User Tools

Site Tools


battery_compatibility:redflow_zcell

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Next revision
Previous revision
battery_compatibility:redflow_zcell [2016-06-10 23:57] – created mvaderbattery_compatibility:redflow_zcell [2020-04-28 07:59] (current) – [For on-grid sites using ESS (not required off-grid)] simonhackett
Line 1: Line 1:
-====== Victron & Redflow ZCell ======+====== Victron & Redflow ZBM2 / ZCell ======
  
-https://www.zcell.com/+[[http://www.zcell.com|ZCell]] is a packaged bundle of the [[http://www.redflow.com|Redflow ZBM2 battery]] inside an external-rated enclosure, supplied with the Redflow CANbus BMS. 
  
-Note that the ZCell is currently only available in Australia.+The Redflow ZBM2 battery is a 48V 10kWh DC Zinc-Bromide hybrid flow battery that is installed in parallel-wired DC clusters. It is the worlds smallest commercial flow battery. It uses the Redflow CANbus BMS as the control and communications interface for the battery system.
  
-==== Compatible Victron products ==== +An overview of the technical specifications of this battery are provided here: 
-  * All 48V Multis and Quattros +https://redflow.zendesk.com/hc/en-us/articles/360025493531-Technical-specification-overview-for-the-Redflow-ZCell-ZBM2-battery
-  * All 48V solar chargers +
-  * Adding a Color Control GX is recommended but not required+
  
-==== Charge profile ===== +**Important** information about installing and configuring ZBM2 systems with Victron Energy products is provided here:  
-  - Charge voltage 57.6V (up to 50 Amps per battery, and current per battery self-limits if you limit the voltage) +https://redflow.zendesk.com/hc/en-us/articles/360025202052-Installation-guide-to-connecting-a-Redflow-battery-array-to-a-Victron-Energy-system
-  Linear charge all the way from empty to full (all charge phases are the same same ‘flat’ voltage). +
-  No need for any sort of battery ‘conditioning’ cycling at all+
  
-Charger settings: +==== Compatible Victron products ==== 
-  - Set both absorption and float voltage to 57.6V +  * All 48V Multis and Quattros  
-  - disable storage mode. +  * All 48V solar chargers that are compatible with DVCC (all except the older 'vertical' shaped CANBus units
-  - disable bulk protection(?? Simon?+  * Any GX unit running current firmware with DVCC enabled and using the CANBus interface.  
-  using Assistants, such as the Hub-4 Assistant, is possible but not required.+==== ZBM2 / ZCell Characteristics ===== 
 +  * Low fire risk: No exothermic reaction if exposed to fireand with water-based fluid electrolyte that is intrinsically fire-retardant 
 +  * Designed to be charged up to 100% SOC and discharged right down to 0% SOC (and zero volts) on a daily basis with no damage and while maintaining full energy cycle output capacity over the battery lifetime
  
-===== Color Control GX =====+==== ZBM2 / ZCell Configuration ===== 
 +  * Clusters of multiple Redflow batteries are automatically controlled using the Redflow BMS to orchestrate their discharge cycles and maintenance cycles for maximum energy availability and maximum operating efficiency and effectiveness. 
 +  * Interface to the GX from the Redflow BMS using CANBus just like any other modern 'smart' battery 
 +  * Always turn on DVCC mode in the GX to allow voltage and current settings to be controlled via CANBus by the BMS (no need to set any battery voltage or current limits in VE.Configure)
  
-Follow [[https://faq.zcell.com/content/10/55/en-us/enabling-state_of_charge-update-using-modbus_tcp-with-a-ccgx.html|this]] procedure to show the ZCell SOC on the Color Control GX.+ ==== For on-grid sites using ESS (ESS is not required off-grid)  ===== 
  
-Also see this other FAQ item on the ZCell website: +  *  Select the Redflow ZCell battery type in the ESS Assistant when setting it up (available in ESS Assistant versions since April 2020) 
-https://faq.zcell.com/content/10/54/en-us/automatic-start-for-a-multiplus-connected-to-a-powered_down-ccgx.html+  * Use the ESS mode "Optimised (without BatteryLife)" to allow full-depth discharge of the battery regularly 
 +  * On single battery setups the ESS 'MinSoC' must be set to 0% to avoid stalling the ZCell maintenance cycle. 
 +  
 +===== DISQUS ===== 
 +~~DISQUS~~
  
-The Color Control GX does not yet have the option to read and show any other ZCell parameters. 
- 
-===== Disqus ===== 
-~~DISQUS~~ 
battery_compatibility/redflow_zcell.1465595832.txt.gz · Last modified: 2016-06-10 23:57 by mvader