User Tools

Site Tools


battery_compatibility:hubble

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
Next revision
Previous revision
battery_compatibility:hubble [2023-11-01 11:33] – [Configure for Victron] adaptive + save and reboot warwickchapmanbattery_compatibility:hubble [2026-02-03 12:29] (current) – [48V] added AM16 warwickchapman
Line 172: Line 172:
     - Battery capacity: Use 100Ah per Hubble battery (excl. AM-10: 200Ah, AM-3: 50Ah, S-200: 200Ah, Blade: 137Ah). Eg. If there are 3 x AM-4, then capacity is 300Ah.     - Battery capacity: Use 100Ah per Hubble battery (excl. AM-10: 200Ah, AM-3: 50Ah, S-200: 200Ah, Blade: 137Ah). Eg. If there are 3 x AM-4, then capacity is 300Ah.
     - Sustain voltage, set the value from the tables below     - Sustain voltage, set the value from the tables below
-    - Dynamic cutoff, set the fallback value from the tables below+    - Dynamic cutoff, use the low cutoff value from the tables below
     - Restart offset, set the value from the tables below     - Restart offset, set the value from the tables below
  
Line 186: Line 186:
 ^ Chemistry ^ Charge ^ Cutoff ^ Restart ^ Sustain ^ Models ^  ^ Chemistry ^ Charge ^ Cutoff ^ Restart ^ Sustain ^ Models ^ 
 | LiNiMnCo (NMC) | 53.3V | 44.2V | 46.2V | 47.0V | AM-2, AM-3, X101 | | LiNiMnCo (NMC) | 53.3V | 44.2V | 46.2V | 47.0V | AM-2, AM-3, X101 |
-| LiFePO4 (LFP)  | 56.0V | 48.0V | 50.0V | 50.0V | AM-5, AM-10, Blade |+| LiFePO4 (LFP)  | 56.0V | 48.0V | 50.0V | 50.0V | AM-5, AM-10, AM-16, Blade |
 | LiFePO4 (LFP)  | 51.0V | 45.0V | 47.0V | 47.0V | X-100 | | LiFePO4 (LFP)  | 51.0V | 45.0V | 47.0V | 47.0V | X-100 |
  
battery_compatibility/hubble.1698834794.txt.gz · Last modified: by warwickchapman

Donate Powered by PHP Valid HTML5 Valid CSS Driven by DokuWiki