-====== Victron & Pylontech US2000, US3000 and Phantom-S =====+====== Victron & Pylontech UP2500, US2000, US3000, US2000C, US3000C, US5000, US5000B, US5000C, Pelio-L, UP5000, Phantom-S, Force-L1 & L2 =====
  
 The combination of Victron products with Pylontech lithium batteries has been tested and certified by the Victron and Pylontech R&D departments.  The combination of Victron products with Pylontech lithium batteries has been tested and certified by the Victron and Pylontech R&D departments. 
Line 7: Line 7:
 This manual is intended to be used in conjunction with the product manual supplied by Pylontech. It provides additional and specific information regarding integration with Victron systems.  This manual is intended to be used in conjunction with the product manual supplied by Pylontech. It provides additional and specific information regarding integration with Victron systems. 
  
-The Pylontech includes a Battery Management System (BMS) with each battery module. This interfaces with the Victron [[venus-os:start|Venus-device]] and can support multiple battery modules connected in parallel.+The Pylontech includes a Battery Management System (BMS) with each battery module. This interfaces with the Victron [[venus-os:start|GX device]] and can support multiple battery modules connected in parallel.
  
 ===== 1. Product & system compatibility ===== ===== 1. Product & system compatibility =====
Line 13: Line 13:
 {{:battery_compatibility:pylontech_battery.png?direct&600|}} {{:battery_compatibility:pylontech_battery.png?direct&600|}}
  
-^  Battery ^  US2000 (Plus) ^ US3000 ^ Force-L1 ^ +^  Battery ^ UP2500* ^ US2000 (Plus/C) ^ US3000(C) ^ UP5000 & US5000(B) ^ US5000C & Pelio-L ^ Force-L1 & L2 
-|  Module capacity|  2.4 kWh |  3.5 kWh| 3.55 kWh |+| Nominal voltage        |  24V  |  48V  |  48V  |  48V  | 48V  | 48V | 
 +Module capacity         2.55 kWh  |  2.4 kWh  |  3.5 kWh |  4.8 kwh  | 5.12kWh | 3.55 kWh | 
 +| Minimum Venus firmware | v2.40 | v2.20 | v2.20 | v2.20 | **imminent** | v2.20 | 
 + 
 +* Note that UP2500 came in two versions, UP2500N__A__01V00101 does not have a CANBUS port, and IS NOT supported by Victron. UP2500N__B__01V00101 released April 2020 has the CANBUS port and IS supported.
  
 === 1.1 Offgrid, Backup and Energy Storage Systems are possible === === 1.1 Offgrid, Backup and Energy Storage Systems are possible ===
Line 20: Line 24:
 Victron + Pylontech can be used for the following system types: Victron + Pylontech can be used for the following system types:
  
-  * Off-grid +  * Off-grid [[https://www.victronenergy.com/live/ccgx:start#dvcc_-_distributed_voltage_and_current_control|(DVCC)]] 
-  * Grid Backup +  * Grid Backup [[https://www.victronenergy.com/live/ccgx:start#dvcc_-_distributed_voltage_and_current_control|(DVCC]] or [[ess:start|ESS)]] 
-  * Energy Storage Systems - Self Consumption ([[ess:start|]])+  * Energy Storage Systems (ESS) - Self Consumption ([[ess:start|]]) 
 + 
 + 
 +=== 1.2 A GX-device is required, eg Cerbo GX or Venus GX (VGX) === 
  
 +It is essential to use the CAN-bus connection of the [[venus-os:start|GX device]] (e.g. Cerbo GX) - this communicates the keep-alive signal, charge and discharge limits, error codes and state of charge (SOC %) between the batteries and the system. 
  
-=== 1.2 A GX-device is required, eg Color Control GX (CCGX) or Venus GX (VGX) === +For new systems, the minimum required firmware version for the [[https://www.victronenergy.com/live/venus-os:start|GX Device (e.g. Cerbo GX ]] is v2.42. It is highly recommended to use the latest firmware version on all connected devices, including the GX device Inverter/Charger and MPPTs. There are regular updates to improve performance and reliability. 
  
-It is essential to use the CAN-bus connection of the [[venus-os:start|Venus-device]] (eg CCGX or VGX) with the batteries for the keep-alive signal, communication of charge and discharge limits, error codes and state of charge+Legacy systems installed with v2.15 can continue to be used without upgrade as long as they do not present any issues
  
-The minimum required firmware version for the [[https://www.victronenergy.com/panel-systems-remote-monitoring/color-control|Color Control GX]] is v2.15. It is highly recommended to use the latest firmware version on all connected devices, including CCGX/VGX, Inverter/Charger and MPPTs. There are regular updates to improve performance and reliability.  
  
