 ====== AC-coupled PV with Fronius PV Inverters ====== ====== AC-coupled PV with Fronius PV Inverters ======
  
-This document describes how to setup Victron Hub-2 and Off-grid systems with AC-coupled PV (micro grids), using Fronius PV Inverters. For Fronius information on the same subject, see their [[http://​www.fronius.com/​cps/​rde/​xbcr/​SID-F75BE891-A018D2F4/​fronius_international/​SE_DOC_FLY_MicroGrids_GridFormer_EN_326404_snapshot.pdf|MicroGrid flyer]].+This document describes how to setup Energy-storage, ​Off-grid/Micro-grid and Backup ​systems with AC-coupled PV, using Fronius PV Inverters. For Fronius information on the same subject, see their [[http://​www.fronius.com/​cps/​rde/​xbcr/​SID-F75BE891-A018D2F4/​fronius_international/​SE_DOC_FLY_MicroGrids_GridFormer_EN_326404_snapshot.pdf|MicroGrid flyer]].
  
-Integrated ​system ​monitoring: use the [[http://​www.victronenergy.com/​panel-systems-remote-monitoring/​color-control|Color Control GX]] (CCGX) and its [[ccgx:​ccgx_fronius|Fronius monitoring ​function]].+The Victron ​system ​monitor, ​the [[https://​www.victronenergy.com/​panel-systems-remote-monitoring/​color-control|Color Control GX]] includes ​[[ccgx:​ccgx_fronius|built-in ​Fronius monitoring]].
  
-===== Introduction to frequency shifting =====+{{:​ac_coupling:​ccgx_devicelist_fronius.png?​direct|}} 
 +{{:​ac_coupling:​ccgx_hub4_overview_froniusicon.png?​direct|}}
  
-To make sure that the Fronius PV inverter works well with Victron inverter/​chargers,​ both must be configureren ​with the right '​frequency shift settings'​. //[To do add a few lines to explain what ac frequency shifting is and what it is for, including link to factor 1.0 rule page. Some snippets: makes the Fronius ​PV inverter limit its output power based on the AC frequency.See the following graph, ​with the frequency on the X-axis, and the maximum output power as a percentage]//+ 
 +===== Frequency shifting ===== 
 + 
 +To make sure that the Fronius PV inverter works well with Victron inverter/​chargers,​ both must be configured ​with the right '​frequency shift settings'​
 +  * The Fronius PV Inverter must be set to Setup MG, short for Micro-Grid 
 +  * For off-grid systems, load the Multi or Quattro with the PV Inverter support Assistant 
 +  * For on-grid / energy-storage systems, load the Multi or Quattro ​with the ESS Assistant. Read information about ESS in the [[ess:​design-installation-manual|]]. 
 + 
 +And the [[ac_coupling:​start|1:​1 limit rule]] must be adhered to.
  
 ===== Fronius / Victron specifics ===== ===== Fronius / Victron specifics =====
  
-With a Fronius PV inverter this is a very easy setup. The Fronius Setup MicroGrid (MG) has been developed in close cooperation with Victron ​EnergySimply order the PV Inverters with option ​Setup MG 50 (for 50 Hz systems) ​or Setup 60 for 60 Hz systems. Everything is then preconfigured. The MG Setups have all the necessary ​settings ​preconfigured,​ and match the default Victron Assistant settings, such as: +This is a very easy setup. The Fronius Setup Microgrid ​has been developed in close cooperation with Victron. ​During commissioning,​ set the PV Inverter to Setup MG50 (or Setup MG60 for 60 Hz systems). Everything is then pre-configured. The Setup MG settings match the default Victron Assistant settings.
-  +
-  * Tolerant voltage and frequency boundaries +
-  * Disable Anti-Islanding detection +
-  * Frequency dependent power reduction according to the graph in the [[http://​www.fronius.com/​cps/​rde/​xbcr/​SID-F75BE891-A018D2F4/​fronius_international/​SE_DOC_FLY_MicroGrids_GridFormer_EN_326404_snapshot.pdf|MicroGrid flyer]] (Starting at 51 Hz with a droop of 60 %/Hz, so at 52.8 Hz the power = zero and the inverter disconnects at 53 Hz)+
    
