actor_ess [2019-05-24 12:27] – lucian | actor_ess [2019-06-11 10:03] – lucian | ||
---|---|---|---|
Line 2: | Line 2: | ||
- | When the batteries are full, we still have PV power available, but our grid operator doesn' | + | When the batteries are full, we still have PV power available, but our grid operator doesn' |
- | The schematic for the ESS system looks like this: | + | The schematic for the ESS system looks like this (the meter from MyPv is not needed in this setup): |
Line 26: | Line 26: | ||
{{:: | {{:: | ||
+ | |||
Please check the firmware version on AC-Thor device, must be at least a0010006. | Please check the firmware version on AC-Thor device, must be at least a0010006. | ||
+ | Go to setting and select the “Mode”. For ESS select ”Hot water 3KW”, . | ||
+ | |||
+ | {{:: | ||
+ | |||
+ | In order to have communication between the Color/Venus GX device and Ac-Thor, some parameters must be configured: | ||
+ | |||
+ | |||
+ | |||
+ | On Signal Source, select “Adjustable Modbus TCP(Sunspec etc)”. | ||
+ | |||
+ | Device ID must be 0. | ||
+ | |||
+ | Metter Register 820, Int16 and -feed in. | ||
+ | |||
+ | For Scale Register, don’t select anything. | ||
+ | |||
+ | For Modbus Port, leave the default value (502). | ||
+ | |||
+ | On the IP address field, you have to put the VenusGX/ | ||
+ | |||
+ | On the Control target, recommended value is -50W. | ||
+ | |||
+ | {{: | ||
+ | |||
+ | Press Save to store the parameters. | ||
+ | |||
+ | On the Venus/Color GX please be sure that Modbus TCP is enabled (Setting, Services, Modbus/ | ||
+ | |||
+ | {{: | ||
+ | |||
+ | Also in Setting /ESS, Feed-in excess solar power must me enabled for system with PV panels connected using MPPT’s | ||
+ | |||
+ | {{:: | ||
+ | |||
+ | If everything is correctly configured, you should see in the information screen of the Ac-Thor, the grid consumption/ | ||
+ | |||
+ | {{:: | ||
+ | {{:: | ||
+ | |||
+ | AC-Thor will control the energy sent to the boiler so that the energy sent to the grid is approximately 50W. | ||
+ | |||
+ | {{:: | ||
+ | |||
+ | To prevent boiler to over heat, please be sure the temperature sensor is connected to AC-Thor and installed inside the boiler. The temperature parameters can be configured in the settings menu: | ||
+ | |||
+ | {{:: | ||
+ | |||
+ | **AC-THOR Technical specifications: | ||
+ | |||
+ | * mains voltage 230 V, 50 Hz | ||
+ | |||
+ | * outputs 0-3000 W infinitely variable + switching output 16 A | ||
+ | |||
+ | * mains connection Single-phase, | ||
+ | |||
+ | * consumer connection Protective contact socket for resistive loads | ||
+ | |||
+ | * display Color Graphics, Touch Screen 2.83 " | ||
+ | |||
+ | * connection cable 2,8 m | ||
+ | |||
+ | * dimensions (W x H x D) 135 x 210 x 65 mm | ||
+ |
actor_ess.txt · Last modified: 2021-02-17 13:34 by bob