 +=== 1.3 All Multi, MultiPlus, MultiGrid and Quattro are compatible ===
  
-=== 1.3 All 48V MultiMultiPlus, MultiGrid and Quattro are compatible ===+As long as you are using the appropriate model for the nominal battery voltageall VE.Bus inverters and inverter/chargers are compatible
  
-The minimum firmware version is 422. Though updating to the latest firmware is recommended where possible.+The minimum firmware version for new installations is 469. Though [[https://docs.victronenergy.com/victronconnect-vebus.html#firmware-updates|updating to the latest firmware]] is recommended where possible, and a necessary first step when troubleshooting issues.
  
-These inverter/charger units must be connected to the [[venus-os:start|Venus-device]] via the VE.Bus connection port. +These inverter/charger units must be connected to the [[venus-os:start|GX device]] via the VE.Bus connection port. 
  
 +Legacy systems installed with VE.Bus firmware 422 can continue to be used without upgrade as long as they do not present any issues. 
  
-=== 1.4 All 48V VE.direct BlueSolar and SmartSolar MPPT Chargers are compatible ===+=== 1.4 All VE.Direct BlueSolar and SmartSolar MPPT Chargers are compatible ===
  
 For proper operation, the Pylontech battery needs to be able to control the charge current. Therefor it is recommended to use Victron 48V compatible MPPTs models with VE.Direct port for charging. For proper operation, the Pylontech battery needs to be able to control the charge current. Therefor it is recommended to use Victron 48V compatible MPPTs models with VE.Direct port for charging.
Line 45: Line 54:
 __MPPTs with a VE.Direct port__ __MPPTs with a VE.Direct port__
  
-MPPTs are controlled via the [[venus-os:start|Venus-device]]. Make sure the [[venus-os:start|Venus-device]] runs v2.15 or later, and the MPPTs to 1.37 or the latest available version. +MPPTs are controlled via the [[venus-os:start|GX device]]. Make sure the [[venus-os:start|GX device]] runs v2.15 or later, and the MPPTs to 1.37 or the latest available version. 
  
-The MPPT requires connection to the [[venus-os:start|Venus-device]] to regulate charge currents as the batteries require (due to temperature, etc) +The MPPT requires connection to the [[venus-os:start|GX device]] to regulate charge currents as the batteries require (due to temperature, etc) 
-To test operation, try disconnecting the [[venus-os:start|Venus-device]] from the MPPT. After a time-out, the MPPT will stop charging and flash an error code on its LEDs. The error code is [[https://www.victronenergy.com/live/mppt-error-codes#err_67_-_no_bms|error #67: no BMS]]. +To test operation, try disconnecting the [[venus-os:start|GX device]] from the MPPT. After a time-out, the MPPT will stop charging and flash an error code on its LEDs. The error code is [[https://www.victronenergy.com/live/mppt-error-codes#err_67_-_no_bms|error #67: no BMS]]. 
  
 __MPPTs with a VE.Can port__ __MPPTs with a VE.Can port__
  
-Use of VE.Can MPPT'with Pylontech batteries is not supported or documented.+New Model (2019 and later) VE.Can MPPTs are also supported from firmware version 1.06 and above. Be aware that some GX devices (e.g. CCGX) only have a single CANBus interface, and that is required for the battery communications. So if you use a new VE.Can MPPT, it must also be with a GX device that has more than one CANbus interface, e.g. the Cerbo GX. 
 +  
 +Old model VE.Can MPPTs (pre 2019) are not supported. 
  
  
 ===== 2. Minimum Battery Sizing Recommendations  ===== ===== 2. Minimum Battery Sizing Recommendations  =====
- +Once DVCC is enabled on the GX devicethe charge and discharge rates are managed by the Pylontech battery.
-Each US2000B Plus battery module is approximately 50Ah at 48Vcan provide 25A continuous charge and discharge and 100A peak for 1 minute. +
- +
-The charge and discharge rates are managed automatically by the Pylontech battery and [[venus-os:start|Venus-device]]+
  
 Using very large solar arrays with battery banks that are too small can exceed the limits of the batteries ability to charge and possibly lead to the BMS triggering over-current alarms. Using very large solar arrays with battery banks that are too small can exceed the limits of the batteries ability to charge and possibly lead to the BMS triggering over-current alarms.
  
