 ==== 1.1 ES Range (Residential) ==== ==== 1.1 ES Range (Residential) ====
  
-^ Model ^ Total Energy (kWh) ^ Usable Energy @ 80% DOD (kWh) ^ Nominal Voltage ^ Nominal Capacity ^ Max Charge (A) ^ Max Discharge (A) ^ Rec. Inverter ^+^ Model ^ Total Energy (kWh) ^ Usable Energy @ 80% DOD (kWh) ^ Nominal Voltage ^ Nominal Capacity ^ Max Charge (A) ^ Max Discharge (A) ^ Rec. Inverter (per 1 unit) ^
 | ES5.4K  | 5.4  | 4.32 | 51.2V | 106 Ah | 100  | 125  | 5 kVA  | | ES5.4K  | 5.4  | 4.32 | 51.2V | 106 Ah | 100  | 125  | 5 kVA  |
-| ES7.4K  | 7.4  | 5.9  | 51.2V | —      | 100  | 125  | —      +| ES7.4K  | 7.4  | 5.9  | 51.2V | —      | 100  | 125  | 5 kVA    
-| ES9.4K  | 9.4  | 7.5  | 51.2V | —      | 160  | 200  | —      | +| ES9.4K  | 9.4  | 7.5  | 51.2V | —      | 160  | 200  | 10 kVA      | 
-| ES12K   | 12.0 | 9.6  | 51.2V | —      | 160  | 200  | —      |+| ES12K   | 12.0 | 9.6  | 51.2V | —      | 160  | 200  | 10 kVA      |
 | ES18K   | 18.0 | 14.4 | 51.2V | 352 Ah | 320  | 400  | 15 kVA | | ES18K   | 18.0 | 14.4 | 51.2V | 352 Ah | 320  | 400  | 15 kVA |
-| ES24K   | 24.0 | 19.2 | 51.2V | —      | 320  | 400  | —      |+| ES24K   | 24.0 | 19.2 | 51.2V | —      | 320  | 400  | 15 kVA     |
  
  
-Nominal voltage for all ES Range models is **51.2V** (16 cells × 3.2V per cell). "48V" is the conventional system voltage designation used in Victron and inverter sizing. Usable energy is calculated at 80% DOD. Capacity in Ah and recommended inverter size are confirmed for ES5.4K and ES18K; refer to individual datasheets for remaining models.+Nominal voltage for all ES Range models is **51.2V** (16 cells × 3.2V per cell). "48V" is the conventional system voltage designation used in Victron and inverter sizing. Usable energy is calculated at 80% DOD. 
  
  
Line 44: Line 44:
  
   * **GX Devices:** Cerbo GX, Cerbo-S GX, Ekrano GX   * **GX Devices:** Cerbo GX, Cerbo-S GX, Ekrano GX
-  * **Inverter/Chargers:** VE.Bus Inverter/Chargers, & RS range, (minimum firmware: see Section 3)+  * **Inverter/Chargers:** VE.Bus Inverter/Chargers, & RS range,  
 +   * EasySolar GX, MultiPlus-II GX - note these GX inverters include an integrated GX device and do not require an additional seperate GX device (minimum firmware: see Section 3)
   * **Solar Chargers:** SmartSolar MPPT (minimum firmware: see Section 3)   * **Solar Chargers:** SmartSolar MPPT (minimum firmware: see Section 3)
   * **Monitoring:** Victron VRM Portal (SOC, cell voltages, temperatures, alarms)   * **Monitoring:** Victron VRM Portal (SOC, cell voltages, temperatures, alarms)
Line 267: Line 268:
   * If the keepalive message is not received **and** the minimum cell voltage drops to or below **2,800 mV**, the hardware breaker will trip to protect the battery cells   * If the keepalive message is not received **and** the minimum cell voltage drops to or below **2,800 mV**, the hardware breaker will trip to protect the battery cells
  
-==== 11.2 Black Start Test Results ==== 
- 
-Black start testing was conducted in accordance with the four official testing protocols provided by Victron R&D. The StorageDOCK ES5.4K passed all required tests. 
- 
-=== Black Start from PV Input === 
- 
-ESS Mode during test: **Keep batteries charged** | Grid feed-in DC-coupled PV: **OFF** 
- 
-^ Parameter ^ Value ^ 
-| PV Input at Test Start | 120V @ 8A | 
-| Battery SOC at Start   | 0% (full BMS shutdown had occurred) | 
-| SOC at Inverter Boot   | 6% | 
-| SOC When Next Test Commenced | 11% | 
- 
-**VRM telemetry – at 0% SOC (pre-recovery):** 
- 
-^ Measurement ^ Value ^ 
-| Battery Voltage  | 47.67V | 
-| Min Cell Voltage | 2.62V  | 
-| Max Cell Voltage | 3.09V  | 
- 
-**VRM telemetry – at 11% SOC (post-recovery):** 
- 
-^ Measurement ^ Value ^ 
-| Battery Voltage  | 51.92V | 
-| Min Cell Voltage | 3.21V  | 
-| Max Cell Voltage | 3.25V  | 
- 
-=== Black Start from AC Input === 
- 
-^ Parameter ^ Value ^ 
-| Starting SOC | 11% | 
-| SOC at BMS Shutdown | 5% | 
-| SOC at Inverter Boot (after AC connected) | 6% | 
-| Final SOC Achieved | 99% | 
- 
-**VRM telemetry – at 5% SOC (pre-recovery):** 
- 
-^ Measurement ^ Value ^ 
-| Battery Voltage  | 46.93V | 
-| Min Cell Voltage | 2.55V  | 
-| Max Cell Voltage | 3.07V  | 
- 
-**VRM telemetry – at 99% SOC:** 
- 
-^ Measurement ^ Value ^ 
-| Battery Voltage  | 54.22V | 
-| Min Cell Voltage | 3.38V  | 
-| Max Cell Voltage | 3.40V  | 
- 
-**VRM telemetry – at 100% SOC (30 minutes after reaching 99%):** 
- 
-^ Measurement ^ Value ^ 
-| Battery Voltage  | 55.62V | 
-| Min Cell Voltage | 3.46V  | 
-| Max Cell Voltage | 3.50V  | 
- 
----- 
  
 ===== 12. Cell Identification in the GX Device ===== ===== 12. Cell Identification in the GX Device =====