drafts:error_codes [2020-09-11 09:53] rvanzundertdrafts:error_codes [2020-09-16 13:49] rvanzundert
Line 151: Line 151:
 This error will not auto-reset. Check the installation and restart the unit using the power-switch. This error will not auto-reset. Check the installation and restart the unit using the power-switch.
  
-==== Err 50 - Inverter overload ====+==== Err 50, Err 52 - Inverter overload, Inverter peak current ====
 Some loads like motors or pumps draw large inrush currents in a start-up situation. In such circumstances, it is possible that the start-up current exceeds the over current trip level of the inverter. In this case the output voltage will quickly decrease to limit the output current of the inverter. If the over current trip level is continuously exceeded, the inverter will shut down: wait 30 seconds and then restart. Some loads like motors or pumps draw large inrush currents in a start-up situation. In such circumstances, it is possible that the start-up current exceeds the over current trip level of the inverter. In this case the output voltage will quickly decrease to limit the output current of the inverter. If the over current trip level is continuously exceeded, the inverter will shut down: wait 30 seconds and then restart.
 +
 +The Inverter can supply more power than the nominal power level for a short time. If the time is exceed the inverter stops. 
  
 After three restarts followed by another overload within 30 seconds of restarting, the inverter will shutdown and remain off. To restart the inverter, switch it Off, then On. After three restarts followed by another overload within 30 seconds of restarting, the inverter will shutdown and remain off. To restart the inverter, switch it Off, then On.
Line 163: Line 165:
  
 The inverter will restart after 30 seconds. The inverter will not stay off after multiple retries. The inverter will restart after 30 seconds. The inverter will not stay off after multiple retries.
- 
-==== Err 52 - Inverter excessive current ==== 
-If the error persists reduce the load on the AC out terminal by switching off or disconnecting appliances. 
- 
-This error will auto-restart after 30s, after 3 attempts the unit shuts down and a power-cycle is needed to restart the unit. 
  
 ==== Err 53, Err 54 - Inverter output voltage ==== ==== Err 53, Err 54 - Inverter output voltage ====
Line 174: Line 171:
  
 ==== Err 57 - Inverter ac voltage on output ==== ==== Err 57 - Inverter ac voltage on output ====
-There is already AC voltage on the AC out terminal before switching on the inverter. Check if the AC out is not connected to a mains outlet or to another inverter.+There is already AC voltage on the AC out terminal before switching on the inverter. Check that the AC out is not connected to a mains outlet or to another inverter.
  
 This error will not auto-reset. Check the installation and restart the unit using the power-switch. This error will not auto-reset. Check the installation and restart the unit using the power-switch.