 Compatible inverters are: Compatible inverters are:
-  * Fronius ​IG Plus V (1~, 2~, 3~, 2.5 kW up to 12 kW) -> from IGF 5.0.66 on with settings according to the VICTRON recommendations. +  * Fronius ​Primo (1~, 3 kW up to 8.2 kW) -> Software //fro27140.upd// or higher ​(see FAQ Q5!
-  * Fronius Galvo (1~, 1.5 kW up to 3.1 kW-> use latest FW +  * Fronius Symo (3~, 3 kW up to 20 kW) -> Software //​fro27140.upd//​ or higher (see FAQ Q5!) 
-  * Fronius Symo (3~, 3 kW up to 20 kW) -> use latest FW +  * Fronius ​Eco (3~, 25 kW or 27 kW) -> Software //​fro27140.upd//​ or higher ​(see FAQ Q5!
-  * Fronius ​Primo (1~, kW up to 8.2 kW) -> use FW that will be available next week (week32+  * Fronius ​Agilo (3~, 75 kW up to 100 kW) -> Software //​update19.tl//​ or higher 
-  * Fronius ​Eco (3~, 25 kW up to 27 kW) -> use latest FW +  * Fronius ​IG Plus V (1~, 2~, 3~, 2.5 kW up to 12 kW) -> from //IGF 5.0.66// on with settings according to the Victron recommendations
-  * Fronius ​Agilo (3~, 75 kW up to 100 kW) -> use latest FW+
  
-Recommended for new systems ​are the SYMO inverters for 3~ systems and PRIMO inverters for 1~ systemsDo note that these products topology is transformerless and therefore PV-Modules that need to be grounded ​cannot be connected.+For new systems the Symo and Eco inverters ​are recommended ​for 3~ applications. The Primo inverters ​are recommended ​for 1~ applicationsPlease ​note that all these inverters are transformerless and therefore PV-Modules that require pole-grounding (on the Plus or Minus pole) cannot be connected.
  
-In case of PV modules that need to be grounded, ​use inverters from the IG Plus V series or Fronius Galvo inverters.+The use of Fronius Galvo inverters ​is not recommended anymore for new applications - the Fronius Primo is the best substitute and offers higher efficiency, wider DC voltage range, two MPP trackers and many other features.
  
-When setting up a system, always update both the Fronius and the Victron devices to their latest versions.+When setting up a system, always update both the Fronius and the Victron devices to their latest ​firmware ​versions. ​For the latest Fronius firmware and information how to update use this link: 
 +[[http://​www.fronius.com/​cps/​rde/​xchg/​SID-0E6A6973-2D12EBA2/​fronius_international/​hs.xsl/​83_20347_ENG_HTML.htm#​.VouMJOb9XxQ|Fronius firmware update]]
  
-===== Setting up the Fronius with MG 50/60 =====+===== Setting up the Fronius with Setup MG50/MG60 =====
  
 When not pre-ordered with a MicroGrid setup, follow these steps: When not pre-ordered with a MicroGrid setup, follow these steps:
-  - Make sure that the Fronius PV inverter is updated to at least the firmware version mentioned above. See table above.+  - Make sure that the Fronius PV inverter is updated to at least the firmware version mentioned above. See Inverter list above.
   - After making the inverter operational according to the manual, select the language and after this the country specific setup.   - After making the inverter operational according to the manual, select the language and after this the country specific setup.
   - Here choose MG50 or MG60 depending on the system frequency.   - Here choose MG50 or MG60 depending on the system frequency.
Line 44: Line 49:
   - Go to the tab Assistants: \\ {{:​ac_coupling:​add_assistant.png?​nolink&​}}   - Go to the tab Assistants: \\ {{:​ac_coupling:​add_assistant.png?​nolink&​}}
   - Add one of the Assistants that regulate output frequency:   - Add one of the Assistants that regulate output frequency:
-      - Self-consumption Hub-2 v2 +      - [[ess:​design-installation-manual|ESS Assistant]]
-      - Self-consumption Hub-2 v3+
       - PV Inverter support       - PV Inverter support
-  - Note that it is not necessary to change the default settings in the Assistant. The default settings work together with the default Fronius Micro-grid settings. \\ {{:​ac_coupling:​8b249443cd6d2a5632b07998773a1e6d.png?​nolink&​}} \\+  - Note that it is not necessary to change the default settings in the Assistant. \\ {{:​ac_coupling:​8b249443cd6d2a5632b07998773a1e6d.png?​nolink&​}} \\
   - Complete the rest of the Assistant and write the new settings to the MultiPlus or Quattro.   - Complete the rest of the Assistant and write the new settings to the MultiPlus or Quattro.
 \\ \\
  
