- | ===== 3. Connection to CCGX === | + | ===== 3. Connection to GX device |
==== Option A: wireless Zigbee connection ==== | ==== Option A: wireless Zigbee connection ==== | ||
Line 75: | Line 75: | ||
== note on GX firmware versions: == | == note on GX firmware versions: == | ||
for the new type Zigbee converters, Venus OS v2.54 is the minimum required software version | for the new type Zigbee converters, Venus OS v2.54 is the minimum required software version | ||
- | ==== Option B: Wired connection to CCGX ==== | ||
- | Connect the Energy Meter to the CCGX using the USB to RS485 cable. The RS485 to USB interface cable between the CCGX and the Energy Meter can be extended up to 100 meters; make sure that the extensions of the Data+ (orange) and Data- (yellow) wires form a twisted pair. | + | ==== Option B: Wired connection to GX device ==== |
+ | |||
+ | Connect the Energy Meter to the GX device | ||
^ RS485 Converter ^ Energy meter ^ | ^ RS485 Converter ^ Energy meter ^ | ||
- | | Yellow (Data-) | ||
| Orange (Data+) | | Orange (Data+) | ||
+ | | Yellow (Data-) | ||
| Black (GND) | Terminal 10 | | | Black (GND) | Terminal 10 | | ||
The red, green and brown wire coming out of the USB to RS485 cable are not used. | The red, green and brown wire coming out of the USB to RS485 cable are not used. | ||
+ | |||
+ | == Note on cable length extensions and bus termination == | ||
+ | |||
+ | To ensure signal integrity and robust operation, particularly ensure that; | ||
+ | |||
+ | Extension cabling complies with the minimum cross-sectional area specifications in the USB to RS485 data sheet. | ||
+ | |||
+ | Extension cabling has appropriate shielding and twisted pair cores | ||
+ | |||
+ | The original cable attached to the Victron RS485 to USB interface is reduced to a maximum length of 20cm in installations where the total cable length is over 10m or there are installation/ | ||
+ | |||
+ | Cabling is installed separated/ | ||
+ | |||
+ | All wiring is properly terminated (including unused wires) and properly isolated from weather/ | ||
+ | |||
+ | RS485 networks are traditionally terminated at both ends with 120Ω terminators. This is not required if the cable length is short and you are using the Victron supplied RS485 to USB lengths, but may be required if they are extended for longer cable runs. The ET340 meter has a built in termination resistor that can be enabled by bridging terminals 7 and 9. | ||
+ | |||
+ | For detailed wiring/ | ||
+ | |||