ac_coupling:fronius

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
ac_coupling:fronius [2016-10-14 10:48]
jperez [AC-coupled PV with Fronius PV Inverters]
ac_coupling:fronius [2019-08-06 08:53] (current)
bob [Zero Feed-in]
Line 13: Line 13:
 To make sure that the Fronius PV inverter works well with Victron inverter/​chargers,​ both must be configured with the right '​frequency shift settings':​ To make sure that the Fronius PV inverter works well with Victron inverter/​chargers,​ both must be configured with the right '​frequency shift settings':​
   * The Fronius PV Inverter must be set to Setup MG, short for Micro-Grid. ​   * The Fronius PV Inverter must be set to Setup MG, short for Micro-Grid. ​
-  * The Victron inverter/​charger must be loaded ​with either ​the PV Inverter support Assistant or the Hub-2 v3 Assistant. ​+  * For off-grid systems, load the Multi or Quattro ​with the PV Inverter support Assistant 
 +  * For on-grid / energy-storage systems, load the Multi or Quattro with the ESS Assistant. Read information about ESS in the [[ess:​design-installation-manual|]].
  
-And the [[ac_coupling:​start|1:​1 rule]] must be adhered to.+And the [[ac_coupling:​start|1:​1 ​limit rule]] must be adhered to.
  
 ===== Fronius / Victron specifics ===== ===== Fronius / Victron specifics =====
Line 22: Line 23:
    
 Compatible inverters are: Compatible inverters are:
-  * Fronius ​Symo (3~, 3 kW up to 20 kW) -> Software //​fro27140.upd//​ or higher +  * Fronius ​Primo (1~, 3 kW up to 8.2 kW) -> Software //​fro27140.upd//​ or higher ​(see FAQ Q5!) 
-  * Fronius ​Eco (3~, 25 kW or 27 kW) -> Software //​fro27140.upd//​ or higher +  * Fronius ​Symo (3~, kW up to 20 kW) -> Software //​fro27140.upd//​ or higher ​(see FAQ Q5!) 
-  * Fronius ​Primo (1~, kW up to 8.2 kW) -> Software //​fro27140.upd//​ or higher+  * Fronius ​Eco (3~, 25 kW or 27 kW) -> Software //​fro27140.upd//​ or higher ​(see FAQ Q5!)
   * Fronius Agilo (3~, 75 kW up to 100 kW) -> Software //​update19.tl//​ or higher   * Fronius Agilo (3~, 75 kW up to 100 kW) -> Software //​update19.tl//​ or higher
   * Fronius IG Plus V (1~, 2~, 3~, 2.5 kW up to 12 kW) -> from //IGF 5.0.66// on with settings according to the Victron recommendations   * Fronius IG Plus V (1~, 2~, 3~, 2.5 kW up to 12 kW) -> from //IGF 5.0.66// on with settings according to the Victron recommendations
Line 48: Line 49:
   - Go to the tab Assistants: \\ {{:​ac_coupling:​add_assistant.png?​nolink&​}}   - Go to the tab Assistants: \\ {{:​ac_coupling:​add_assistant.png?​nolink&​}}
   - Add one of the Assistants that regulate output frequency:   - Add one of the Assistants that regulate output frequency:
-      - Self-consumption Hub-2 v2 +      - [[ess:​design-installation-manual|ESS Assistant]]
-      - Self-consumption Hub-2 v3+
       - PV Inverter support       - PV Inverter support
   - Note that it is not necessary to change the default settings in the Assistant. \\ {{:​ac_coupling:​8b249443cd6d2a5632b07998773a1e6d.png?​nolink&​}} \\   - Note that it is not necessary to change the default settings in the Assistant. \\ {{:​ac_coupling:​8b249443cd6d2a5632b07998773a1e6d.png?​nolink&​}} \\
Line 57: Line 57:
 Table for settings for 50Hz and 60Hz frequency Table for settings for 50Hz and 60Hz frequency
 | ** State ** | ** 50Hz ** | ** 60Hz ** |. | | ** State ** | ** 50Hz ** | ** 60Hz ** |. |
-| Start| ​50.| 60.2|Hz|+| Start| ​51.| 60.2|Hz|
 | Minimum| 52.7 | 62.7|Hz| | Minimum| 52.7 | 62.7|Hz|
 | Disconnect| 53.0 | 63.0|Hz| \\ | Disconnect| 53.0 | 63.0|Hz| \\
Line 75: Line 75:
 A video instruction how to set up the Datamanager 2.0 + Solar.web can be found [[https://​youtu.be/​u_DX7PmHPXQ|here]]. A video instruction how to set up the Datamanager 2.0 + Solar.web can be found [[https://​youtu.be/​u_DX7PmHPXQ|here]].
  
-===== Frequently asked questions ​=====+===== Zero Feed-in ​=====
  
-=== Why doesn'​t the frequency settings in the Multi and the Fronius need to be the same? ===+It is possible to make a Zero feed-in system with Victron & Fronius. The Venus device will the control the Fronius output power. See the [[ess:​design-installation-manual|ESS manual]], chapter 4.3.11 Fronius Zero feed-in for details. 
 +===== Frequently Asked Questions ===== 
 + 
 +==== Q1 Why doesn'​t the frequency settings in the Multi and the Fronius need to be the same? ====
  
 The first two frequencies do not need to be the same since the Multi actively regulates. ​ The first two frequencies do not need to be the same since the Multi actively regulates. ​
  
-=== I have an Fronius IG inverter (not Plus), can that work? ===+==== Q2 I have an Fronius IG inverter (not Plus), can that work? ====
 No, the IG inverters cannot be made to work in a MicroGrid system. The appropriate substitute for an IG 30 is the GALVO 2.5-1 or an IG Plus 25V-1 (depending on the desired DC voltage range). No, the IG inverters cannot be made to work in a MicroGrid system. The appropriate substitute for an IG 30 is the GALVO 2.5-1 or an IG Plus 25V-1 (depending on the desired DC voltage range).
  
 +==== Q3 The system is locked to 53 Hz and does not resume ====
 +See [[:​assistants:​pv-inverter-support#​q1_the_system_is_locked_to_53_hz_and_does_not_resume|here]].
 +==== Q4 Can I use the Fronius Smart Meter? ====
 +
 +That depends on the type of system and software configuration.
 +
 +A Fronius Smart Meter can be used in these two situations:
 +
 +  - when used only for reporting to Solarweb
 +  - when used for limiting export, in a system where the Victron system is not configured as an ESS system.
 +
 +The Fronius Smart-Meter can not be used for the Fronius built-in export limiting feature when part of a Victron ESS system. Instead, use the Victron ESS Fronius Zero-feed in feature, see chapter 4.3.11, Fronius Zero Feed-in, in the [[ess:​design-installation-manual|ESS manual]].
 +
 +
 +==== Q5 How can I get the Fronius firmware that improves flickering? ====
 +
 +Fronius has a special firmware available, on request, that fixes light flickering issues that occur on certain installations under certain circumstances.
 +
 +For Fronius PV inverters produced after 2018-week 16, contain the flicker-fix already straight from production.
 +
 +To update earlier and/or already installed PV Inverters, contact Fronius Tech Support for the file. The required file is fro29130.upd. Which works for all snap-inverter models (Primo, Symo and Eco). There is no, and will be no, fix available for Fronius Galvos.
 +
 +===== DISQUS =====
  