Line 67: | Line 67: | ||
If you wish to use the fuse indication LEDs on the Lynx Distributor, | If you wish to use the fuse indication LEDs on the Lynx Distributor, | ||
- | RJ11 fly leads are used to connect the Lynx Shunt to the Distributor. This RJ11 cable is supplied with the Distributor in the box. There are two ports on the Lynx Shunt, and it is possible to use either. | + | RJ10 fly leads are used to connect the Lynx Shunt to the Distributor. This RJ10 cable is supplied with the Distributor in the box. There are two ports on the Lynx Shunt, and it is possible to use either. |
When all is OK, only the central LED is green; when a fuse has blown (or is missing) the central and blow fuse circuit LEDs turn red. If you are not using all connection points in your DC distribution, | When all is OK, only the central LED is green; when a fuse has blown (or is missing) the central and blow fuse circuit LEDs turn red. If you are not using all connection points in your DC distribution, | ||
- | |||
- | A future upgrade is planned to also send info back to the GX device over the VE-can, but is not yet implemented. | ||
- | |||
==== Fuses ==== | ==== Fuses ==== | ||
Uses MEGA fuses. Please note that some MEGA fuses are only rated to 36Volt (suitable for 24V systems), You must use 58/64V rated fuses for 48V systems. | Uses MEGA fuses. Please note that some MEGA fuses are only rated to 36Volt (suitable for 24V systems), You must use 58/64V rated fuses for 48V systems. | ||
Line 93: | Line 90: | ||
A - That’s for manual settings, please don’t touch as the system will auto configure (up to 32 battery’s ) | A - That’s for manual settings, please don’t touch as the system will auto configure (up to 32 battery’s ) | ||
- | Q - The Distributor has a 6-pin header block. What is it for? | ||
- | |||
- | A - In the future, the read out of fuses, but this is not supported yet. | ||