Line 33: Line 33:
 ==== Err 18 - Controller over-current ==== ==== Err 18 - Controller over-current ====
 This error will auto-reset. This error will auto-reset.
-Disconnect the charge controller from all power-sources, wait 3 minutes, and power up again. +If the error does not auto-reset disconnect the charge controller from all power-sources, wait 3 minutes, and power up again. If the error persists the charge controller is probably faulty
-If the error persists the charge controller is probably faulty.+A cause for this error can be switching on a very large load on the battery side.
  
 ==== Err 20 - Maximum Bulk-time exceeded ==== ==== Err 20 - Maximum Bulk-time exceeded ====
Line 58: Line 58:
  
 This error will auto-reset. This error will auto-reset.
 +
 +==== Err 28 - Power stage issue ====
 +
 +This error will not auto-reset.
 +
 +Disconnect all wires, and then reconnect all wires. If the error persists the charge controller is probably faulty.
  
 ==== Err 33 - PV over-voltage ==== ==== Err 33 - PV over-voltage ====
Line 67: Line 73:
 Disconnect the charger from all power-sources, wait 3 minutes, and power-up again. If the error persists the controller is probably faulty, contact your dealer. Disconnect the charger from all power-sources, wait 3 minutes, and power-up again. If the error persists the controller is probably faulty, contact your dealer.
  
-==== Err 38 - Input shutdown due to battery over-voltage ==== +==== Err 38, Err 39 PV Input shutdown ==== 
-To protect the battery from over-charging the panel input is shut down. To recover from this condition first disconnect the solar panels and disconnect the battery. Wait for 3 minutes reconnect the battery first and next the panels.+To protect the battery from over-charging the panel input is shorted
  
-A common reason for this error to occur is that the Battery voltage (12/24/48V) is set, or auto-detected, incorrectly.+Possible reasons for this error to occur
 + * The Battery voltage (12/24/48V) is set, or auto-detected, incorrectly. Use VictronConnect to disable auto-detect and set the Battery Voltage to a fixed voltage. 
 + * There is another device connected to the battery, which is configured to a higher voltage. For example a MultiPlus, configured to equalise at 17 Volts, while in the MPPT this is not configured. 
 + * The battery is disconnected using a manual switch. Ideally the charger should be switched off before disconnecting the battery, this avoids a voltage overshoot on the charger output. If necessary the voltage trip-level for the PV Short protection can be increased by raising the Equalization voltage set-point (note: equalization does not have to be enabled in this case). 
 + * The battery is disconnected using a Lithium charge relay connected to the “allow-to-charge” output of a BMS. Consider wiring this signal to the Remote terminal of the charger instead. This shuts down the charger gracefully without creating a voltage overshoot.
  
-Use VictronConnect to disable auto-detect and set the BatteryVoltage to a fixed voltage.+Error recovery: 
 + * Error 38: First disconnect the solar panels and disconnect the battery. Wait for 3 minutes, then reconnect the battery first and next the panels. 
 + * Error 39: The charger will automatically resume operation once the battery voltage drops below the float level for 1 minute.
  
 If the error persists the charge controller is probably faulty. If the error persists the charge controller is probably faulty.
 +
 ==== Information 65 - Communication warning ==== ==== Information 65 - Communication warning ====
 Communication with one of the paralleled controllers was lost. To clear the warning, switch the controller off and back on  Communication with one of the paralleled controllers was lost. To clear the warning, switch the controller off and back on 
Line 97: Line 110:
  
 Note that (solar-)chargers automatically configure themselves to be BMS-controlled when they are connected to one; either direct or via a Color Control GX or Venus GX. Note that (solar-)chargers automatically configure themselves to be BMS-controlled when they are connected to one; either direct or via a Color Control GX or Venus GX.
 +
 +==== Err 68 - Network misconfigured ====
 +
 +The charger detects multiple conflicting network sources trying to take control of the charger.
 +
 +Applies to SmartSolar MPPTs and SmartSolar MPPTs VE.Can.
 +
 +The typical reason for the error to show is that the charger is configured to operate in parallel using our [[https://www.victronenergy.com/live/victronconnect:ve-smart-networking|wireless VE.Smart protocol]]; and at the same time it is part of an [[https://www.victronenergy.com/live/ess:start|Energy Storage System (ESS)]]. Or its used in an installation with an intelligent battery. In all those cases, the charger is being externally controlled, and should not at the same time be configured for parallel operation.
 +
 +Resolution: disable the parallel operation by connecting VictronConnect, going to settings, then "VE.Smart networking" and choose "Leave network".
 +
 +For SmartSolar MPPT VE.Can only, also make sure its not connected to a [[https://www.victronenergy.com/live/venus-os:start|GX Device]] via both VE.Can and VE.Direct. Either disconnect the VE.CAN cable or the VE.Direct cable.
 +
 +Once the conflict is resolved the error will disappear and the charger will resume normal operation, usually within a minute.
 +
 +
  
 ==== Err 114 - CPU temperature too high ==== ==== Err 114 - CPU temperature too high ====
Line 104: Line 133:
  
 ==== Err 116 - Calibration data lost ==== ==== Err 116 - Calibration data lost ====
-The unit is faulty, contact your dealer for a replacement.+If the unit does not work and error 116 pops up as the active error the unit is faulty, contact your dealer for a replacement.  
 + 
 +If the error is only present in the history data and the unit operates normally this error can be ignored safely. Explanation: when the units power up for the very first time in the factory, it does not have calibration data and an error 116 is logged. Obviously this should have been cleared, but in the beginning units left the factory with this message still in the history data.
  
 +SmartSolar models (not the BlueSolar models): upgrading to v1.4x firmware is a one-way trip, you cannot go back to an older firmware version once you upgrade to v1.4x. Reverting to older firmware gives error 116 (calibration data lost), this can be fixed by re-installing the v1.4x firmware.
 ==== Err 119 - Settings data lost ==== ==== Err 119 - Settings data lost ====
 The charger cannot read its configuration, and stopped. The charger cannot read its configuration, and stopped.
Line 114: Line 146:
   - wait 3 minutes, and power up again.   - wait 3 minutes, and power up again.
   - Reconfigure the charger.   - Reconfigure the charger.
 +
  
  