-You must have the minimum number of units to supply the potential current demand of the load connected to the inverter. It is more desirable to have the inverter/charger overload than the battery. +You must have the minimum number of battery modules to supply the inverters startup inrush surge currents that charge the capacitors when the inverter is first connected, this occurs prior to any loads being connected. There is also the subsequent potential current demands of the loads connected to the inverter.  
 +It is much more desirable to have the inverter/charger overload than the battery, as the inverter will automatically recover, whereas the battery may require intervention once in a fault state. 
 + 
 +These minimum battery sizings are required for reliable operation.
  
-Some suggested battery sizings for common Victron inverter/chargers are listed below. These are suggestions for reliable operation for single phase off grid and are not specified by Pylontech+An example of minimum system sizing based on the US2000 battery module is below. Each battery module is approximately 50Ah at 48V, can provide 25A continuous charge and discharge and 100A peak for 1 minute.
  
 ^ Inverter / Charger Model ^ Inv continuous watts @ 25 degrees ^ Inverter peak watts surge rating ^ Number of Pylontech modules ^ Battery continuous discharge watt rating ^ Battery peak discharge watt rating ^  ^ Inverter / Charger Model ^ Inv continuous watts @ 25 degrees ^ Inverter peak watts surge rating ^ Number of Pylontech modules ^ Battery continuous discharge watt rating ^ Battery peak discharge watt rating ^ 
Line 76: Line 87:
 | Quattro 48/10000/140-100/100 | 8000 | 20000 | 7 | 8400 | 33600 | | Quattro 48/10000/140-100/100 | 8000 | 20000 | 7 | 8400 | 33600 |
 | Quattro 48/15000/200-100/100 | 12000 | 25000 | 10 | 12000 | 48000 | | Quattro 48/15000/200-100/100 | 12000 | 25000 | 10 | 12000 | 48000 |
- 
  
  
Line 86: Line 96:
 You can connect multiple battery modules together to form a single large battery by connecting the RJ-45 cable supplied by Pylontech using the link ports on the battery. This is shown in more detail in the  [[https://www.victronenergy.com/live/_media/battery_compatibility:pylon-diagram-2018-12-28.jpg|example wiring diagram]] and Pylontech manual. You can connect multiple battery modules together to form a single large battery by connecting the RJ-45 cable supplied by Pylontech using the link ports on the battery. This is shown in more detail in the  [[https://www.victronenergy.com/live/_media/battery_compatibility:pylon-diagram-2018-12-28.jpg|example wiring diagram]] and Pylontech manual.
  
-The batteries will automatically detect and link to each other, no adjustment of dip switches or software changes are necessary on the batteries+The communications for UP2500 can be paralleled up to 20 modules per string (and cannot use the LV-HUB). Other models can connect up to 8 battery modules (see Pylontech data sheets), in those models when using more than 8 parallel units, some limitations, additional configuration or equipment (e.g. Pylontech LV-Hub) may apply. See your Pylontech dealer, and Pylontech documentation for more details.  
 + 
 +The batteries will automatically detect and link to each other, no adjustment of dip switches on the battery module are necessary
  
 The battery with the empty link port 0 is the master battery.  The battery with the empty link port 0 is the master battery. 
-You must use the //VE.Can to CAN-bus BMS type B Cable//, part number ASS030720018, you cannot use the cable supplied by Pylontech.  
  
-Plug the type B cable with the side which is labeled Battery BMS into the Pylontech CAN port of the master battery. Plug the side labeled Victron VE.Can into the [[venus-os:start|GX device]].+** Important note on DIP switches **
  
