Line 61: Line 61:
 Note that this settings has a higher priority than the //Grid power setpoint//. Note that this settings has a higher priority than the //Grid power setpoint//.
  
 +=== d) Maximum inverter power - Modbus-TCP register 2704 ===
 +  * -1: No limit
 +  * Any positive number: Maximum power in Watt that the Multi will feed to the loads.
 +
 +=== e) DVCC maximum system charge current - Modbus-TCP register 2705 ===
 +  * -1: No limit. Solar Chargers and the Multi will charge to their full capacity or individual configurd limits.
 +  * Any positive number: Maximum combined current in Ampere for battery charging. This limits the solar chargers and the multi, and takes loads into account. Solar chargers take priority over the Multi.
 +
 +=== f) Maximum system grid feed-in - Modbus-TCP register 2706 ===
 +  * -1: No limit. If feeding in excess PV is enabled, all of it will be fed in. See registers 2707 and 2708 below.
 +  * Any positive number: Maximum power in 100 Watt units to feed into the grid.
 +
 +=== g) Feed excess DC-coupled PV into the grid - Modbus-TCP register 2707 ===
 +  * 0: Excess DC-coupled PV is not fed into the grid.
 +  * 1: Excess DC-coupled PV is fed into the grid
 +
 +=== h) Feed excess AC-coupled PV into the grid - Modbus-TCP register 2708 ===
 +Please note that for historical reasons this register is inverted compared to 2707.
 +  * 0: Excess AC-coupled PV is fed into the grid
 +  * 1: Excess AC-coupled PV is not fed into the grid.
 +
 +=== i) Grid limiting status - Modbus-TCP register 2709 ===
 +When feed-in of excess AC-coupled PV is disabled, or when a limit is set in register 2706, limiting will be active.
 +  * 0: Feed-in of excess power is not limited in any way.
 +  * 1: Feed-in of excess power is limited in some way, either register 2707 is set to 0, or register 2706 is set to a positive number.
 ==== 2.2 Accessing the control points ==== ==== 2.2 Accessing the control points ====
  