multiplus_faq [2019-06-11 07:03] guy_stewartmultiplus_faq [2019-12-01 23:50] – updated ve-configure to veconfigure guy_stewart
Line 59: Line 59:
 Warning: changing these settings will allow to feed-through current that may be of insufficient quality for the electrical requirements of your equipment. Warning: changing these settings will allow to feed-through current that may be of insufficient quality for the electrical requirements of your equipment.
  
-For information on VE-Configure and how to get started, please see this [[https://www.victronenergy.com/support-and-downloads/software|VE Configure Software page]], or contact your [[https://www.victronenergy.com/where-to-buy|local Victron dealer.]]+For information on VEConfigure and how to get started, please see this [[https://www.victronenergy.com/support-and-downloads/software|VE Configure Software page]], or contact your [[https://www.victronenergy.com/where-to-buy|local Victron dealer.]]
  
-====== 1. In the “Grid” tab of VE-Configure: ======+====== 1. In the “Grid” tab of VEConfigure: ======
  
  {{:veconfigure:grid_tab.jpg?nolink&400|}}  {{:veconfigure:grid_tab.jpg?nolink&400|}}
Line 103: Line 103:
  
 ===== 1.5 Loss of mains detection (LOM) ===== ===== 1.5 Loss of mains detection (LOM) =====
 +
 +Loss of mains detection will push and pull at voltage and frequency to see if there is still a generating source. This process can cause issues with some generators, or high impedance connections to generators. 
 +
 +For large and stable Generators Type B LOM will work, and is safer.
 +However, if you are experiencing issues with voltage, frequency or power fluctuations, you may wish to try Disabling LOM.
 +
 +**Disabling LOM**
 +
 +Disabling the LOM on an input connected to the grid is only allowed when other external safety equipment is installed.
 +Disabling the LOM on an input connected to generator can be done, but then other methods / warning signs / physical lockout safety measures must be provided. Ensuring that any installer that will work on the generator, wiring or system, will make sure to also switch off or otherwise disconnect the Inverter/charger system.
  
 For Full information on Loss of Mains detection, please see [[ve.bus:grid-codes-and-loss-of-mains-detection|this more detailed explanation.]] For Full information on Loss of Mains detection, please see [[ve.bus:grid-codes-and-loss-of-mains-detection|this more detailed explanation.]]
  
  
-===== Example configuration in VEConfigure =====+**Example configuration in VEConfigure**
  
   * A generator that requires LOM to be disabled.   * A generator that requires LOM to be disabled.
   * Generator on AC in 1, and grid on AC in 2, as recommended.   * Generator on AC in 1, and grid on AC in 2, as recommended.
  
-{{ :ve.bus:grid-code.png?direct |}}+{{::lom_generator.jpg?direct&400|}}
  
  
  
- +====== 2. In the “General” tab of VEConfigure: ======
-====== 2. In the “General” tab of VE-Configure: ======+
  
 {{::veconfigure:general_tab.jpg?nolink&400|}} {{::veconfigure:general_tab.jpg?nolink&400|}}
Line 132: Line 141:
 ===== 2.2 AC Input Current Limit ===== ===== 2.2 AC Input Current Limit =====
  
-The charger on the Multiplus is very powerful. If you have an existing generator that is not able to supply the maximum charging current of the Multi, you will need to adjust the AC Input Current Limit in the General Tab of VE-Configure.+The charger on the Multiplus is very powerful. If you have an existing generator that is not able to supply the maximum charging current of the Multi, you will need to adjust the AC Input Current Limit in the General Tab of VEConfigure.
  
 A reasonable starting point for the AC Current input limit is 80% of the generator capacity in Watts. For example:  A reasonable starting point for the AC Current input limit is 80% of the generator capacity in Watts. For example: 
Line 153: Line 162:
  
  
-====== 3. In the "Charger" tab of VE-Configure: ======+====== 3. In the "Charger" tab of VEConfigure: ======
  
 {{:veconfigure:charger_tab.jpg?nolink&400|}} {{:veconfigure:charger_tab.jpg?nolink&400|}}
Line 164: Line 173:
  
 This leading or lagging power factor will have the effect of demanding more kVa from the generator for the same or less DC Watts delivered to the batteries. You may need to further reduce the DC Current Limit in the Charger tab of VEConfigure if the generator continues to overload after changing this setting. This leading or lagging power factor will have the effect of demanding more kVa from the generator for the same or less DC Watts delivered to the batteries. You may need to further reduce the DC Current Limit in the Charger tab of VEConfigure if the generator continues to overload after changing this setting.
 +
 +Effectively, the total charge current possible will be less that the rated maximum charge current output of the charger (under normal conditions) when weak AC is disabled.
  
  
 **Important note:** **Important note:**
  
-A detailed description of all settings is available in the VE-Configure help menu, and more instructions are available in our manuals.+A detailed description of all settings is available in the VEConfigure help menu, and more instructions are available in our manuals.
  
-====== 4. In the “Inverter” tab of VE-Configure: ======+====== 4. In the “Inverter” tab of VEConfigure: ======
  
 ===== 4.1 PowerAssist ===== ===== 4.1 PowerAssist =====
Line 186: Line 197:
 Try with a different generator. Try with a different generator.
  
-There can be issues with generators with Residual Current Devices (RCD's), control electronics or circuit breakers. There is some discussion about troubleshooting these issues on this [[https://community.victronenergy.com/questions/1702/multiplus-with-generator-and-residual-current-devi.html|Victron Community Question - Multiplus With Generator And Residual Current Device]], however as troubleshooting and correcting these faults have serious safety implications, they are best discussed with a local installer who has appropriate electrical qualifications, or your Victron Dealer.+As troubleshooting and correcting these faults have serious safety implications, they are best discussed with a local installer who has appropriate electrical qualifications, or your Victron Dealer. 
 + 
 +There can be issues with generators with Residual Current Devices (RCD's), control electronics or circuit breakers. There is some discussion about troubleshooting these issues on this [[https://community.victronenergy.com/questions/1702/multiplus-with-generator-and-residual-current-devi.html|Victron Community Question - Multiplus With Generator And Residual Current Device]].
  
 +Simplify the AC wiring, With everything safely shut down and tested for voltage, disconnect the AC-Output active, neutral and earth. Direct wire in the generator connections, with no other bus bar links. A common neutral can cause issues.
  
 If there is still no connection, contact your dealer or distributor. Tell them the steps that you have taken already to attempt to get it to work and they can help from there. If there is still no connection, contact your dealer or distributor. Tell them the steps that you have taken already to attempt to get it to work and they can help from there.