mppt_pv_short_relay_reset
Differences
This shows you the differences between two versions of the page.
Both sides previous revisionPrevious revision | |||
mppt_pv_short_relay_reset [2023-02-03 02:11] – [When to perform this procedure?] mleeftink | mppt_pv_short_relay_reset [2023-04-18 09:34] (current) – [Reset latching relay] tabreu | ||
---|---|---|---|
Line 19: | Line 19: | ||
To recover from such failure, the below reset procedure must be followed. | To recover from such failure, the below reset procedure must be followed. | ||
- Disconnect the PV Input terminals. | - Disconnect the PV Input terminals. | ||
- | - Power the solar charger through its battery terminals with a 12V battery or bench power supply set to 12V. | + | - Power the solar charger through its battery terminals with a **12V** battery or bench power supply set to **12V**. Note that if the voltage at the solar charger battery terminals is higher than 15V, reset button is disabled in VictronConnect so the reset procedure won't be possible. |
- Make sure no error 80 to 83 is active. If it is active, power cycle the unit. | - Make sure no error 80 to 83 is active. If it is active, power cycle the unit. | ||
- Open VictronConnect and navigate to the Product settings menu. There the PV Short reset feature is shown.{{ : | - Open VictronConnect and navigate to the Product settings menu. There the PV Short reset feature is shown.{{ : |