battery_compatibility:cegasa [2025-05-26 13:33] – [2. Minimum Battery Sizing] guy_stewartbattery_compatibility:cegasa [2025-06-02 09:46] (current) – [4. VEConfigure settings] guy_stewart
Line 79: Line 79:
 |  Inverter RS & Multi RS 48/6000|  1|  -|  1|  -| |  Inverter RS & Multi RS 48/6000|  1|  -|  1|  -|
 |  Quattro 48/5000/70-100/100|  1|  2|  1|  2| |  Quattro 48/5000/70-100/100|  1|  2|  1|  2|
-|  Quattro 48/8000/110-100/100|  1|  3|  2|  4|+|  Quattro 48/8000/110-100/100|  1|  3|  1|  3|
 |  Quattro 48/10000/140- 100/100|  1|  3|  2|  4| |  Quattro 48/10000/140- 100/100|  1|  3|  2|  4|
-|  Quattro 48/15000/200- 100/100|  2|  6|  3|  6|+|  Quattro 48/15000/200- 100/100|  2|  6|  2|  6|
 |  EasySolar & EasySolar-II 48/3000/35-50 MPPT|  1|  1|  1|  2| |  EasySolar & EasySolar-II 48/3000/35-50 MPPT|  1|  1|  1|  2|
 |  EasySolar 48/5000/70-100 MPPT|  1|  2|  1|  2| |  EasySolar 48/5000/70-100 MPPT|  1|  2|  1|  2|
Line 117: Line 117:
 | Float voltage (1)         | 52 V  |  | Float voltage (1)         | 52 V  | 
 | Absorption time        | 8 Hr    | | Absorption time        | 8 Hr    |
-| Charge Current         30-50A per battery module |+| Charge Current         140A per battery module |
  
 If you use any assistants after programming these settings, make sure to double check the float voltage after completing them, and if necessary set it back to 52 V. If you use any assistants after programming these settings, make sure to double check the float voltage after completing them, and if necessary set it back to 52 V.