battery_compatibility:discover [2025-12-01 20:36] – dettingalebattery_compatibility:discover [2026-10-10 08:31] (current) – HELIOS ESS: model 52-48-16000; direct path uses the Victron VE.Can to CAN-bus BMS Type A cable with a terminator; patch-cable note for LYNK II only; section 5 numbering guy_stewart
Line 62: Line 62:
  
   * AES RACKMOUNT 48-48-5120 / 48-48-5120-H   * AES RACKMOUNT 48-48-5120 / 48-48-5120-H
-  * HELIOS ESS 42-48-16000+  * HELIOS ESS 52-48-16000
  
 **Victron Products** **Victron Products**
Line 210: Line 210:
 2. LYNK II Gateway  2. LYNK II Gateway 
  
-The HELIOS ESS supports direct closed-loop communication with Victron inverter-chargers through a modified CAT6 or higher cable.+The HELIOS ESS supports direct closed-loop communication with a Victron GX device through the Victron VE.Can to CAN-bus BMS Type A cable.
  
-{{:battery_compatibility:cat5-rj45-cable-for-victron.png?direct&600|}}+{{:battery_compatibility:ve-can-to-can-bus-bms-type-a-cable.png?direct&600|Victron VE.Can to CAN-bus BMS Type A cable}}
  
-Use this cable for connections between Victron Energy products and the HELIOS ESS.+Use the [[battery_compatibility:can-bus_bms-cable|Victron VE.Can to CAN-bus BMS Type A cable]] for the direct connection. Its pin-out matches the HELIOS ESS COM2 port: COM2 pins 4 (CAN-H), 5 (CAN-L) and 6 (GND) connect to VE.Can pins 7, 8 and 3. A standard straight patch cable does not work for this connection.
  
-1. Connect the modified CAT6 or higher cable from the HELIOS ESS COM2 port to the CAN port of the Victron GX device.+1. Plug the cable end labelled "Battery BMS CAN-type A" into the HELIOS ESS COM2 port. Plug the end labelled "Victron VE.Can" into a VE.Can port of the Victron GX device. Insert a VE.Can terminator in the other VE.Can port of the GX device.
  
 {{:battery_compatibility:victron-nw-connect.png?direct&600|}} {{:battery_compatibility:victron-nw-connect.png?direct&600|}}
Line 231: Line 231:
 If communication is interrupted between the BMS and Victron inverter-charger, the Victron inverter-charger stops charging until communication is re-established. If communication is interrupted between the BMS and Victron inverter-charger, the Victron inverter-charger stops charging until communication is re-established.
  
-Skip to section 5. Configuring Victron Products.+For the DVCC settings in step 4, go to section 5.2.1 Configurable Closed-Loop Settings. The 250 kbit/s setting and the cable note in section 5.2 apply to the LYNK II path only.
  
 ==== 4.2 Configuring the LYNK II ==== ==== 4.2 Configuring the LYNK II ====
Line 387: Line 387:
  
  
-==== 5.1 Setting Up Closed-Loop Configuration ====+==== 5.2 Setting Up Closed-Loop Configuration (LYNK II) ====
  
 Refer to the latest Discover Energy Systems documentation for battery values and the latest Victron documentation for menu navigation and details on the setup procedure. Refer to the latest Discover Energy Systems documentation for battery values and the latest Victron documentation for menu navigation and details on the setup procedure.
Line 410: Line 410:
  
  
-**NOTE:** If **Discover AES** does not appear on the Device List, confirm that the CAT5e or higher communication cable is a normal patch type, not a cross-over type. Use manufactured cables to avoid bad crimps and reduce the risk of a poor connection.+**NOTE:** This note applies to the LYNK II path only. If **Discover AES** does not appear on the Device List, confirm that the CAT5e or higher communication cable from the LYNK II CAN Out port is a normal patch type, not a cross-over type. Use manufactured cables to avoid bad crimps and reduce the risk of a poor connection. For the direct HELIOS ESS connection (section 4.1), use the Victron VE.Can to CAN-bus BMS Type A cable. A patch cable does not work on that path.
  
  
-=== 5.1.1 Configurable Closed-Loop Settings ===+=== 5.2.1 Configurable Closed-Loop Settings ===
  
 During regular operation, the BMS sets the battery’s charge parameter limits, which the Victron GX device communicates to the inverter-charger and MPPT. During regular operation, the BMS sets the battery’s charge parameter limits, which the Victron GX device communicates to the inverter-charger and MPPT.
Line 441: Line 441:
  
  
-=== 5.1.2 Saving the Configurable Closed-Loop Settings ===+=== 5.2.2 Saving the Configurable Closed-Loop Settings ===
  
 **Device List > Settings > General > Reboot?** **Device List > Settings > General > Reboot?**