-===== Frequently asked questions =====+Table for settings for 50Hz and 60Hz frequency 
 +| ** State ** | ** 50Hz ** | ** 60Hz ** |. | 
 +| Start| 51.0 | 60.2|Hz| 
 +| Minimum| 52.7 | 62.7|Hz| 
 +| Disconnect| 53.0 | 63.0|Hz| \\
  
-=== Why doesn'​t the frequency settings in the Multi and the Fronius need to be the same? ===+More information on adding Assistants is [[assistants:​how_to_add_and_configure_an_assistant|here]]. 
 + 
 +===== Remote system monitoring ===== 
 + 
 +The Victron system can be monitored through Victron VRM Portal if a [[https://​www.victronenergy.com/​panel-systems-remote-monitoring/​color-control|Color Control GX]] is present at the site. 
 +The Fronius PV inverter data can be [[ccgx:​ccgx_fronius|integrated into the Color Control GX]]  and therefore also in the VRM portal. 
 +So the VRM portal is the recommended monitoring platform also for AC-coupled installations. 
 +  
 +However, also Fronius offers an equivalent monitoring solution. The Fronius portal is called Fronius Solar.web. The PV system data can be transfered to the portal if the inverter is equipped with a Datamanager 1.0 or Datamanager 2.0. 
 + 
 +The usage of both portals in parallel is possible. 
 + 
 +A video instruction how to set up the Datamanager 2.0 + Solar.web can be found [[https://​youtu.be/​u_DX7PmHPXQ|here]]. 
 + 
 +===== Zero Feed-in ===== 
 + 
 +It is possible to make a Zero feed-in system with Victron & Fronius. The Venus device will the control the Fronius output power. See the [[ess:​design-installation-manual|ESS manual]], chapter 4.3.11 Fronius Zero feed-in for details. 
 +===== Frequently Asked Questions ===== 
 + 
 +==== Q1 Why doesn'​t the frequency settings in the Multi and the Fronius need to be the same? ====
  
 The first two frequencies do not need to be the same since the Multi actively regulates. ​ The first two frequencies do not need to be the same since the Multi actively regulates. ​
  
-=== I have an Fronius IG inverter (not Plus), can that work? ===+==== Q2 I have an Fronius IG inverter (not Plus), can that work? ====
 No, the IG inverters cannot be made to work in a MicroGrid system. The appropriate substitute for an IG 30 is the GALVO 2.5-1 or an IG Plus 25V-1 (depending on the desired DC voltage range). No, the IG inverters cannot be made to work in a MicroGrid system. The appropriate substitute for an IG 30 is the GALVO 2.5-1 or an IG Plus 25V-1 (depending on the desired DC voltage range).
  
 +==== Q3 The system is locked to 53 Hz and does not resume ====
 +See [[:​assistants:​pv-inverter-support#​q1_the_system_is_locked_to_53_hz_and_does_not_resume|here]].
 +==== Q4 Can I use the Fronius Smart Meter? ====
 +
 +That depends on the type of system and software configuration.
 +
 +A Fronius Smart Meter can be used in these two situations:
 +
 +  - when used only for reporting to Solarweb
 +  - when used for limiting export, in a system where the Victron system is not configured as an ESS system.
 +
 +The Fronius Smart-Meter can not be used for the Fronius built-in export limiting feature when part of a Victron ESS system. Instead, use the Victron ESS Fronius Zero-feed in feature, see chapter 4.3.11, Fronius Zero Feed-in, in the [[ess:​design-installation-manual|ESS manual]].
 +
 +
 +==== Q5 How can I get the Fronius firmware that improves flickering? ====
 +
 +Fronius has a special firmware available, on request, that fixes light flickering issues that occur on certain installations under certain circumstances.
 +
 +For Fronius PV inverters produced after 2018-week 16, contain the flicker-fix already straight from production.
 +
 +To update earlier and/or already installed PV Inverters, contact Fronius Tech Support for the file. The required file is fro29130.upd. Which works for all snap-inverter models (Primo, Symo and Eco). There is no, and will be no, fix available for Fronius Galvos.
 +