ac_coupling:start
Differences
This shows you the differences between two versions of the page.
| Both sides previous revisionPrevious revisionNext revision | Previous revision | ||
| ac_coupling:start [2019-01-21 10:33] – [DISQUS] ictbeheer | ac_coupling:start [2026-09-01 10:41] (current) – [2.4 Should you look at the total PV array, or the PV inverter rating?] sloges | ||
|---|---|---|---|
| Line 2: | Line 2: | ||
| ===== 1. Introduction to the AC-Coupling concept ===== | ===== 1. Introduction to the AC-Coupling concept ===== | ||
| - | Already familiar with the concepts of AC-coupling and regulating PV inverter output power by frequency shifting? Skip to [[: | + | Already familiar with the concepts of AC-coupling and regulating PV inverter output power by frequency shifting? Skip to the requirements and limitations: |
| + | |||
| + | - [[: | ||
| + | - [[: | ||
| + | - [[: | ||
| + | |||
| ==== 1.1 What is AC-coupling? | ==== 1.1 What is AC-coupling? | ||
| + | |||
| + | {{: | ||
| In an AC-coupled system, a grid-tied PV inverter is connected to the output of a Multi, Inverter or Quattro. PV power is first used to power the loads, then to charge the battery, and any excess PV power can be fed back to the grid. | In an AC-coupled system, a grid-tied PV inverter is connected to the output of a Multi, Inverter or Quattro. PV power is first used to power the loads, then to charge the battery, and any excess PV power can be fed back to the grid. | ||
| Line 16: | Line 24: | ||
| * Systems with only a grid-tied PV inverter will fail when there is a grid black-out. A micro-grid system will continue to operate, and even keep using solar power. | * Systems with only a grid-tied PV inverter will fail when there is a grid black-out. A micro-grid system will continue to operate, and even keep using solar power. | ||
| * It is also possible to run a AC-coupled micro-grid on a generator | * It is also possible to run a AC-coupled micro-grid on a generator | ||
| - | * Most brands of PV inverters can be used for these systems, they need to be setup to support frequency shifting, often called the island-mode or micro-grid mode. For Fronius settings, see [[ac_coupling: | + | * Most brands of PV inverters can be used for these systems, they need to be setup to support frequency shifting, often called the island-mode or micro-grid mode. For SolarEdge settings, see [[venus-os: |
| + | * To read out SMA inverters, see [[ccgx: | ||
| * If power will be fed back into the grid an anti-islanding device may have to be added to the system, depending on local regulations. | * If power will be fed back into the grid an anti-islanding device may have to be added to the system, depending on local regulations. | ||
| Line 26: | Line 35: | ||
| - | ===== 2. The 1.0 rule: Max PV power must be equal or less than the VA rating of the Multi ===== | + | ===== 2. The Factor |
| + | **The max PV power must be equal to or less than the continuous output power at 25 °C of the inverter/ | ||
| ==== 2.1 Rule definition ==== | ==== 2.1 Rule definition ==== | ||
| - | In both grid-connected and off-grid systems with PV inverters installed on the output of a Multi, Inverter or Quattro, there is a maximum of PV power that can be installed. | + | In both grid-connected and off-grid systems with PV inverters installed on the output of a Multi, Inverter or Quattro, there is a maximum of PV power that can be installed. |
| + | |||
| + | A MultiPlus-II 48/3000 is rated 2400 W continuous at 25 °C, so the maximum is 2400 Wp of installed solar power. | ||
| ==== 2.2 Example and background ==== | ==== 2.2 Example and background ==== | ||
| Line 42: | Line 54: | ||
| ==== 2.3 Charge current limit ==== | ==== 2.3 Charge current limit ==== | ||
| - | Another | + | A question frequently asked is how PV power up to the full continuous output rating |
| - | An example, | + | An example, |
| - | - When the Multi is connected to the grid, all 3000 W can be fed back to the grid through the Multi, no problem. | + | - When the Multi is connected to the grid, all 2400 W can be fed back to the grid through the Multi, no problem. |
| - | - In case the Multi is not connected to the grid, the 3000 Wp is more than the charger in a Multi 3000 VA can handle. The charger is around 2000 W. Therefore the grid inverter assistant will automatically increase the frequency to reduce the output of the grid inverter, to match maximum charge current. | + | - In case the Multi is not connected to the grid, the 2400 Wp is more than the charger in a Multi 3000 VA can handle. The charger is around 2000 W. Therefore the grid inverter assistant will automatically increase the frequency to reduce the output of the grid inverter, to match maximum charge current. |
