 ====== Victron & Leoch ====== ====== Victron & Leoch ======
 +
 +{{:battery_compatibility:attachment_4_battery_photo.png?800|}}
  
 ===== 1. Product & System compatibility ===== ===== 1. Product & System compatibility =====
Line 7: Line 9:
 It is essential to use the BMS-Can (500 kbit/s) connection type of a [[venus-os:start|GX device]] with these batteries for communication of charge and discharge limits, error codes and state of charge.  It is essential to use the BMS-Can (500 kbit/s) connection type of a [[venus-os:start|GX device]] with these batteries for communication of charge and discharge limits, error codes and state of charge. 
  
-Use a Victron Type VE.CAN to BMS-Can cable to connect the GX device to the battery. The VE.Can labelled end of the cable should be connected to the GX device, even if using a BMS-Can labeled port on a GX device. The BMS-Can labeled end of the cable should be connected to the battery.+Use a Victron Type VE.CAN to BMS-Can cable to connect the GX device to the battery. The VE.Can labelled end of the cable should be connected to the GX device, even if using a BMS-Can labeled port on a GX device. The BMS-Can labeled end of the cable should be connected to the battery.
  
 It is possible to use either the BMS-Can or VE.Can ports with this battery. Depending which one you use will require additional configuration on the batteries side, please see the documentation linked below for instructions.  It is possible to use either the BMS-Can or VE.Can ports with this battery. Depending which one you use will require additional configuration on the batteries side, please see the documentation linked below for instructions. 
Line 13: Line 15:
 The minimum supported GX firmware version is v3.50. It is recommended to use the latest firmware version on new installations and when trouble shooting issues. The minimum supported GX firmware version is v3.50. It is recommended to use the latest firmware version on new installations and when trouble shooting issues.
  
-The minimum supported Leoch BMS firmware version is ??????+The minimum supported Leoch BMS firmware version is v2.4
  
-Connecting a Leoch battery to the GX device will automatically enable DVCC, and disable SVS and STS.+Confirm that DVCC is enabled after connecting a Leoch battery to the GX device, and disable SVS and STS. 
 + 
 +{{:battery_compatibility:leoch-1.jpg?400|}}
  
 === 1.2 All 48V Multis, MultiPlus, Quattros and RS models are compatible === === 1.2 All 48V Multis, MultiPlus, Quattros and RS models are compatible ===
Line 37: Line 41:
 ===== 2. Minimum battery sizing  ===== ===== 2. Minimum battery sizing  =====
  
-For reliable operation there are minimum numbers of batteries required for different Victron inverters. Contact your battery supplier for these specifications.+For reliable operation there are minimum numbers of batteries required for different Victron inverters.  
 + 
 +{{:battery_compatibility:leoch_minimum_battery.jpg?1000|}} 
 + 
  
  
 ===== 3. System integration documentation  ===== ===== 3. System integration documentation  =====
  
 +{{ :battery_compatibility:leoch_victron_settings.pdf |Leoch Battery with Victron Inverter Instructions
 +}}
  
 If additional details about installation and configuration is required please contact your battery supplier.  If additional details about installation and configuration is required please contact your battery supplier. 
  
 +
 +==== 3.1 GX Information  ====
 +
 +The Leoch BMS provides Minimum and maximum cell voltage and temperature information to the GX device.
 +
 +{{:battery_compatibility:leoch_min_max.jpg?400|}}
 +
 +The prefix to the minimum and maximum values is an identifier. 
 +
 +  * Lowest Cell Voltage: “2::13”,”3.358V” that means the address 2 battery, cell 13 is the Min cell Voltage, and it is 3.358V.
 +  * Highest Cell Voltage: “1::16”,”3.398V” that means the address 1 battery, cell 16 is the Max cell Voltage, and it is 3.398V.
 +  * Min Cell temperature: “2::6”,”21°C” that means the address 2 battery, cell 6 is the Min cell temperature, and it is 21°C.
 +  * Max Cell temperature: “1::2”,”35°C” that means the address 1 battery, cell 2 is the Max cell temperature, and it is 35°C.
 +
 +**Example GX device displays**
 +
 +{{:battery_compatibility:leoch_gx.jpg?800|}}
  
 ===== 4. Support  ===== ===== 4. Support  =====
battery_compatibility/leoch.1730283729.txt.gz · Last modified: by guy_stewart