Line 82: | Line 82: | ||
**AC low disconnect: | **AC low disconnect: | ||
- | On generators where the output voltage drops under load, setting this value to a higher value can help solve shutdowns on overload. | + | On generators where the output voltage drops under load, setting this value to a higher value can help resolve inverter |
- | **AC Low connect:** minimum value: at this value or any higher value, | + | The reason |
+ | If the generator is disconnected under load (either due to low-voltage disconnection, | ||
+ | |||
+ | As overload is driven by current, not power, this can result in an overload. | ||
+ | |||
+ | By increasing this minimum voltage level, you tell the inverter/ | ||
+ | |||
+ | **AC Low connect:** minimum value: at this value or any higher value, the MultiPlus will reconnect after having disconnected (default = 187Vac). | ||
===== 1.4 Maximum voltage levels ===== | ===== 1.4 Maximum voltage levels ===== | ||
Line 150: | Line 157: | ||
{{: | {{: | ||
- | **Derating of the power factor** | + | ===== 3.1 Derating of the power factor |
Some generators have a waveform which makes it difficult to charge with the normal charge mechanism. Through activating the " | Some generators have a waveform which makes it difficult to charge with the normal charge mechanism. Through activating the " | ||
Line 162: | Line 169: | ||
A detailed description of all settings is available in the VE-Configure help menu, and more instructions are available in our manuals. | A detailed description of all settings is available in the VE-Configure help menu, and more instructions are available in our manuals. | ||
+ | |||
+ | ====== 4. In the “Inverter” tab of VE-Configure: | ||
+ | |||
+ | ===== 4.1 PowerAssist ===== | ||
+ | |||
+ | The [[https:// | ||
+ | |||
+ | If you have a small generator and have trouble getting connected or staying connected, Disable PowerAssist to allow the device to reduce the AC input current limit. | ||
+ | |||
+ | |||
+ | |||
+ | ====== Still not connecting? ====== | ||
+ | |||
+ | If the unit is still not connecting, switch the Multi over to Charger only mode. | ||
+ | |||
+ | Try with a different generator. | ||
+ | |||
+ | There can be issues with generators with Residual Current Devices (RCD' | ||
+ | |||
+ | |||
+ | If there is still no connection, contact your dealer or distributor. Tell them the steps that you have taken already to attempt to get it to work and they can help from there. | ||