-Then, plug a [[https://www.victronenergy.com/accessories/ve-can-rj45-terminator|VE.Can terminator]] in the other VE.Can socket on the [[venus-os:start|Venus-device]]. Two VE.Can terminators are included with the package of the [[venus-os:start|Venus-device]] as an accessory, only one is used. Keep the other one as a spare.+No adjustment to the DIP switches is necessary, unless you are using a LV-Hub to connect a large number of modules. The address DIP-switches must be set to 000 for correct operation, and the GX device will not detect the battery if you use any other setting. Larger batteries using an LV-Hub is discussed later in this document. 
 + 
 +**Type A cable** 
 + 
 +The Victron //VE.Can to CAN-bus BMS type A Cable//, part number ASS030710018 is used for connection with US2000C / US3000C / UP5000 / US5000 / US5000B / Force-L. 
 + 
 +**Type B cable** 
 + 
 +The Victron //VE.Can to CAN-bus BMS type B Cable//, part number ASS030720018 is used for connection with US2000 / US3000 / UP2500;  
 + 
 +Note you cannot use the comms cable supplied by Pylontech for this connection between the master battery and the GX device. 
 + 
 +**Connections** 
 + 
 +Plug the communication cable with the side which is labeled Battery BMS into the Pylontech CAN port of the master battery.  
 + 
 +Some GX devices (such as the Cerbo GX), have multiple CAN ports. If your GX device has a BMS-Can port, this should be used. If your GX device ONLY has VE.Can ports, you will need to change the VE.Can port profile to CAN-bus BMS (500 kbit/s) for the battery (and then it cannot be used for other VE.Can devices). 
 + 
 +Plug the side labeled Victron VE.Can into the [[venus-os:start|GX device]]. 
 + 
 + 
 + 
 +Then, plug a [[https://www.victronenergy.com/accessories/ve-can-rj45-terminator|VE.Can terminator]] in the other VE.Can socket on the [[venus-os:start|GX device]]. Two VE.Can terminators are included with the package of the [[venus-os:start|GX device]] as an accessory, only one is used. Keep the other one as a spare.
  
 More information about the cable can be found in [[battery_compatibility:can-bus_bms-cable|its manual]]. More information about the cable can be found in [[battery_compatibility:can-bus_bms-cable|its manual]].
  
-Without properly connecting this cable, the battery will not show up on the display of the [[venus-os:start|Venus-device]]. The battery will also turn itself off.+Without properly connecting this cable, the battery will not show up on the display of the [[venus-os:start|GX device]]. The battery will also turn itself off.
  
-It is important to ensure this connection and display of the battery on the [[venus-os:start|Venus-device]] display before attempting firmware updates or settings changes on other devices if they depend on the power supply from the battery. Without this connection, the battery may turn off unexpectedly. +It is important to ensure this connection and display of the battery on the [[venus-os:start|GX device]] display before attempting firmware updates or settings changes on other devices if they depend on the power supply from the battery. Without this connection, the battery may turn off unexpectedly. 
  
 +===== 4. GX Device Settings =====
  
-===== 4VEConfigure Settings =====+When the Pylontech battery is connected to the BMS-Can port of a GX device (running v2.80 and later) the following DVCC settings will be set and enforced automatically.
  
