drafts:pylontest [2018-12-27 13:17] – guy_stewart | drafts:pylontest [2018-12-27 15:49] – guy_stewart | ||
---|---|---|---|
Line 55: | Line 55: | ||
- | ==== 1.6 Minimum Battery Sizing Recommendations | + | ===== 2. Minimum Battery Sizing Recommendations |
Each US2000B Plus battery module is approximately 50Ah at 48V, can provide 25A continuous charge and discharge and 100A peak for 1 minute. | Each US2000B Plus battery module is approximately 50Ah at 48V, can provide 25A continuous charge and discharge and 100A peak for 1 minute. | ||
Line 80: | Line 80: | ||
- | ==== 2. Wiring of CAN-bus cable between B-Box and Venus-device ==== | + | ===== 3. Wiring of CAN-bus cable between B-Box and Venus-device |
- | Use the //VE.Can to CAN-bus BMS type B Cable//, part number ASS030720018. Plug the side which is labeled Battery BMS into the Pylontech CAN port. Plug the side labeled Victron VE.Can into the [[venus-os: | + | You can connect multiple battery modules together to form a single large battery by connecting the RJ-45 cable supplied by Pylontech using the link ports on the battery. This is shown in more detail in the [[https:// |
+ | |||
+ | The batteries will automatically detect and link to each other, no adjustment of dip switches or software changes are necessary on the batteries. | ||
+ | |||
+ | The battery with the empty link port 0 is the master battery. Using the //VE.Can to CAN-bus BMS type B Cable//, part number ASS030720018, Plug the side which is labeled Battery BMS into the Pylontech CAN port of the master battery. Plug the side labeled Victron VE.Can into the [[venus-os: | ||
Then, plug a [[https:// | Then, plug a [[https:// | ||
Line 88: | Line 92: | ||
More information about the cable can be found in [[battery_compatibility: | More information about the cable can be found in [[battery_compatibility: | ||
- | Without properly connecting this cable, the battery will not show up on the display of the [[venus-os: | + | Without properly connecting this cable, the battery will not show up on the display of the [[venus-os: |
It is important to ensure this connection and display of the battery on the [[venus-os: | It is important to ensure this connection and display of the battery on the [[venus-os: | ||
- | ==== 4. VEConfigure settings ==== | + | ===== 4. VEConfigure settings |
This section presumes familiarity with [[https:// | This section presumes familiarity with [[https:// | ||
Line 160: | Line 164: | ||
If operation is attempted outside the operating range, the battery will disconnect to protect itself. | If operation is attempted outside the operating range, the battery will disconnect to protect itself. | ||
- | ==== 5. Venus-device Configuration ==== | + | ===== 5. Venus-device Configuration |
* Select the //CAN-bus BMS (500 kbit/s)// CAN-profile in the CCGX. Menu path: //Settings -> Services -> CAN-profile// | * Select the //CAN-bus BMS (500 kbit/s)// CAN-profile in the CCGX. Menu path: //Settings -> Services -> CAN-profile// | ||
Line 187: | Line 191: | ||
===== 7. Example Wiring Diagram ===== | ===== 7. Example Wiring Diagram ===== | ||
- | {{: | + | {{ : |
===== 8. Troubleshooting ===== | ===== 8. Troubleshooting ===== | ||
Line 212: | Line 216: | ||
Check the Max Charge Voltage parameter. This voltage parameter is sent, together with the other three parameters, | Check the Max Charge Voltage parameter. This voltage parameter is sent, together with the other three parameters, | ||
+ | |||
+ | ===== 9. FAQ ===== | ||
+ | |||
+ | **The maximum charge and discharge current is limited to 25A, but the data sheet tells me the maximum is 100A.** | ||
+ | |||
+ | The maximum current is limited to keep the battery healthy and reach the 10 year guarantee. In off-grid, the inverter can draw more than the 25A limit to run the loads, make sure you have sufficient batteries installed to keep the load per battery around this limit. | ||
+ | |||
+ | **After charging the battery the charge current often changes between 0A and 25A.** | ||
+ | This is caused by cell balancing inside the battery. This happens with new batteries and after a deep discharge. | ||
+ | |||
- | ===== 11. Further Information ===== | + | ===== 10. Further Information ===== |
For information about where to buy or find suitably qualified installers, visit the [[https:// | For information about where to buy or find suitably qualified installers, visit the [[https:// | ||
Further community discussion about installing and using Pylontech and Victron can found at [[https:// | Further community discussion about installing and using Pylontech and Victron can found at [[https:// |