battery_compatibility:pylontech_phantom [2019-01-22 10:16] – external edit 127.0.0.1battery_compatibility:pylontech_phantom [2019-02-28 11:46] guy_stewart
Line 31: Line 31:
 The minimum required firmware version for the [[https://www.victronenergy.com/panel-systems-remote-monitoring/color-control|Color Control GX]] is v2.15. It is highly recommended to use the latest firmware version on all connected devices, including CCGX/VGX, Inverter/Charger and MPPTs. There are regular updates to improve performance and reliability.  The minimum required firmware version for the [[https://www.victronenergy.com/panel-systems-remote-monitoring/color-control|Color Control GX]] is v2.15. It is highly recommended to use the latest firmware version on all connected devices, including CCGX/VGX, Inverter/Charger and MPPTs. There are regular updates to improve performance and reliability. 
  
-In grid connected systems, advanced control functions are configurable in the ESS settings on the [[venus-os:start|Venus-device]]. 
- 
-In off-grid systems, the system control functions from the Pylontech Battery Management System (BMS) are built into the latest version of the [[venus-os:start|Venus-device]]. 
  
 === 1.3 All 48V Multi, MultiPlus, MultiGrid and Quattro are compatible === === 1.3 All 48V Multi, MultiPlus, MultiGrid and Quattro are compatible ===
Line 230: Line 227:
  
 The Pylontech manual contains additional diagnostic and troubleshooting information, specifically around decoding any indicator LEDs. The Pylontech manual contains additional diagnostic and troubleshooting information, specifically around decoding any indicator LEDs.
-===== 9. FAQ ===== 
  
-**The maximum charge and discharge current is limited to 25A, but the data sheet tells me the maximum is 100A.** +===== 9. FAQ and Known Issues===== 
 + 
 +==== The maximum charge and discharge current is limited to 25A, but the data sheet tells me the maximum is 100A. ====
  
 The maximum current is limited to keep the battery healthy and reach the 10 year guarantee. In off-grid, the inverter can draw more than the 25A limit to run the loads, make sure you have sufficient batteries installed to keep the load per battery around this limit. The maximum current is limited to keep the battery healthy and reach the 10 year guarantee. In off-grid, the inverter can draw more than the 25A limit to run the loads, make sure you have sufficient batteries installed to keep the load per battery around this limit.
  
-**After charging the battery the charge current often changes between 0A and 25A.** +==== After charging the battery the charge current often changes between 0A and 25A. ==== 
 This is caused by cell balancing inside the battery. This happens with new batteries and after a deep discharge. This is caused by cell balancing inside the battery. This happens with new batteries and after a deep discharge.
  
 +==== My system isn't charging at the rated capacity, or my PV is shutting down ====
  
 +Pylontech's BMS will restrict the Charge Current Limit of the battery in cold weather. The precise temperatures and limits are not published by Pylontech, but anecdotally from reports on [[http://commmunity.victronenergy.com|Victron Community]] it would appear that batteries begin to be limited below 18 degree C, severely limited below 10 degrees C, and completely restricted from charging below 2 degrees C. 
 +
 +You can confirm if this is affecting your installation be entering the Pylontech Battery menu on your Venus-device, and then the Parameters Menu. This will report the Charge Current Limit (CCL) and Discharge Current Limit (DCL).
  
 ===== 10. Further Information ===== ===== 10. Further Information =====