====== Automatic Generator start/stop ====== | ====== Automatic Generator start/stop ====== | ||
+ | |||
+ | ==== 1. Which relay and control to use? ==== | ||
Various Victron products have functions to automatically signal when to start and stop a generator. Here is advice on when to use which product and method. | Various Victron products have functions to automatically signal when to start and stop a generator. Here is advice on when to use which product and method. | ||
- | When there is a [[venus-os: | ||
- | The next most used option | + | === Option 1: GX device like CCGX or Venus GX === |
+ | When there is a [[venus-os:start|GX device]] (CCGX, Venus GX, or other) in the system, the best option is to use its [[ccgx:generator_start_stop|Generator Start Stop mechanism]]. Its the most feature-rich generator start/stop system that we have to offer. It provides | ||
- | Also the VE.Bus Inverters, Multis and Quattros offer a Generator start/stop mechanism. They have the relatively easy to configure | + | === Option 2: BMV Battery Monitor === |
+ | The next most used option is a BMV-700 Battery Monitor or similar model. It can start the generator on low battery voltage | ||
+ | === Option 3: Using the relay in the Multis or Quattros === | ||
+ | The Multis, MultiPlus-IIs, | ||
+ | |||
+ | - [[ve.bus: | ||
+ | - [[assistants: | ||
+ | |||
+ | === Combining the options === | ||
Lastly, its of course also possible to combine above mentioned methods, by wiring the open contacts in parallel to each other, or in series, to the Generator. | Lastly, its of course also possible to combine above mentioned methods, by wiring the open contacts in parallel to each other, or in series, to the Generator. | ||
- | ===== Starting a genset | + | ==== 2. How to wire generators |
- | For example Cummins/ | + | All above Victron products and devices have a single relay; which will close when the generator needs to starts; and then expect the generator to then keep running until the relay is opened again. Or the other way around. |
+ | |||
+ | When having a generator | ||
To start such a genset, the open/close contact needs to be converted into a start and stop pulse. Below solution, using standard available timing relays, does exactly that: when the open/close contact closes it generates the start pulse, and when the open/close contact opens again it generates the stop pulse. | To start such a genset, the open/close contact needs to be converted into a start and stop pulse. Below solution, using standard available timing relays, does exactly that: when the open/close contact closes it generates the start pulse, and when the open/close contact opens again it generates the stop pulse. | ||
Line 23: | Line 35: | ||
{{ : | {{ : | ||
- | ==== Alternative using Assistants === | + | === Alternative using Assistants === |
- | (provided by Thierry Cortasa) | + | |
- | hy | + | (provided by Thierry Cortasa) |
- | + | ||
- | just for information, | + | |
- | i use k1 and k2 relais and relai programmable assistant | + | |
- | + | ||
- | first to close k1 if voltage under 24v (for exemple) | + | |
- | segond to open k1 if ac1 avalable | + | |
- | third to close k2 if voltage uper 27v (for exemple) | + | |
- | last to open k2 if ac1 not avalable | + | |
- | in this case you have a three-wire | + | One solution using MultiPlus relay for start stop a three-wire |
+ | Use k1 and k2 relays and programmable relay assistant. | ||
- | i have some systeme using this solution and all looks ok | + | * First to close k1 if voltage under 24v (for example) |
+ | * Second to open k1 if AC1 is available | ||
+ | * Third to close k2 if voltage over 27v (for example) | ||
+ | * Last to open k2 if AC1 not available | ||