battery_compatibility:axistorage
Differences
This shows you the differences between two versions of the page.
| Next revision | Previous revision | ||
| battery_compatibility:axistorage [2017-04-13 10:02] – created bob-victron | battery_compatibility:axistorage [2019-08-15 12:18] (current) – replace venus-device with GX device guy_stewart | ||
|---|---|---|---|
| Line 2: | Line 2: | ||
| The combination of Victron products with the BMZ ESS 7.0 battery has been tested and certified by the R&D departments. The combination is actively supported by both companies. | The combination of Victron products with the BMZ ESS 7.0 battery has been tested and certified by the R&D departments. The combination is actively supported by both companies. | ||
| - | The AXIstorage 7S/ 9S is identical with the BMZ ESS hardware and software and therefor | + | The AXIstorage 7S/ 9S is identical with the BMZ ESS hardware and software and therefore |
| - | {{ : | + | {{ : |
| ==== 1. Introduction ==== | ==== 1. Introduction ==== | ||
| === 1.1 Compatible Victron products === | === 1.1 Compatible Victron products === | ||
| - | All 48V Multis and Quattros. | + | All 48V Multis and Quattros. |
| === 1.2 Notes === | === 1.2 Notes === | ||
| Line 15: | Line 15: | ||
| * Minimum CCGX version is v1.72 | * Minimum CCGX version is v1.72 | ||
| * The derating mechanism is not very precise yet. In other words, do not expect a discharge limit of 30A to result in a precise discharge of 30A. | * The derating mechanism is not very precise yet. In other words, do not expect a discharge limit of 30A to result in a precise discharge of 30A. | ||
| - | * Actual charge- and discharge limits are visible in the Parameters page. See screenshot below in Chapter | + | * Actual charge- and discharge limits are visible in the Parameters page. See screenshot below in Chapter |
| + | * AXIstorage batteries and MPPT Solar Chargers with a VE.Can communication port cannot be both connected to the CCGX, because of different canbus speeds. Use Solar Chargers with a VE.Direct comm. port instead. | ||
| === 1.3 System diagram === | === 1.3 System diagram === | ||
| - | {{ : | + | {{ : |
| - | ==== 2. Wiring of communication cables | + | ==== 2. GX device needed |
| - | To use the AXIstorage ESS in Victron system, it is necessary to use a Color Control GX. The Color Control GX takes care of sending the necessary canbus keep-a-live message to the ESS battery. Without it, the battery will open its internal emergency relay after 10 minutes. | + | To use the AXIstorage ESS in Victron system, it is necessary to use a ColorControlGX or a VenusGX. The controller |
| - | A special RJ-45 cable is necessary to connect | + | ==== 3. Wiring of communication cables ==== |
| + | Use the //VE.Can to CAN-bus BMS type B Cable//, part number ASS030720018. Plug the side which is labeled Battery BMS into the AXIstorage BMS. Plug the side labeled Victron VE.Can into the [[venus-os:start|GX device]]. | ||
| - | ^ Function ^ VE.Can RJ-45 ^ AXIstorage RJ-45 ^ | + | Then, plug a [[https:// |
| - | | GND | Pin 3 | Pin 2 | | + | |
| - | | CAN-L | Pin 8 | Pin 5 | | + | |
| - | | CAN-H | Pin 7 | Pin 4 | + | |
| - | Place a VE.Can terminator in the empty socket on the CCGX | + | More information about the cable can be found in [[battery_compatibility: |
| - | ==== 3. VEConfigure settings ==== | + | Without properly connecting this cable, the battery will stop charging/ |
| - | === 3.1 Charge tab === | + | |
| + | |||
| + | ==== 4. VEConfigure settings ==== | ||
| + | |||
| + | === 4.1 General tab === | ||
| + | - Check " | ||
| + | - Set the battery capacity to 121.5 Ah | ||
| + | - The other parameters (" | ||
| + | |||
| + | === 4.2 Charger | ||
| ^ Parameter | ^ Parameter | ||
| | Battery type | Lithium | | | Battery type | Lithium | | ||
| Line 43: | Line 51: | ||
| Note: make sure to double check the float voltage after completing Assistants, and if necessary set it back to 60.00 V. | Note: make sure to double check the float voltage after completing Assistants, and if necessary set it back to 60.00 V. | ||
| - | === 3.2 ESS Assistant === | + | === 4.3 ESS Assistant === |
| Select the fourth battery type: | Select the fourth battery type: | ||
| Line 49: | Line 57: | ||
| Then: | Then: | ||
| - | - Enter the battery capacity: | + | - Sustain voltage: 50.0V |
| - | - AXIstorage 7S - 121.5 Ah | + | |
| - Do not change the dynamic cut-off values, they have already been set correctly after selecting the lithium battery type. | - Do not change the dynamic cut-off values, they have already been set correctly after selecting the lithium battery type. | ||
| - Same for the restart offset: do not change that. | - Same for the restart offset: do not change that. | ||
| - | ==== 4. Color Control | + | ==== 5. GX device |
| - | * Enable | + | * Select |
| * After properly wiring and setting up, the AXIstorage will be visible as a battery in the device list:{{ : | * After properly wiring and setting up, the AXIstorage will be visible as a battery in the device list:{{ : | ||
| * The parameters option within the battery page shows the actual battery charge and discharge limits:{{ : | * The parameters option within the battery page shows the actual battery charge and discharge limits:{{ : | ||
| - | * Make sure to enable the // | + | |