Line 48: | Line 48: | ||
* This register has range -32768W to 32767W (scale factor=1). Use register 2703 for a larger range (scale factor=0.01). | * This register has range -32768W to 32767W (scale factor=1). Use register 2703 for a larger range (scale factor=0.01). | ||
- | === b) Enable/ | + | === b) Enable/ |
* 0: disable charging. This setting may be used for time shifting. For example by disabling charging the battery when feeding back to the grid is profitable, and leaving battery capacity for later. | * 0: disable charging. This setting may be used for time shifting. For example by disabling charging the battery when feeding back to the grid is profitable, and leaving battery capacity for later. | ||
Line 57: | Line 57: | ||
* This setting has a higher priority than the //Grid power setpoint//. | * This setting has a higher priority than the //Grid power setpoint//. | ||
- | === c) Enable/ | + | === c) Enable/ |
* 0: disable inverter | * 0: disable inverter | ||
* 100: enabled inverter. Use value 100 here instead of 1 because this setting was originally designed to be used as a percentage. | * 100: enabled inverter. Use value 100 here instead of 1 because this setting was originally designed to be used as a percentage. |