mppt-error-codes [2019-05-06 13:46] rvanzundertmppt-error-codes [2019-05-06 13:58] – [Err 68 - Network misconfigured] mvader
Line 115: Line 115:
 The charger detects multiple conflicting network sources trying to take control of the charger. The charger detects multiple conflicting network sources trying to take control of the charger.
  
-All Smart Solar charger models:+Applies to SmartSolar MPPTs and SmartSolar MPPTs VE.Can.
  
-  * If the charger is connected to a Venus GX device that takes control of the charger (by sending Charge Voltage Limits to the unit), the charger cannot not be joined to a VE.Smart network as well. In VictronConnect go to settings "VE.Smart networking" and choose "Leave network".+The typical reason for the error to show is that the charger is configured to operate in parallel using our [[https://www.victronenergy.com/live/victronconnect:ve-smart-networking|wireless VE.Smart protocol]]; and at the same time it is part of an [[https://www.victronenergy.com/live/ess:start|Energy Storage System (ESS)]]. Or its used in an installation with an intelligent battery. In all those cases, the charger is being externally controlled, and should not at the same time be configured for parallel operation.
  
-VE.CAN Smart Solar chargers only:+Resolution: disable the parallel operation by connecting VictronConnect, going to settings, then "VE.Smart networking" and choose "Leave network".
  
-  * If the charger is connected via VE.CAN to a Venus GX device do not install a VE.Direct cable to a Venus GX device as well. Either disconnect the VE.CAN cable or the VE.Direct cable.+For SmartSolar MPPT VE.Can only, also make sure its not connected to a [[https://www.victronenergy.com/live/venus-os:start|GX Device]] via both VE.Can and VE.Direct. Either disconnect the VE.CAN cable or the VE.Direct cable.
  
 Once the conflict is resolved the error will disappear and the charger will resume normal operation, usually within a minute. Once the conflict is resolved the error will disappear and the charger will resume normal operation, usually within a minute.