**AC low disconnect: | **AC low disconnect: | ||
- | On generators where the output voltage drops under load, setting this value to a higher value can help solve shutdowns on overload. | + | On generators where the output voltage drops under load, setting this value to a higher value can help resolve inverter |
- | **AC Low connect:** minimum value: at this value or any higher value, | + | The reason |
+ | If the generator is disconnected under load (either due to low-voltage disconnection, | ||
+ | |||
+ | As overload is driven by current, not power, this can result in an overload. | ||
+ | |||
+ | By increasing this minimum voltage level, you tell the inverter/ | ||
+ | |||
+ | **AC Low connect:** minimum value: at this value or any higher value, the MultiPlus will reconnect after having disconnected (default = 187Vac). | ||