-You will need the latest firmware on all connected devices. +If you are running a GX firmware version prior to this, these will need to be manually configured.  
 + 
 +=== Manual Configuration === 
 + 
 +On the [[venus-os:start|GX device]],  
 + 
 +  * If your GX device has a BMS-Can port, the battery should be connected to this.  
 +  * If you connect the BMS to the VE.Can port you will need to adjust the port speed. Select the //CAN-bus BMS (500 kbit/s)// CAN-profile in the GX device. Menu path: //Settings -> Services -> VE.CAN port//.  
 + 
 +After properly wiring and setting the correct CAN-bus speed, the Pylontech will be visible as a battery in the device list. If you have multiple batteries a single entry will show up, which represents all batteries: 
 +{{ :battery_compatibility:pylon-menu.png?nolink&400 |}} 
 + 
 +Next, go to Settings, DVCC, and configure as follows: 
 + 
 +^Venus Settings -> System Setup Parameter ^ Value ^  
 +|DVCC|ON| 
 +|Shared Voltage Sense |OFF|  
 +|Shared Temperature Sense |OFF|  
 + 
 +For more information about the behaviour of DVCC, please see the [[https://www.victronenergy.com/media/pg/Cerbo_GX/en/dvcc---distributed-voltage-and-current-control.html|GX device manual]].  
 + 
 +=== Additional optional controls === 
 + 
 +Note: The "Limit managed battery charge voltage" feature should be left OFF, unless you are experiencing "High Voltage" or "Internal Error" alarms. These alarms can indicate that there is an internal cell imbalance in the battery. It may be useful in this situation to enable this feature, and then adjust the voltage limit down so that the batteries are able to balance charge without reaching over voltage internally. This imbalance is at a cell level, so might not be reflected as a high overall battery voltage if measured with a Multimeter. This can then be turned off once the battery has balanced itself properly.  
 + 
 +The 'limit charge current' value that you set manually in the DVCC menu of the GX device will allow you to set a value less than the ceiling Charge Current Limit (CCL) set by the BMS, if you want to further restrict system wide charge current for some reason. You can enter a larger number than the CCL, but the system will then stop at the CCL number (and not your manually entered figure). 
 + 
 +For example if you only wired in 80A capacity wire / fuses through the system, and didn't want the potential combined power delivery of a generator charging as well as a solar charge, you could limit the total system charging (MPPT + MultiPlus) to that lower level, even though the batteries could potentially absorb more. 
 + 
 +=== Other information === 
 + 
 +The parameters option within the battery page shows the battery charge and discharge limits as communicated to the DVCC system by the BMS. 
 +{{ :battery_compatibility:pylon-params.png?nolink&400 |}} 
 + 
 +The 'charge current limit' (CCL) as shown in the parameters screen (and received from the BMS, by the GX device, via DVCC) will be the ceiling, and the system will try its best not to exceed that (as much as it can - it may spike under momentary peaking conditions). 
 + 
 +This parameters page is also a good place to check that all batteries are connected and working properly. The battery data sheet specifies the normal working conditions, e.g. the current limit per cell. For example, If each battery is rated to 25A charge current, and the menu shows a 75A charge current limit ( 75 / 25 = 3 ) means there are 3 Pylontech battery modules connected.  
 + 
 +In off-grid systems, the inverter will prioritise running the load, and potentially exceed this Discharge Current Limit. This could lead to the battery shutting down, and why it is important to follow the minimum battery sizing guide. 
 + 
 +In grid connected ESS systems, the inverter will do its best to respect the Discharge Current Limit and use the grid to supplement the load if required. 
 + 
 +Note that 'details' menu of the battery (e.g. Lowest and Highest cell voltages etc) is only supported with recent Pylontech firmware. 
 + 
 +{{ :battery_compatibility:pylon-bms-details.png?nolink&400 |}} 
 + 
 +The firmware requirements for the details menu is documented in the table below. 
 + 
 +^ Product ^ Firmware version ^  
 +| LV HUB | v1.8 | 
 +| US2000B | v2.9 | 
 +| US2000C & US3000C | v2.1 | 
 +| ForceL | v1.4 | 
 +| US5000 & Pelio-L | All firmware versions | 
 +===== 5. VEConfigure Settings ===== 
 + 
 +When using the latest firmware on all compatible connected devices, and once the battery module has been detected by the GX device, battery charging parameters (e.g. Maximum Charge Current, Target Battery Voltage, etc) are automatically configured by the Pylontech BMU, and communicated to the rest of the Victron components in the system via [[https://www.victronenergy.com/media/pg/Cerbo_GX_Device_Manual/en/dvcc---distributed-voltage-and-current-control.html|DVCC]]. 
 + 
 +It is possible to override some of these automatic settings to provide additional limitations (e.g. reduce the total charge current that would be provided but the MultiPlus). The following information is provided for that purpose, though is not required for the safe operation of the system.
  
 This section presumes familiarity with [[https://www.victronenergy.com/upload/documents/Manual-A-Guide-to-VEConfigure-EN.pdf|VEConfigure software.]]  This section presumes familiarity with [[https://www.victronenergy.com/upload/documents/Manual-A-Guide-to-VEConfigure-EN.pdf|VEConfigure software.]] 
  
-=== 4.1 General tab ===+Voltages shown are for the 48V model, and should be scaled for the 24V model. The 24V model is an 8-series configuration while the 48V model is a 15-series configuration. Voltages should therefore be scaled by 8/15. 
 + 
 +=== 5.1 General tab ===
  
   * Check the "Enable battery monitor" function   * Check the "Enable battery monitor" function
-  * Set the battery capacity to the total capacity of the battery: eg 50Ah times the number of battery modules for the 2000B Plus model.+  * Set the battery capacity to the total capacity of the battery: eg 50Ah times the number of battery modules for the US2000 model.
   * The other parameters ("State of charge when bulk finished" and "Charge efficiency") can be left to their default setting: They are ignored for a Pylontech installation.   * The other parameters ("State of charge when bulk finished" and "Charge efficiency") can be left to their default setting: They are ignored for a Pylontech installation.
  
