Line 53: Line 53:
   * 100: unlimited charging. Battery, VEConfigure settings, and BMS permitting. Use value 100 here instead of 1 because this setting was originally designed to be used as a percentage.   * 100: unlimited charging. Battery, VEConfigure settings, and BMS permitting. Use value 100 here instead of 1 because this setting was originally designed to be used as a percentage.
  
-Note that this setting has a higher priority than the //Grid power setpoint//.+Notes: 
 +  * This setting is deprecated and only works when DVCC is disabled. It is retained for backwards compatibility only. Use register 2705 instead to control battery charging. 
 +  * This setting has a higher priority than the //Grid power setpoint//.
  
 === c) Enable/Disable inverter - Modbus-TCP register 2702 === === c) Enable/Disable inverter - Modbus-TCP register 2702 ===
Line 59: Line 61:
   * 100: enabled inverter. Use value 100 here instead of 1 because this setting was originally designed to be used as a percentage.   * 100: enabled inverter. Use value 100 here instead of 1 because this setting was originally designed to be used as a percentage.
  
-Note that this settings has a higher priority than the //Grid power setpoint//.+Notes: 
 +  * This setting is deprecated and only works when DVCC is disabled. It is retained for backwards compatibility only. Use register 2704 instead to control battery discharge. 
 +  * This settings has a higher priority than the //Grid power setpoint//.
  
 === d) Maximum inverter power - Modbus-TCP register 2704 === === d) Maximum inverter power - Modbus-TCP register 2704 ===
Line 66: Line 70:
  
 === e) DVCC maximum system charge current - Modbus-TCP register 2705 === === e) DVCC maximum system charge current - Modbus-TCP register 2705 ===
-  * -1: No limit. Solar Chargers and the Multi will charge to their full capacity or individual configurd limits.+  * -1: No limit. Solar Chargers and the Multi will charge to their full capacity or individual configured limits.
   * Any positive number: Maximum combined current in Ampere for battery charging. This limits the solar chargers and the multi, and takes loads into account. Solar chargers take priority over the Multi.   * Any positive number: Maximum combined current in Ampere for battery charging. This limits the solar chargers and the multi, and takes loads into account. Solar chargers take priority over the Multi.
  