User Tools

Site Tools


ess:design-installation-manual

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
Next revisionBoth sides next revision
ess:design-installation-manual [2019-03-08 14:50] mvaderess:design-installation-manual [2019-04-03 13:27] guy_stewart
Line 410: Line 410:
  
 This sets the point at which power is taken from the grid when the installation is in self-consumption mode. Setting this value slightly above 0W prevents the system from feeding back power to the grid when there is a bit of over-shoot in the regulation. The default value is therefore 50W - but should be set to a higher value on large systems. This sets the point at which power is taken from the grid when the installation is in self-consumption mode. Setting this value slightly above 0W prevents the system from feeding back power to the grid when there is a bit of over-shoot in the regulation. The default value is therefore 50W - but should be set to a higher value on large systems.
 +
  
 ==== 4.4 Venus-device - Scheduled Charging ====  ==== 4.4 Venus-device - Scheduled Charging ==== 
Line 604: Line 605:
  
 (This 0.1 V is the threshold for 12 V systems; for 24 V the threshold is 0.2 V above; and for 48 V it is 0.4V above.) (This 0.1 V is the threshold for 12 V systems; for 24 V the threshold is 0.2 V above; and for 48 V it is 0.4V above.)
 +
 +==== 6.5 ESS Battery Status Code Numbers ====
 +
 +In addition to the charger states (Bulk/Absorption/Float), there are additional Discharging and Sustain codes that provide at-a-glance information on the Pages Overview of GX display. 
 +
 +{{:ess:victron_-_ess_codes.jpg?direct}}
 +
 +The key for these codes is:
 +
 +  * #1: SOC is low
 +  * #2: BatteryLife is active
 +  * #3: BMS disabled charging
 +  * #4: BMS disabled discharge
 +  * #5: Slow Charge in progress (part of BatteryLife, see above)
 +  * #6: User configured a charge limit of zero.
 +  * #7: User configured a discharge limit of zero.
 +
 +
 ===== 7. Phase compensation - further information ===== ===== 7. Phase compensation - further information =====
  
Line 879: Line 898:
 ===== DISQUS ===== ===== DISQUS =====