 In most networks the meter will be automatically configured by DHCP when plugged in. For larger installations we recommend configuring a static IP address. This avoids an address change if the DHCP server assigns a different IP address in future. In most networks the meter will be automatically configured by DHCP when plugged in. For larger installations we recommend configuring a static IP address. This avoids an address change if the DHCP server assigns a different IP address in future.
  
-TODODocument process of scanning and configuring meter.+The configuration for Ethernet EM24 meters can be found under Settings -> Modbus TCP devices. The default is to scan for new devices every ten minutes, but a manual scan is also possible. 
 + 
 + {{ :energy-meters:modbus-tcp-devices.png?nolink |}} 
 + 
 +Once a meter is found, it will be shown under Devices. It is also possible to manually define the connection details of a meter, in case scanning does not locate it. 
 + 
 +{{ :energy-meters:modbus-tcp-device-list.png?nolink |}} 
 + 
 +The meter will also show up on the Device List on the GX Device. Accessing it will show the relevant information. 
 + 
 +{{ :energy-meters:modbus-tcp-device-meter.png?nolink |}} 
 + 
 +The role of the meter can also be changed through the Setup menu. The role will be one of Grid meter, PV inverter, or Generator. 
 + 
 +{{ :energy-meters:modbus-tcp-device-setup.png?nolink |}}
  
 == note on GX firmware versions: == == note on GX firmware versions: ==
 To support the ethernet EM24 meters, Venus 2.60 is the minimum firmware required on the GX device. To support the ethernet EM24 meters, Venus 2.60 is the minimum firmware required on the GX device.