Various Victron products have functions to automatically signal when to start and stop a generator. Here is advice on when to use which product and method. | Various Victron products have functions to automatically signal when to start and stop a generator. Here is advice on when to use which product and method. | ||
- | When there is a [[venus-os: | ||
- | The next most used option | + | === Option 1: GX device like CCGX or Venus GX === |
+ | When there is a [[venus-os:start|GX device]] (CCGX, Venus GX, or other) in the system, the best option is to use its [[ccgx:generator_start_stop|Generator Start Stop mechanism]]. Its the most feature-rich generator start/stop system that we have to offer. It provides | ||
+ | === Option 2: BMV Battery Monitor === | ||
+ | The next most used option is a BMV-700 Battery Monitor or similar model. It can start the generator on low battery voltage and/or low battery state of charge. The BMV uses a dry contact, voltage free relay. See the [[https:// | ||
+ | |||
+ | === Option 3: Using the relay in the Multis or Quattros === | ||
The Multis, MultiPlus-IIs, | The Multis, MultiPlus-IIs, | ||
Line 14: | Line 18: | ||
- [[assistants: | - [[assistants: | ||
+ | === Combining the options === | ||
Lastly, its of course also possible to combine above mentioned methods, by wiring the open contacts in parallel to each other, or in series, to the Generator. | Lastly, its of course also possible to combine above mentioned methods, by wiring the open contacts in parallel to each other, or in series, to the Generator. | ||
- | ==== 2. How to wire a a genset with three-wire interface ==== | + | ==== 2. How to wire generators with a three-wire interface ==== |
- | All above products and devices have a single relay; | + | All above Victron |
When having a generator that requires a start pulse and a stop pulse, such as for example Cummins/ | When having a generator that requires a start pulse and a stop pulse, such as for example Cummins/ | ||
Line 30: | Line 35: | ||
{{ : | {{ : | ||
- | ==== Alternative using Assistants === | + | === Alternative using Assistants === |
(provided by Thierry Cortasa) | (provided by Thierry Cortasa) | ||
- | hy | + | One solution using MultiPlus |
- | + | Use k1 and k2 relays | |
- | just for information, | + | |
- | i use k1 and k2 relais | + | |
- | + | ||
- | first to close k1 if voltage under 24v (for exemple) | + | |
- | segond to open k1 if ac1 avalable | + | |
- | third to close k2 if voltage uper 27v (for exemple) | + | |
- | last to open k2 if ac1 not avalable | + | |
- | + | ||
- | in this case you have a three-wire system with out any think more needed ! | + | |
- | i have some systeme using this solution and all looks ok | + | * First to close k1 if voltage under 24v (for example) |
+ | * Second to open k1 if AC1 is available | ||
+ | * Third to close k2 if voltage over 27v (for example) | ||
+ | * Last to open k2 if AC1 not available | ||