Line 5: Line 5:
 The here described functionality builds on top of the normal standalone operation, see [[ess:design-installation-manual|ESS manual]]. The here described functionality builds on top of the normal standalone operation, see [[ess:design-installation-manual|ESS manual]].
  
 +WARNING & DISCLAIMER: whilst publically available, Victron Energy does not offer support in professional customers or end-users that implement features using the here documented functionality, except in real specific situations.
 ===== 1. Overview of ESS operating modes ===== ===== 1. Overview of ESS operating modes =====
  
Line 33: Line 34:
 === Mode 3 with a managed battery === === Mode 3 with a managed battery ===
 When using Mode 3 with a managed battery, please note that the maximum discharge current sent by the battery will be ignored. The implemented control loop should take care of discharge limits communicated by the battery. When using Mode 3 with a managed battery, please note that the maximum discharge current sent by the battery will be ignored. The implemented control loop should take care of discharge limits communicated by the battery.
- 
-The exception to the above rule is a zero discharge limit. If a managed battery requests a zero discharge limit, the Multi will stop discharging the battery. 
-    * If grid power is available, the Multi will go into passthru. 
-    * If grid power is not available, the Multi will switch off. 
  
 The maximum charge current sent by a managed battery is however always heeded and cannot be overruled by the setpoint. The maximum charge current sent by a managed battery is however always heeded and cannot be overruled by the setpoint.
Line 72: Line 69:
 For more information, see [[https://groups.google.com/forum/m/#!forum/victron-dev-venus|the developer mailing list]] as well as the [[https://github.com/victronenergy/dbus-mqtt|mqtt github repo]]. For more information, see [[https://groups.google.com/forum/m/#!forum/victron-dev-venus|the developer mailing list]] as well as the [[https://github.com/victronenergy/dbus-mqtt|mqtt github repo]].
  
-MQTT is available both on the local broker on the [[venus-os:start|GX device]], as well as remotely through the secure could connection.+MQTT is available both on the local broker on the [[venus-os:start|GX device]], as well as remotely through the secure cloud connection.
  
 === C) Running your own scripts on the CCGX === === C) Running your own scripts on the CCGX ===