-====== MultiPlus Backup only 1600VA / 12 volt ====== 
- 
-=== Introduction === 
-Short story 
- 
-=== Parts === 
-  * 1x - CMP121620000 - [[http://www.victronenergy.com/inverters-chargers/MultiPlus-12v-24v-48v-800va-3kva#datasheet|MultiPlus Compact 12/1600/70-16 230V VE.Bus Inverter/Charger]] 
-  * 2x - BAT412201080 - [[http://www.victronenergy.com/batteries/Gel-and-AGM-batteries|12V/220Ah AGM Deep Cycle Battery ]] 
-  * or - BAT412201100 - [[http://www.victronenergy.com/batteries/Gel-and-AGM-batteries|12V/220Ah Gel Deep Cycle Battery]] 
-  * 2x - Battery link cables 
- 
-{{ :drafts:sa_system:1600w multiplus-simple.jpg?nolink&500 |}} 
- 
-=== optional === 
-  * DMC000200000R - Digital Multi Control 200/200A GX (90º RJ45) Retail  
-  * BPP000300100R - Color Control GX Retail  
- 
-{{ :drafts:sa_system:1600w multiplus-option.jpg?nolink&700 |}} 
- 
-== How long is the backup time? == 
-Explain what it solves: 
-  * Load shedding period: High power 1000W DoD 50% SoC about 2 hours 
-  * At night: Low power 250W DoD 50% SoC about 8 hours 
- 
-== Notes for batteries: == 
-  * We recommend deep-cycle GEL or AGM batteries. At least 200Ah per block.   
-  * Cable cross section: xxxx mm2  MCO: welke mm2 / stroom rating welke lengte 
-\\  
-== VE.Configure Settings == 
-plaatjes toevoegen!! \\ 
-[[http://www.victronenergy.com/support-and-downloads/software|software download VE.Configure]] \\ 
-[[http://www.victronenergy.com/live/updating_firmware:updating_ve.bus_products|Updating VE.Bus products]] \\ 
- 
-settings: 
-  * Disable overrule by remote 
-  * Change DC input low shutdown to 10.8 volts 
-  * Change DC input low restart to 11.8 volts 
-  * Change DC input low pre-alarm to ??.? volts 
-  * Charge current can be left at standard setting. 
-  * Enable battery monitor and set correct Battery capacity 
-{{ :drafts:sa_system:veconf-inv.jpg?nolink&440|}} 
-{{ :drafts:sa_system:veconf-batmon.jpg?nolink&430 |}} 
- 