=== Mode 3 with a managed battery === | === Mode 3 with a managed battery === | ||
When using Mode 3 with a managed battery, please note that the maximum discharge current sent by the battery will be ignored. The implemented control loop should take care of discharge limits communicated by the battery. | When using Mode 3 with a managed battery, please note that the maximum discharge current sent by the battery will be ignored. The implemented control loop should take care of discharge limits communicated by the battery. | ||
- | |||
- | The exception to the above rule is a zero discharge limit. If a managed battery requests a zero discharge limit, the Multi will stop discharging the battery. | ||
- | * If grid power is available, the Multi will go into passthru. | ||
- | * If grid power is not available, the Multi will switch off. | ||
The maximum charge current sent by a managed battery is however always heeded and cannot be overruled by the setpoint. | The maximum charge current sent by a managed battery is however always heeded and cannot be overruled by the setpoint. |