-=== 4.2 Charge Settings ===+=== 5.2 Charge Settings ===
  
 === Charger tab === === Charger tab ===
 ^ Parameter              ^ Setting ^ ^ Parameter              ^ Setting ^
-| Battery type           | Lithium |+| Battery type           | Lithium | 
 | Charge curve           | Fixed    | Charge curve           | Fixed   
-| Absorption voltage     53.V  | +| Absorption voltage     52.V  | 
-| Float voltage          | 53.0 V  | +| Float voltage          | 51.0 V  | 
 | Absorption time        | 1 Hr    | | Absorption time        | 1 Hr    |
  
-Note: make sure to double check the float voltage after completing Assistants, and if necessary set it back to 53.0 V.+Note: make sure to double check the float voltage after completing Assistants, and if necessary set it back to 51.0 V.
  
-=== 4.3 Inverter Settings ===+Note For off-grid use: ignore the 'bms assistant required' warning. 
 + 
 +=== 5.3 Inverter Settings ===
  
 In the Inverter tab of VEConfigure In the Inverter tab of VEConfigure
 ^VEConfigure Inverter Parameter              ^Setting^ ^VEConfigure Inverter Parameter              ^Setting^
-|DC input low shut-down | 47V+|DC input low shut-down | 44V
-|DC input low restart   51V+|DC input low restart   48V
-|DC input low pre-alarm* | 48.5V|+|DC input low pre-alarm* | 48V|
  
  
Line 157: Line 253:
 === Hardware Protection Points === === Hardware Protection Points ===
  
-In normal operation, the charge parameter limits are set by the Pylontech battery and communicated through the system by the [[venus-os:start|Venus-device]] to the inverter/charger and MPPT. +In normal operation, the charge parameter limits are set by the Pylontech battery and communicated through the system by the [[venus-os:start|GX device]] to the inverter/charger and MPPT. 
  
   * Low Voltage: When the battery discharges to 44.5V or less, battery protection will turn on.     * Low Voltage: When the battery discharges to 44.5V or less, battery protection will turn on.  
Line 168: Line 264:
 If operation is attempted outside the operating range, the battery will disconnect to protect itself. If operation is attempted outside the operating range, the battery will disconnect to protect itself.
  
-===== 5. Venus-device Settings ===== 
  
-On the [[venus-os:start|Venus-device]], go to Settings, System setup: 
  
-^Venus Settings -> System Setup Parameter ^ Value ^  +===== 6. VE.Direct MPPT Settings =====
-|DVCC|ON| +
-|Shared Voltage Sense |OFF|  +
- +
-  * Select the //CAN-bus BMS (500 kbit/s)// CAN-profile in the CCGX. Menu path: //Settings -> Services -> CAN-profile//.  +
- +
-  * After properly wiring and setting up, the Pylontech will be visible as a battery in the device list. If you have multiple batteries a single entry will show up, which represents all batteries: +
-{{ :battery_compatibility:pylon-menu.png?nolink&400 |}} +
-  +
- +
-  * The parameters option within the battery page shows the actual battery charge and discharge limits +
-{{ :battery_compatibility:pylon-params.png?nolink&400 |}} +
- +
-This parameters page is also a good place to check that all batteries are connected and working properly. In normal working conditions, the current limit is 25A per cell. For example, 75A charge current limit ( 75 / 25 = 3 ) means there are 3 Pylontech battery modules connected.  +
- +
-===== 6. VE-Direct MPPT Settings =====+
  
-In normal operation the MPPT charge characteristics are governed by the [[venus-os:start|Venus-device]]  via DVCC, with instructions from the connected Pylontech battery. +In normal operation the MPPT charge characteristics are governed by the [[venus-os:start|GX device]]  via DVCC, with instructions from the connected Pylontech battery. 
  
 This section presumes familiarity with [[victronconnect:start|VictronConnect]] This section presumes familiarity with [[victronconnect:start|VictronConnect]]
  
-The settings below are a precautionary measure. +The settings below can be set as a precautionary measure. 
  
 ^MPPT Parameter ^ Setting ^ ^MPPT Parameter ^ Setting ^
 |Battery voltage.     |48V| |Battery voltage.     |48V|
-|Absorption voltage   |53V|+|Absorption voltage   |52V|
  
 +Note for MPPT RS - the Remote Mode in VictronConnect must be set to Remote on/off, not BMS.
 ===== 7. Example Wiring Diagram ===== ===== 7. Example Wiring Diagram =====
  
-{{ :battery_compatibility:pylon-diagram-2018-12-28.jpg?direct&800 |}} +{{:battery_compatibility:ds_-_pylontech_-_managed_lithium_battery_-_2021-3-11.jpg?direct&800|}}
 ===== 8. Troubleshooting ===== ===== 8. Troubleshooting =====
  
 If the system is not operating correctly, go through these steps. If the system is not operating correctly, go through these steps.
  
