User Tools

Site Tools


battery_compatibility:byd_b-box

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
Next revision
Previous revision
Next revisionBoth sides next revision
battery_compatibility:byd_b-box [2020-12-08 10:34] mvaderbattery_compatibility:byd_b-box [2020-12-08 12:25] – [6.2 Self-Startup from Low voltage shutdown modes] guy_stewart
Line 18: Line 18:
   * Off-grid   * Off-grid
  
-Note that for Off-grid systems, its strongly recommend to make sure there is a minimum of DC-Coupled PV (= MPPT Solar Charger) in the system. Ie. not only AC-Coupled PV. Also, minimum battery configuration, and factor 1.0 are always important to adhere to, and even more so in case of Off-grid systems. Both BYD and Victron will be reluctant or even refusing to give support to systems that are not sized according to the minimum battery configuration table.+__Special note for Off-Grid systems__ 
 + 
 +For Off-grid systems, its strongly recommend to make sure there is a minimum of DC-Coupled PV (= MPPT Solar Charger) in the system. Ie. not only AC-Coupled PV. Also, minimum battery configuration, and factor 1.0 are always important to adhere to, and even more so in case of Off-grid systems. Both BYD and Victron will be reluctant or even refusing to give support to systems that are not sized according to the minimum battery configuration table.
  
 === 1.2 A GX device is required, eg Cerbo GX, Color Control GX (CCGX), Venus GX (VGX), etc ===  === 1.2 A GX device is required, eg Cerbo GX, Color Control GX (CCGX), Venus GX (VGX), etc === 
Line 274: Line 276:
 In a correctly configured system, the inverter will shut itself down before the batteries enter a self protective shut down state.  In a correctly configured system, the inverter will shut itself down before the batteries enter a self protective shut down state. 
  
-If your system is charged only with an AC-coupled PV inverter, this may prevent the AC-coupled PV inverter from starting up to recharge the batteries. Therefore it is strongly recommended that there is also either a generator or DC MPPT charge controller to provide DC bus power to bring the inverter back online to allow normal recharging to resume+Therefore it is essential that there is also either a generator or DC MPPT charge controller for overall system stability. If your system is charged only with an AC-coupled PV inverter, this may prevent the AC-coupled PV inverter from starting up to recharge the batteries. 
  
-Even a single 100/20 48V MPPT charger unit with 2 x 60 cell solar panels would be sufficient to add this self correcting mechanism able to maintain the DC bus voltage and improve longterm system reliability considerably from accidental deep discharge and subsequent shut down. +Even a single 100/20 48V MPPT charger unit with 2 x 60 cell solar panels would be sufficient to add this self correcting mechanism able to maintain the DC bus voltage and improve longterm system reliability considerably from accidental deep discharge and subsequent shut down.  
 ===== 7. Example Wiring Diagram ===== ===== 7. Example Wiring Diagram =====
  
battery_compatibility/byd_b-box.txt · Last modified: 2024-01-22 07:32 by guy_stewart

Donate Powered by PHP Valid HTML5 Valid CSS Driven by DokuWiki