energy-meters:start [2018-11-30 22:59] mvaderenergy-meters:start [2019-01-22 10:16] – external edit 127.0.0.1
Line 1: Line 1:
 ====== Energy Meters start page ===== ====== Energy Meters start page =====
  
-At Victron Energy, we stock several types of Energy Meters depending on the application.  +At Victron Energy, we stock several types of Energy Meters.
-  * ET112 for single phase monitoring (including a single phase inverter in a 3 phase system) +
-  * ET340 for multi-phase installations +
-  * EM24 for 3 phase monitoring only.+
  
-The Energy Meters are used in systems with a Venus-device. To measure the output of a grid inverter (more info in the Venus-OS manual [[https://www.victronenergy.com/live/ccgx:start#measuring_pv_inverter_output|here]]. Or as a Grid Meter in an ESS installation, more information in the [[https://www.victronenergy.com/live/ess:design-installation-manual|ESS manual]].+The Energy Meters are used in systems with a Venus-device. To measure the output of a PV inverter (more info in the Venus-OS manual [[https://www.victronenergy.com/live/ccgx:start#measuring_pv_inverter_output|here]]. Or as a Grid Meter in an ESS installation, more information in the [[https://www.victronenergy.com/live/ess:design-installation-manual|ESS manual]].
  
 ===== 1. Selection guide ===== ===== 1. Selection guide =====
 +
 +=== First decide if you need single- or three phase meters ===
 +
 +For a three phase utility connection, use a three phase meter. For a three phase PV Inverter, use a three phase meter as well. For a single phase utility connection, use a single phase meter. And in an installation with a single phase utility connection, that also has a PV Inverter that needs measuring with a Victron meter, then you can use Rutger 2 pieces of ET112; or use the ET340.
 +
 +=== Now, based on current, select the model ===
 ^ Requirement                       ^ Type  ^ Solution                                         ^^^ ^ Requirement                       ^ Type  ^ Solution                                         ^^^
 ^ :::                               ^ :::   ^ Part number  ^ Model ^ Specs                        ^ :::                               ^ :::   ^ Part number  ^ Model ^ Specs                       
 | Single phase up to 100A           | Shunt | REL300100000 | ET112 | 1 phase - max 100A          | | Single phase up to 100A           | Shunt | REL300100000 | ET112 | 1 phase - max 100A          |
 | Three phase up to 65A/phase       | Shunt | REL200100000 | EM24  | 3 phase - max 65A/phase     | | Three phase up to 65A/phase       | Shunt | REL200100000 | EM24  | 3 phase - max 65A/phase     |
-| Single phase more than 100A/phase | CT    | See three phase CT solution                      |||+| Single phase more than 100A/phase | CT    | Not available, use the three phase CT solution                      |||
 | Three phase more than 65A/phase   | CTs   | Carlo Gavazzi EM24DINAV53DISX (see FAQ Q8)       ||| | Three phase more than 65A/phase   | CTs   | Carlo Gavazzi EM24DINAV53DISX (see FAQ Q8)       |||
  
Line 37: Line 40:
   * [[et112|REL300100000 - ET112 - 1 phase - max 100A]]   * [[et112|REL300100000 - ET112 - 1 phase - max 100A]]
   * [[et340|REL300300000 - ET340 - 3 phase max 65A/phase]]   * [[et340|REL300300000 - ET340 - 3 phase max 65A/phase]]
- 
-No longer used: 
   * [[em24|REL200100000 - EM24 - 3 phase max 65A/phase]]   * [[em24|REL200100000 - EM24 - 3 phase max 65A/phase]]
  
Line 45: Line 46:
  
 === Q1: Can I combine three ET112s for a three phase system? === === Q1: Can I combine three ET112s for a three phase system? ===
-No.+No. Use a real three-phase meter.
  
 === Q2: Can I use other meters, for example from other brands? === === Q2: Can I use other meters, for example from other brands? ===
Line 99: Line 100:
 This is also how Victron’s phase compensation feature works, to make the most of the cost savings for an ESS system when there is a differential in generation and load across different phases. This is also how Victron’s phase compensation feature works, to make the most of the cost savings for an ESS system when there is a differential in generation and load across different phases.
  
-===== DISQUS =====+=== Q10: Can I use an isolated USB-RS485 interface? ===
  
 +Yes. The interfaces we sell are non isolated; suitable for most use cases.
 +
 +In case an isolated one is needed; purchase it dirsctly from [[https://hjelmslund.eu/default.asp|Hjelmslund Electronics]].
 +
 +  * USB485-STIXL : Isolated USB to RS485 converter
 +