Various Victron products have functions to automatically signal when to start and stop a generator. Here is advice on when to use which product and method. | Various Victron products have functions to automatically signal when to start and stop a generator. Here is advice on when to use which product and method. | ||
- | When there is a [[venus-os: | + | When there is a [[venus-os: |
The next most used option is a BMV-700 Battery Monitor or similar model. It can start the generator on low battery voltage and/or low battery state of charge. See the [[https:// | The next most used option is a BMV-700 Battery Monitor or similar model. It can start the generator on low battery voltage and/or low battery state of charge. See the [[https:// | ||
Line 23: | Line 23: | ||
{{ : | {{ : | ||
- | ===== DISQUS ===== | + | ==== Alternative using Assistants |
- | ~~DISQUS~~ | + | (provided by Thierry Cortasa) |
+ | |||
+ | hy | ||
+ | |||
+ | just for information, | ||
+ | i use k1 and k2 relais and relai programmable assistant | ||
+ | |||
+ | first to close k1 if voltage under 24v (for exemple) | ||
+ | segond to open k1 if ac1 avalable | ||
+ | third to close k2 if voltage uper 27v (for exemple) | ||
+ | last to open k2 if ac1 not avalable | ||
+ | |||
+ | in this case you have a three-wire system with out any think more needed ! | ||
+ | |||
+ | i have some systeme using this solution and all looks ok | ||
+ |