multiplus_faq
Differences
This shows you the differences between two versions of the page.
Both sides previous revisionPrevious revisionNext revision | Previous revisionNext revisionBoth sides next revision | ||
multiplus_faq [2018-01-02 19:43] – mvader | multiplus_faq [2019-06-11 07:03] – guy_stewart | ||
---|---|---|---|
Line 2: | Line 2: | ||
- | What to do when a MultiPlus, or Quattro, does not accept generator power | + | __What |
- | ---- | + | __ |
Power supply from a generator is typically more variable than a power supply from shore or the main grid. The MultiPlus is sensitive to this and will reject power that is outside of it's programmed settings causing the unit to not connect, synchronise or charge. | Power supply from a generator is typically more variable than a power supply from shore or the main grid. The MultiPlus is sensitive to this and will reject power that is outside of it's programmed settings causing the unit to not connect, synchronise or charge. | ||
- | **Selecting a Generator** | + | ==== Selecting a Generator |
Some generators are more suitable than others for use with inverter/ | Some generators are more suitable than others for use with inverter/ | ||
Line 17: | Line 18: | ||
Inverter based generators have a characteristic where the motor continues to run even if the unit has electronically overloaded and no longer delivering power. It may appear that the generator is operating and the system is charging when it isn't. These units are also more easily overloaded by surge loads, as they are electronically limited rather than mechanically. | Inverter based generators have a characteristic where the motor continues to run even if the unit has electronically overloaded and no longer delivering power. It may appear that the generator is operating and the system is charging when it isn't. These units are also more easily overloaded by surge loads, as they are electronically limited rather than mechanically. | ||
+ | Make sure that the generator, inverter/ | ||
+ | Eg 230V / 50hz. Do not mix and match frequencies and voltages, or parts from different regions. | ||
- | **Generator Sizing** | ||
- | It is possible to overload generators with the power demanded by the Multi' | + | ==== Generator Sizing ==== |
- | 2 kVa - 800VA Multi | + | It is possible to overload generators with the power demanded by the Multi's charger. The following generator sizings are indicative of those sizes are appropriate for the charging potential of the various multis. It is still possible to overload these generator sizings with large loads, and flat batteries using the PowerAssist function, so they should be treated as safe minimums to eliminate this as a potential cause of issues. A bigger generator is usually better. |
- | 2.5 kVa - 1200VA Multi | + | ^ Inverter Charger Size ^ Minimum Recommended Generator Size ^ 240V AC Input Current Limit ^ |
+ | | 800VA | 2 kVa | 5A | | ||
+ | | 1200VA | 2.5 kVa | 7A | | ||
+ | | 1600VA | 3 kVa | 10A | | ||
+ | | 3000VA | 5 kVa | 16A | | ||
+ | | 5000VA | 8 kVa | 25A | | ||
- | 3 kVa - 1600VA Multi | + | If your generator is smaller than the recommended size for your inverter/ |
- | 5 kVa - 3000VA Multi | + | ==== Operation ==== |
- | 8 kVa - 5000VA Multi | ||
- | |||
- | **Operation** | ||
It is important to note that the inverter/ | It is important to note that the inverter/ | ||
Line 41: | Line 45: | ||
- | **Software Changes** | + | ==== Software Changes |
The settings which you should attempt first are ' | The settings which you should attempt first are ' | ||
Line 77: | Line 82: | ||
**AC low disconnect: | **AC low disconnect: | ||
- | On generators where the output voltage drops under load, setting this value to a higher value can help solve shutdowns on overload. | + | On generators where the output voltage drops under load, setting this value to a higher value can help resolve inverter |
- | **AC Low connect:** minimum value: at this value or any higher value, | + | The reason |
