Line 7: Line 7:
 It consists of the following modules: It consists of the following modules:
  
-  * Lynx Power In +  * [[https://www.victronenergy.com/dc-distribution-systems/lynx-power-in|Lynx Power In]] 
-  * Lynx Shunt +  * [[https://www.victronenergy.com/dc-distribution-systems/lynx-shunt-ve-can|Lynx Shunt]] 
-  * Lynx Distributor+  * [[https://www.victronenergy.com/dc-distribution-systems/lynx-distributor|Lynx Distributor]] 
 + 
 +You can use the Lynx Distributor or Lynx Power In without the Lynx Shunt.
  
 Information on these 3 parts can be found below, but also in this [[https://www.victronenergy.com/upload/documents/Manual-Lynx-Ion-+-Shunt-and-24V-180Ah-Lithium-batteries-EN.pdf|manual]] Information on these 3 parts can be found below, but also in this [[https://www.victronenergy.com/upload/documents/Manual-Lynx-Ion-+-Shunt-and-24V-180Ah-Lithium-batteries-EN.pdf|manual]]
Line 20: Line 22:
 {{:drafts:lynx_power_in.png?200|}} {{:drafts:lynx_power_in.png?200|}}
  
-The lynx power in module is used to connect batteries. It contains a negative and positive DC bus-bar with M8 bolts to connect batteries cables to.+The lynx power in module is used to connect batteries. It contains a negative and positive DC bus-bar with M8 bolts in which to connect batteries cables.
  
  
Line 29: Line 31:
  
 The Lynx shunt contains a positive bus-bar with space to mount a fuse and a negative bus-bar with a shunt. The Lynx shunt contains a positive bus-bar with space to mount a fuse and a negative bus-bar with a shunt.
-It also contains battery monitor electronics. The Lynx shunt can send via the VE.CAN bus battery motoring information to a CCGX or VGX or to a third party can bus monitoring system, such as a NMEA2000 (check with Johannes). The CCGX, VGX or third party display acts as battery monitor display and is also used to set up the built-in batter monitor. +It also contains battery monitoring electronics. The Lynx shunt can send via the VE.CAN bus battery monitoring information to a CCGX or VGX or to a third party CANbus monitoring system, such as a NMEA2000. The CCGX, VGX or third party display acts as battery monitor display and is also used to set up the built-in battery monitor.
- +
-The Lynx shunt is available in two models:  +
-  * VE.CAN +
-  * VE.NET (depreciated)+
  
 +The Lynx shunt is available with a VE.Can connection. A previous model had a VE.Net connection and is now discontinued.
 ==== Fuse ==== ==== Fuse ====
  
Line 69: Line 68:
  
 It is important that in cases where batteries are combined, and there is the opportunity for current to flow from one connection to another in fault, that there is sufficient and robust circuit protection. It is important that in cases where batteries are combined, and there is the opportunity for current to flow from one connection to another in fault, that there is sufficient and robust circuit protection.
 +
 +For example, the BYD Lithium IP55 cabinets. 
  
 In this case the 4 module battery cabinets are each protected by individual 85A circuit breakers and also collectively protected by a 125A circuit breaker at the cabinet end. In this case the 4 module battery cabinets are each protected by individual 85A circuit breakers and also collectively protected by a 125A circuit breaker at the cabinet end.
Line 80: Line 81:
 Without the 125A bus bar MEGA fuse. There is the possibility of the battery take off cables fault that the 125A cabinet circuit breaker trips, but that the fault is continued by the supply of the other batteries (up to their combined 375A) and this exceeds the current rating of the cable to the fault and starts a fire. Without the 125A bus bar MEGA fuse. There is the possibility of the battery take off cables fault that the 125A cabinet circuit breaker trips, but that the fault is continued by the supply of the other batteries (up to their combined 375A) and this exceeds the current rating of the cable to the fault and starts a fire.
  
-This is an unlikely scenario, but consequences of a fire in an energy storage situation are so serious that it is the required level of protection.+This is an unlikely scenario, but consequences of a fire in an energy storage situation are so serious that it is a recommended level of protection.
  
  
Line 91: Line 92:
  
 ==== Fuses ==== ==== Fuses ====
-Uses MEGA fuses. Please note that some MEGA fuses are only rated to 36Volt (suitable for 24V systems), You must use 64V rated fuses for 48V systems.+Uses MEGA fuses. Please note that some MEGA fuses are only rated to 36Volt (suitable for 24V systems), You must use 58/64V rated fuses for 48V systems.
 ==== Installation ==== ==== Installation ====
  
Line 130: Line 131:
  
 [[https://static1.squarespace.com/static/562bc73de4b0908330f67ee0/t/59d3f48fe9bfdf11a11df040/1507062949908/Redwood-+38RL-Victron.jpg|Closeup Photo of Lynx]] [[https://static1.squarespace.com/static/562bc73de4b0908330f67ee0/t/59d3f48fe9bfdf11a11df040/1507062949908/Redwood-+38RL-Victron.jpg|Closeup Photo of Lynx]]
- 
- 
- 