 ====== Automatic Generator start/stop ====== ====== Automatic Generator start/stop ======
 +
 +==== 1. Which relay and control to use? ====
  
 Various Victron products have functions to automatically signal when to start and stop a generator. Here is advice on when to use which product and method. Various Victron products have functions to automatically signal when to start and stop a generator. Here is advice on when to use which product and method.
Line 7: Line 9:
 The next most used option is a BMV-700 Battery Monitor or similar model. It can start the generator on low battery voltage and/or low battery state of charge. See the [[https://www.victronenergy.com/battery-monitors/bmv-700#manual|BMV-700 manual]] for configuration. The next most used option is a BMV-700 Battery Monitor or similar model. It can start the generator on low battery voltage and/or low battery state of charge. See the [[https://www.victronenergy.com/battery-monitors/bmv-700#manual|BMV-700 manual]] for configuration.
  
-Also the VE.Bus Inverters, Multis and Quattros offer a Generator start/stop mechanismThey have the relatively easy to configure and quite flexible Generator Start/stop function of the Virtual Switch, or the more advanced [[assistants:overview_of_available_assistants#generator_start_and_stop|Generator start/stop Assistant]]+The Multis, MultiPlus-IIs, Quattros, EasySolars and the rest of the VE.Bus family also have Generator start/stop feature with a relayThere are two different ways to configure them: 
 + 
 +  - [[ve.bus:virtual-switch-generator-start-stop|Generator Start/stop function of the Virtual Switch]] (recommended) 
 +  - [[assistants:overview_of_available_assistants#generator_start_and_stop|Generator start/stop Assistant]] (more advanced / complex)
  
 Lastly, its of course also possible to combine above mentioned methods, by wiring the open contacts in parallel to each other, or in series, to the Generator. Lastly, its of course also possible to combine above mentioned methods, by wiring the open contacts in parallel to each other, or in series, to the Generator.
  
-===== Starting a genset with three-wire interface =====+==== 2. How to wire a a genset with three-wire interface ====
  
-For example Cummins/Onan gensets, that need a start pulse and a stop pulse.+All above products and devices have a single relay; that require a generator that starts and keeps running when- and while the relay is closed; and stops again when opened. Or the other way around. 
 + 
 +When having a generator that requires a start pulse and a stop pulse, such as for example Cummins/Onan generators; additional wiring is required.
  
 To start such a genset, the open/close contact needs to be converted into a start and stop pulse. Below solution, using standard available timing relays, does exactly that: when the open/close contact closes it generates the start pulse, and when the open/close contact opens again it generates the stop pulse.  To start such a genset, the open/close contact needs to be converted into a start and stop pulse. Below solution, using standard available timing relays, does exactly that: when the open/close contact closes it generates the start pulse, and when the open/close contact opens again it generates the stop pulse. 
Line 40: Line 47:
 i have some systeme using this solution and all looks ok i have some systeme using this solution and all looks ok
  
 +