User Tools

Site Tools


battery_compatibility:redflow_zbm

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Next revision
Previous revision
battery_compatibility:redflow_zbm [2016-06-10 23:14] – created mvaderbattery_compatibility:redflow_zbm [2021-03-20 02:50] (current) guystewart
Line 1: Line 1:
 ====== Victron & Redflow ZBM ====== ====== Victron & Redflow ZBM ======
  
 +http://www.redflow.com/
  
-===== Charge profile ===== +==== Compatible Victron products ==== 
-  - Charge voltage 57.6V (up to 50 Amps per battery, and current per battery self-limits if you limit the voltage) +  * All 48V Multis and Quattros.  
-  - Linear charge all the way from empty to full (all charge phases are the same - same ‘flat’ voltage). +  * All 48V solar chargers 
-  - No need for any sort of battery ‘conditioning’ cycling at all+  * Adding a GX device is STRONGLY recommended, but not required
  
-Charger settings+==== Charge profile ===== 
-  Set both absorption and float voltage to 57.6V + 
-  - disable storage mode. +See the information for the Redflow ZCell at https://www.victronenergy.com/live/battery_compatibility:redflow_zcell 
-  - disable bulk protection(??)+ 
 + 
 +===== GX Device Connect ===== 
 + 
 +Redflow ZBM batteries can be directly interfaced to the GX device (Cerbo GX) for monitoring and control (see below). 
 + 
 +Alternatively one or more ZBM batteries can be used with the Redflow/ZCell Battery Management System (BMS). That results in keeping all ZBM specific information and control inside the BMS and sending only general summary data (such as system State of Charge) up to the GX device using a TCP/IP connection. See the Redflow ZCell page at the link above for more information. 
 + 
 +For the direct-attach option, the GX device has built in support for directly attaching to one or more Redflow ZBM batteries using the built in Modbus connection and protocol. 
 + 
 +{{ :battery_compatibility:image.png?direct |}} 
 + 
 +  - Connect the GX device to each battery in the system via Modbus-RS485, (our RS485 to USB interface is needed for that, ASS0305700xx)
 +  - Monitoring the battery: battery voltage, current, state of charge, temperature and many more ZBM specific alarms and flags. 
 +  - Control the battery: set it to run mode, initiate a maintenance cycle, clear the alarms and more
 +  - Configure the battery: the GX device will automatically assign a unique Modbus address to each battery. Just make sure to connect them, slowly, one by one. After connecting one, wait for it to show up on the GX device, and then connect the next one. Additionally, it is possible to manually change the Modbus address of the battery. 
 + 
 +===== DISQUS ===== 
 +~~DISQUS~~
  
-===== Color Control GX ===== 
battery_compatibility/redflow_zbm.1465593279.txt.gz · Last modified: 2016-06-10 23:14 by mvader