- | Some generators are more suitable than others for use with inverter/ | + | Some generators are more suitable than others for use with inverter/ |
For example; some things to look for when selecting a generator is a high quality alternator and AVR (auto voltage regulation). | For example; some things to look for when selecting a generator is a high quality alternator and AVR (auto voltage regulation). | ||
Line 35: | Line 35: | ||
If your generator is smaller than the recommended size for your inverter/ | If your generator is smaller than the recommended size for your inverter/ | ||
+ | If you do want an inverter based generator (eg for noise reasons under lower loading), get one that is at least 30% larger than required than an equivalent AVR based model to help prevent nuisance overloads. | ||
+ | |||
+ | It is also important to look at the DUTY CYCLE rating of the generator. Some generators are marketed for their peak output, but may only be designed to sustain 50% of that peak load rating for longer periods of time. | ||
+ | |||
+ | Battery charging is a very heavy use case load for a generator, so make sure it is up to the job, and the installation has plenty of good airflow and ventilation when operating to allow for heat to dissipate. | ||
+ | |||
+ | Some generators are only designed to operate for several hours, before requiring time to rest and cool down. Make sure this limitation is part of your load profile and system design. | ||
==== Operation ==== | ==== Operation ==== | ||
Line 193: | Line 200: | ||
====== Still not connecting? ====== | ====== Still not connecting? ====== | ||
- | If the unit is still not connecting, | + | If the unit is still not connecting, |
+ | |||
+ | Check the VE.Bus Monitor and AC Input Connection timer | ||
+ | |||
+ | {{:: | ||
+ | |||
+ | With Multi firmwares xxyy460 and up, VEConfig will indicate why the AC Input is rejected and will also show an indication of the remaining waiting time as a blue bar. | ||
+ | |||
+ | After the waiting time the unit will connect to AC input provided that there is no assistant which prevents the unit from connecting to grid and that the required relay test is performed. | ||
+ | |||
+ | Switch | ||
Try with a different generator. | Try with a different generator. | ||