-=== Step 0. If the Inverter/Charger or Venus-device does not switch on ===+=== Step 0. If the Inverter/Charger or GX device does not switch on === 
 + 
 +When the grid is connected there are two software controls to sustain voltage. The Minimum SOC (while grid is connected) set in the GX device, and the sustain voltage (set in the ESS assistant). 
 + 
 +If the grid fails and no AC supply is available, in this deeply discharged state, and the battery has set the Discharge Current Limit (DCL) to 0A, then the inverter will turn off in a software off state. 
 +The GX device will remain on, as there is still DC voltage provided by the batteries for a while. 
 + 
 +Note in this state an AC PV inverter will not produce any power, and will not start up, as it requires the inverter to create the sine wave to synchronise. 
 + 
 +If the AC grid or generator, or DC MPPT is connected, then the battery will begin to charge and then the inverter will start itself again automatically, also resuming charge from an AC PV inverter.
  
-As a safety precaution, the inverter/charger will not switch on if the [[venus-os:start|Venus-device]] is not on. If you are unable to start the system due to a total system blackout / battery shutdown due to low voltage, you may need to disconnect the VE.BUS connection cable between the inverter/charger and [[venus-os:start|Venus-device]]+If instead the battery becomes completely discharged the battery will further protect itself by not just sending the 0A discharge limit, but also disconnecting DC voltage from the battery terminals (via internal MOSFETS). As there is no DC voltage available on the terminals any more the GX device will also shut down, and the inverter will also then be hard off (not just software off).
  
-You can then start the inverter/charger from an external charge source such as a generator or grid connection. Once the inverter/charger has startedit should supply power to the DC terminals and this should start the [[venus-os:start|Venus-device]] and Pylontech battery again. You will need to then reconnect the VE.Bus Communications cable back to the inverter/charger and [[venus-os:start|Venus-device]].+If you then reconnect a DC charge sourceor AC input supply (grid or generator), after approximately 2 minutes the inverter will start up again, power the DC bus, powering up the GX deviceand then powering up the battery, and the system will recover.
  
-=== Step 1. Check that the Pylontech battery is visible on the Venus-device list ===+=== Step 1. Check that the Pylontech battery is visible on the GX device list ===
  
 {{ :battery_compatibility:pylon-menu.png?nolink&400 |}} {{ :battery_compatibility:pylon-menu.png?nolink&400 |}}
Line 219: Line 307:
 If its not visible, check: If its not visible, check:
  
-  * [[venus-os:start|Venus-device]] firmware version (update to latest version, v2.15 or later)+  * [[venus-os:start|GX device]] firmware version (update to latest version, v2.15 or later)
   * CAN-bus communication cabling between Pylontech and Victron system. Make sure that it is in the right way around.   * CAN-bus communication cabling between Pylontech and Victron system. Make sure that it is in the right way around.
   * Pylontech system is up and running (LEDs are on)   * Pylontech system is up and running (LEDs are on)
Line 225: Line 313:
 === Step 2. Check that the Pylontech battery is ready for use === === Step 2. Check that the Pylontech battery is ready for use ===
  
-Check the Max Charge Voltage parameter. This voltage parameter is sent, together with the other three parameters,  by the Pylontech system via the CAN-bus cable. They are visible on the [[venus-os:start|Venus-device]]: Device List -> Pylontech battery -> Parameters menu.+Check the Max Charge Voltage parameter. This voltage parameter is sent, together with the other three parameters,  by the Pylontech system via the CAN-bus cable. They are visible on the [[venus-os:start|GX device]]: Device List -> Pylontech battery -> Parameters menu.
  
 === Step 3. Check the Pylontech manual === === Step 3. Check the Pylontech manual ===
Line 245: Line 333:
 Pylontech's BMS will restrict the Charge Current Limit of the battery in cold weather. The precise temperatures and limits are not published by Pylontech, but anecdotally from reports on [[http://commmunity.victronenergy.com|Victron Community]] it would appear that batteries begin to be limited below 18 degree C, severely limited below 10 degrees C, and completely restricted from charging below 2 degrees C.  Pylontech's BMS will restrict the Charge Current Limit of the battery in cold weather. The precise temperatures and limits are not published by Pylontech, but anecdotally from reports on [[http://commmunity.victronenergy.com|Victron Community]] it would appear that batteries begin to be limited below 18 degree C, severely limited below 10 degrees C, and completely restricted from charging below 2 degrees C. 
  