+ | If the generator is disconnected under load (either due to low-voltage disconnection, | ||
+ | |||
+ | As overload is driven by current, not power, this can result in an overload. | ||
+ | |||
+ | By increasing this minimum voltage level, you tell the inverter/ | ||
+ | |||
+ | **AC Low connect:** minimum value: at this value or any higher value, the MultiPlus will reconnect after having disconnected (default = 187Vac). | ||
===== 1.4 Maximum voltage levels ===== | ===== 1.4 Maximum voltage levels ===== | ||
Line 87: | Line 99: | ||
**AC high connect:** maximum value: at this value or any lower value, the MultiPlus will reconnect after having disconnected (default = 265Vac). | **AC high connect:** maximum value: at this value or any lower value, the MultiPlus will reconnect after having disconnected (default = 265Vac). | ||
+ | |||
+ | |||
+ | |||
+ | ===== 1.5 Loss of mains detection (LOM) ===== | ||
+ | |||
+ | For Full information on Loss of Mains detection, please see [[ve.bus: | ||
+ | |||
+ | |||
+ | ===== Example configuration in VEConfigure ===== | ||
+ | |||
+ | * A generator that requires LOM to be disabled. | ||
+ | * Generator on AC in 1, and grid on AC in 2, as recommended. | ||
+ | |||
+ | {{ : | ||
Line 131: | Line 157: | ||
{{: | {{: | ||
- | **Derating of the power factor** | + | ===== 3.1 Derating of the power factor |
Some generators have a waveform which makes it difficult to charge with the normal charge mechanism. Through activating the " | Some generators have a waveform which makes it difficult to charge with the normal charge mechanism. Through activating the " | ||
Line 138: | Line 164: | ||
This leading or lagging power factor will have the effect of demanding more kVa from the generator for the same or less DC Watts delivered to the batteries. You may need to further reduce the DC Current Limit in the Charger tab of VEConfigure if the generator continues to overload after changing this setting. | This leading or lagging power factor will have the effect of demanding more kVa from the generator for the same or less DC Watts delivered to the batteries. You may need to further reduce the DC Current Limit in the Charger tab of VEConfigure if the generator continues to overload after changing this setting. | ||
+ | |||
**Important note:** | **Important note:** | ||
A detailed description of all settings is available in the VE-Configure help menu, and more instructions are available in our manuals. | A detailed description of all settings is available in the VE-Configure help menu, and more instructions are available in our manuals. | ||
- | ===== Disqus | + | |
+ | ====== 4. In the “Inverter” tab of VE-Configure: | ||
+ | |||
+ | ===== 4.1 PowerAssist ===== | ||
+ | |||
+ | The [[https:// | ||
+ | |||
+ | If you have a small generator and have trouble getting connected or staying connected, Disable PowerAssist to allow the device to reduce the AC input current limit. | ||
+ | |||
+ | |||
+ | |||
+ | ====== Still not connecting? ====== | ||
+ | |||
+ | If the unit is still not connecting, switch the Multi over to Charger only mode. | ||
+ | |||
+ | Try with a different generator. | ||
+ | |||
+ | There can be issues with generators with Residual Current Devices (RCD' | ||
+ | |||
+ | |||
+ | If there is still no connection, contact your dealer or distributor. Tell them the steps that you have taken already to attempt to get it to work and they can help from there. | ||
+ | |||
+ | |||
+ | ====== Further Reading ====== | ||
+ | |||
+ | There have been extensive articles and documentation written about generators and their interaction with Victron systems. This includes troubleshooting, | ||
+ | |||
+ | [[https:// | ||
+ | |||
+ | [[https:// | ||
+ | |||
+ | [[https:// | ||
+ | |||
+ | [[https:// | ||
+ | |||
+ | [[https:// | ||
+ | |||
+ | [[https:// | ||
+ | |||
+ | |||
+ | |||
+ | |||
+ | ===== DISQUS | ||
~~DISQUS~~ | ~~DISQUS~~ |
multiplus_faq.txt · Last modified: 2024-07-17 06:57 by guy_stewart