User Tools

Site Tools


battery_compatibility:cegasa

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
battery_compatibility:cegasa [2022-06-24 04:22] – [Victron & Cegasa] guystewartbattery_compatibility:cegasa [2023-02-01 01:16] (current) – [4. VEConfigure settings] guy_stewart
Line 145: Line 145:
 ^VEConfigure Inverter Parameter              ^Setting^ ^VEConfigure Inverter Parameter              ^Setting^
 |DC input low shut-down | 44V| |DC input low shut-down | 44V|
-|DC input low restart   50V|+|DC input low restart   48V|
 |DC input low pre-alarm* | 45V| |DC input low pre-alarm* | 45V|
  
Line 163: Line 163:
 ^ ESS Parameter ^ Settings ^ ^ ESS Parameter ^ Settings ^
 |Battery Capacity     | 280 Ah| |Battery Capacity     | 280 Ah|
-|Sustain voltage.       52V|+|Sustain voltage.       50V|
 |Dynamic cut-off values | Voltage | |Dynamic cut-off values | Voltage |
-|0.05 | 47V |+|0.05 | 46V |
 |0.2 | 44V | |0.2 | 44V |
 |0.7 | 43.5V | |0.7 | 43.5V |
battery_compatibility/cegasa.1656037324.txt.gz · Last modified: 2022-06-24 04:22 by guystewart