-You can confirm if this is affecting your installation be entering the Pylontech Battery menu on your Venus-device, and then the Parameters Menu. This will report the Charge Current Limit (CCL) and Discharge Current Limit (DCL).+You can confirm if this is affecting your installation be entering the Pylontech Battery menu on your GX device, and then the Parameters Menu. This will report the Charge Current Limit (CCL) and Discharge Current Limit (DCL). This information is also logged in the advanced section of the VRM monitoring portal
  
 +==== My system only charges the battery to 52.4V ====
 +When DVCC is enabled, the battery (via the CAN-bms) is responsible for the charge voltage. The Pylontech battery requests a charge voltage of 53.2V. We have however found that in practice this is too high.
 +
 +The Pylontech battery has 15 cells in series, so 53.2V equates to 3.55V per cell. This is very highly charged and makes the system prone to go overvoltage.
 +
 +It should also be noted that a LiFePO4 cell stores very little additional energy above 3.45V.
 +
 +For this reason we opted to override the BMS and cap the voltage at 52.4V. This sacrifices almost none of the capacity and greatly improves the stability of the system.
 +
 +==== The battery won't charge to 100% ====
 +Also see the question above. The state of charge of the battery is estimated based on the overall voltage and on how well balanced the internal cells are. Because we cap the battery voltage at 52.4V, the state of charge will sometimes rise very slowly once it reaches the mid-90s. This is normal and usually resolves over time.
 +
 +==== 'Internal Error' shown on battery status ====
 +The 'Internal Error' shown in battery status is not a critical error. This only defines that within a battery system, some of the slave batteries are offline(which is due to these modules have been discharged to an extremely low SOC or being in idle mode for more than 72hrs), once the system is available for a charging activity such an error will be automatically eliminated. 
 +
 +==== 'High voltage' warning or alarm shown on battery status ====
 +The 'high voltage' warning or alarm is not unusual on new batteries that are not yet balanced. To help the batteries balance quickly, keep the batteries fully charged until the errors go away.
 +In an ESS system, set it to 'keep batteries charged', in an off-grid system the fastest way is to either charge / balance the battery before installation, or to fully charge with a generator if not enough solar is available to keep the batteries fully charged.
 +
 +If you are unable to maintain the target voltage to balance the batteries without the 'high voltage' alarm occurring, you may need to enable and set the "Limit managed battery charge voltage" setting in the DVCC menu of the GX device. Reduce this voltage as necessary until the alarm stops. 
 +After sufficient time to balance the batteries, try increasing this value until it can be disabled again for normal operation. 
 +
 +{{:battery_compatibility:maximum_charge_voltage.jpg?400|}}
 +
 +If it is not possible to raise the voltage over time, and eventually disable this manual override:
 +
 +1: If you have 2 or more batteries in your system, you can try shutting down the system once it is as close to fully charged as possible, and then physically connecting the batteries in smaller groups (or even individually) so that balancing can occur on each individual battery without it being masked by the others connected in parallel. It may help you to see the indicator lights on the battery (if available on that model) to find which battery might be out of balance with the others.
 +
 +2: Contact your Pylontech dealer for further assistance (they can provide additional software to see individual cell level data), or assist with other potential solutions. 
 ===== 10. Further Information ===== ===== 10. Further Information =====
  
Line 252: Line 369:
  
 Further community discussion about installing and using Pylontech and Victron can found at [[https://community.victronenergy.com|Victron Community]], use the topic label 'Pylontech'. Further community discussion about installing and using Pylontech and Victron can found at [[https://community.victronenergy.com|Victron Community]], use the topic label 'Pylontech'.
 +
 +=== LV-Hub specific information ===
 +
 +Please discuss large Pylontech systems that require the LV-Hub with your experienced Pylontech agent FIRST. These additional LV-Hub references are provided without any support or endorsement from Victron, and should not be assumed to be up to date. Defer to your experienced dealers recommendations.  
 +
 +{{ :battery_compatibility:lv-hub_communication_hub_product_manual_20210705.pdf |Pylontech LV-hub manual}}
 +
 +[[https://community.victronenergy.com/questions/129009/lv-hub-troubleshooting.html|Victron Community discussion on LV-hub configuration settings with Victron]]
  
  