battery_compatibility:bmz_ess [2019-01-22 10:16] – external edit 127.0.0.1 | battery_compatibility:bmz_ess [2019-09-09 08:34] – alexander.joist_ibc-solar.co.za | ||
---|---|---|---|
Line 1: | Line 1: | ||
- | ====== Victron & BMZ ESS 3.0 / ESS 7.0 ===== | + | ====== Victron & BMZ ESS 7.0 / ESS 9.0 / ESS X===== |
- | The combination of Victron products with the BMZ ESS 7.0 battery has been tested and certified by the R&D departments. The combination is actively supported by both companies. | + | The combination of Victron products with the BMZ ESS battery has been tested and certified by the R&D departments. The combination is actively supported by both companies. |
==== 1. Introduction ==== | ==== 1. Introduction ==== | ||
=== 1.1 Compatible Victron products === | === 1.1 Compatible Victron products === | ||
- | All 48V Multis and Quattros. And always a [[venus-os: | + | All 48V Multis and Quattros. And always a [[venus-os: |
=== 1.2 Notes === | === 1.2 Notes === | ||
Line 19: | Line 19: | ||
{{ : | {{ : | ||
- | ==== 2. Venus-device needed ==== | + | ==== 2. GX device needed ==== |
- | To use the BMZ ESS in Victron system, it is necessary to use a Color Control GX or Venus GX. On first commissioning an external power supply (Not the 48V from the BMZ-Battery) is needed. The CCGX/VGX sends a keep alive signal to the BMZ ESS via canbus. This will only be send once the canbus baud rate is changed (see 5. [[venus-os: | + | To use the BMZ ESS in Victron system, it is necessary to use a Color Control GX or Venus GX. On first commissioning an external power supply (Not the 48V from the BMZ-Battery) is needed. The CCGX/VGX sends a keep alive signal to the BMZ ESS via canbus. This will only be send once the canbus baud rate is changed (see 5. [[venus-os: |
==== 3. Wiring of communication cables ==== | ==== 3. Wiring of communication cables ==== | ||
- | Use the //VE.Can to CAN-bus BMS type B Cable//, part number ASS030720018. Plug the side which is labeled Battery BMS into the BMZ BMS. Plug the side labeled Victron VE.Can into the [[venus-os: | + | Use the //VE.Can to CAN-bus BMS type B Cable//, part number ASS030720018. Plug the side which is labeled Battery BMS into the BMZ BMS. Plug the side labeled Victron VE.Can into the [[venus-os: |
- | Then, plug a [[https:// | + | Then, plug a [[https:// |
More information about the cable can be found in [[battery_compatibility: | More information about the cable can be found in [[battery_compatibility: | ||
- | Without properly connecting this cable, the battery will stop charging/ | + | Without properly connecting this cable, the battery will stop charging/ |
==== 4. VEConfigure settings ==== | ==== 4. VEConfigure settings ==== | ||
Line 37: | Line 37: | ||
- Check " | - Check " | ||
- Enter the battery capacity: | - Enter the battery capacity: | ||
- | - BMZ ESS 3.0 - 121.5 Ah | + | - BMZ ESS 7.0 - 121.5 Ah |
- | - BMZ ESS 7.0 - 156.6 Ah | + | - BMZ ESS 9.0 - 156.6 Ah |
- BMZ ESS X - 186.3 Ah | - BMZ ESS X - 186.3 Ah | ||
- The other parameters (" | - The other parameters (" | ||
Line 63: | Line 63: | ||
- | ==== 5. Venus-device Configuration ==== | + | ==== 5. GX device Configuration ==== |
- | * Select the //CAN-bus BMS (500 kbits/s)// CAN-profile in the [[venus-os: | + | * Select the //CAN-bus BMS (500 kbits/s)// CAN-profile in the [[venus-os: |