| ==== 2.4 Should you look at the total PV array, or the PV inverter rating? ==== | ==== 2.4 Should you look at the total PV array, or the PV inverter rating? ==== | ||
| - | The mentioned | + | The mentioned |
| And for an undersized PV array, where the total Wp of installed PV panels is less than the installed PV grid inverter, you use the Wp from the PV panels in your calculation. | And for an undersized PV array, where the total Wp of installed PV panels is less than the installed PV grid inverter, you use the Wp from the PV panels in your calculation. | ||
| Line 57: | Line 69: | ||
| ===== 3. Minimum battery capacity ===== | ===== 3. Minimum battery capacity ===== | ||
| - | Besides the relation between installed PV Power and the inverter/ | + | Besides the relation between installed PV Power and the continuous output power of the inverter/ |
| Note that, besides the minimum battery capacity, the mentioned sizes are often also the most economical battery size. In case used for self-consumption purposes that is. In case the goal is to increase autonomy, of course installing a large battery increases the system autonomy in case of a grid failure. | Note that, besides the minimum battery capacity, the mentioned sizes are often also the most economical battery size. In case used for self-consumption purposes that is. In case the goal is to increase autonomy, of course installing a large battery increases the system autonomy in case of a grid failure. | ||
| ==== 3.1 Lead batteries ==== | ==== 3.1 Lead batteries ==== | ||
| - | 1 kWp installed PV power requires approximately 5kWh of battery: | + | 1 kWp installed PV power requires approximately 5kWh of lead acid battery: |
| - | * 100 Ah accubank | + | * 100 Ah at 48 Vdc |
| - | * 200 Ah accubank | + | * 200 Ah at 24 Vdc |
| - | * 400 Ah accubank | + | * 400 Ah at 12 Vdc |
| + | Each additional 1 kWp of AC PV will require an additional proportional 5 kWh increase in lead acid battery storage. | ||
| ==== 3.2 Lithium batteries ==== | ==== 3.2 Lithium batteries ==== | ||
| - | 1,5 kWp installed PV power requires: | + | 1,5 kWp installed |
| - | * 100 Ah accubank | + | * 100 Ah at 48 Vdc |
| - | * 200 Ah accubank | + | * 200 Ah at 24 Vdc |
| - | * 400 Ah accubank | + | * 400 Ah at 12 Vdc |
| - | ==== 4 Software configuration | + | Each additional 1.5 kWp of AC PV will require an additional proportional 4.8 kWh increase in battery storage. |
| + | ===== 4 Requirement of adding DC-Coupling - MPPT Solar Chargers ===== | ||
| - | Multis and Quattros with factory settings will not shift the AC output frequency to regulate charge current. When setting up an AC Coupled system, install either the [[ess: | + | Not required for Energy Storage Systems in Germany or other reliable grid situations. |
| + | |||
| + | Required for offgrid systems as well as backup systems that need to overcome extended grid failures. | ||
| + | |||
| + | Reason: recover from deadlock situation of AC-Coupling only situation. | ||
| + | |||
| + | There is no Factor 1.0 limit that applies for DC coupled PV through a Victron MPPT. Nor is there a specific minimum amount of battery storage capacity, though please follow battery manufacture specifications for maximum charge rates. A rule of thumb is C10 (10% of Ah capacity in A) for lead acid batteries, and C2 (50% of Ah capacity in A) for lithium batteries. | ||
| + | |||
| + | ===== 5 Software configuration ===== | ||
| + | |||
| + | Multis and Quattros with factory settings will not shift the AC output frequency to regulate charge current. When setting up an AC Coupled system, install either the [[ess: | ||
| + | |||
| + | The Inverter RS will automatically shift frequency without any additional configuration required when a surplus/ | ||
| Other options, __all deprecated__, | Other options, __all deprecated__, | ||
| Line 81: | Line 107: | ||
| - Hub-4 Assistant in combination with the PV Inverter support Assistant | - Hub-4 Assistant in combination with the PV Inverter support Assistant | ||
| - Use the Inverter period time settings on the Virtual switch tab. | - Use the Inverter period time settings on the Virtual switch tab. | ||
| + | |||
| + | ===== Monitoring ===== | ||
| + | |||
| + | See [[https:// | ||
| + | |||
| + | ===== DISQUS ===== | ||
| + | ~~DISQUS~~ | ||
ac_coupling/start.1548063218.txt.gz · Last modified: by ictbeheer
