter based generator (eg for noise reasons under lower loading), get one that is at least 30% larger than required than an equivalent AVR based model to help prevent nuisance overloads. | ||
+ | |||
+ | It is also important to look at the DUTY CYCLE rating of the generator. Some generators are marketed for their peak output, but may only be designed to sustain 50% of that peak load rating for longer periods of time. | ||
+ | |||
+ | Battery charging is a very heavy use case load for a generator, so make sure it is up to the job, and the installation has plenty of good airflow and ventilation when operating to allow for heat to dissipate. | ||
+ | |||
+ | Some generators are only designed to operate for several hours, before requiring time to rest and cool down. Make sure this limitation is part of your load profile and system design. | ||
==== Operation ==== | ==== Operation ==== | ||
Line 45: | Line 52: | ||
- | ==== Software | + | ==== Software |
The settings which you should attempt first are ' | The settings which you should attempt first are ' | ||
- | If the generator will still not synchronise or disconnects, | + | If the generator will still not synchronise or disconnects, |
Lastly, adjusting the settings for Voltage and Frequency windows. These are higher risk to your appliances, they should only be used cautiously when it is confirmed that the loads will tolerate the out of specification power supply. This should be done by a competent technician with the aid of a multimeter and only opened so far as to allow for safe functionality. | Lastly, adjusting the settings for Voltage and Frequency windows. These are higher risk to your appliances, they should only be used cautiously when it is confirmed that the loads will tolerate the out of specification power supply. This should be done by a competent technician with the aid of a multimeter and only opened so far as to allow for safe functionality. | ||
Line 102: | Line 109: | ||
- | ===== 1.5 Loss of mains detection (LOM) ===== | + | ===== 1.5 Loss of mains detection (LOM) (Only applicable to ESS systems) ===== |
+ | |||
+ | This part is only applicable on systems where a grid-code is selected (generally only ESS systems) on an off-grid system a grid code should not be used and in the selection box for grid code, ' | ||
Loss of mains detection will push and pull at voltage and frequency to see if there is still a generating source. This process can cause issues with some generators, or high impedance connections to generators. | Loss of mains detection will push and pull at voltage and frequency to see if there is still a generating source. This process can cause issues with some generators, or high impedance connections to generators. | ||
Line 174: | Line 183: | ||
This leading or lagging power factor will have the effect of demanding more kVa from the generator for the same or less DC Watts delivered to the batteries. You may need to further reduce the DC Current Limit in the Charger tab of VEConfigure if the generator continues to overload after changing this setting. | This leading or lagging power factor will have the effect of demanding more kVa from the generator for the same or less DC Watts delivered to the batteries. You may need to further reduce the DC Current Limit in the Charger tab of VEConfigure if the generator continues to overload after changing this setting. | ||
- | Effectively, | + | Effectively, when Weak AC is enabled, the total charge current possible will be less that the rated maximum charge current output of the charger (under normal conditions). |
Line 193: | Line 202: | ||
====== Still not connecting? ====== | ====== Still not connecting? ====== | ||
- | If the unit is still not connecting, | + | If the unit is still not connecting, |
+ | |||
+ | Check the VE.Bus Monitor and AC Input Connection timer | ||
+ | |||
+ | {{:: | ||
+ | |||
+ | With Multi firmwares xxyy460 and up, VEConfig will indicate why the AC Input is rejected and will also show an indication of the remaining waiting time as a blue bar. | ||
+ | |||
+ | After the waiting time the unit will connect to AC input provided that there is no assistant which prevents the unit from connecting to grid and that the required relay test is performed. | ||
+ | |||
+ | Switch | ||
Try with a different generator. | Try with a different generator. | ||
Line 213: | Line 232: | ||
[[https:// | [[https:// | ||
+ | |||
+ | [[https:// | ||
[[https:// | [[https:// | ||
Line 222: | Line 243: | ||
[[https:// | [[https:// | ||
+ | [[https:// | ||
+ | |||
+ | ===== Community Discussion on MultiPlus 2x120 and generator phase compatibility ===== | ||
+ | |||
+ | [[https:// | ||
+ | [[https:// | ||
- | ===== DISQUS ===== | ||
- | ~~DISQUS~~ |
multiplus_faq.txt · Last modified: 2023-02-16 01:50 by guy_stewart