| - | - Carefully review | + | - It is not necessary to change |
| - Complete the rest of the Assistant and write the new settings to the MultiPlus or Quattro. | - Complete the rest of the Assistant and write the new settings to the MultiPlus or Quattro. | ||
| \\ | \\ | ||
| - | Suggested | + | Table with general |
| | ** State ** | ** 50Hz ** | ** 60Hz ** |. | | | ** State ** | ** 50Hz ** | ** 60Hz ** |. | | ||
| | Start| 50.2 | 60.2|Hz| | | Start| 50.2 | 60.2|Hz| | ||
| | Minimum| 52.7 | 62.7|Hz| | | Minimum| 52.7 | 62.7|Hz| | ||
| | Disconnect| 53.0 | 63.0|Hz| \\ | | Disconnect| 53.0 | 63.0|Hz| \\ | ||
| - | |||
| - | Suggested suggested settings for frequency (Fronius firmware after fro35020) | ||
| - | | ** State ** | ** 50Hz ** | ** 60Hz ** |. | | ||
| - | | Start| 50.2 | 60.2|Hz| | ||
| - | | Minimum| 53.1 | 63.1|Hz| | ||
| - | | Disconnect| 53.5 | 63.5|Hz| \\ | ||
| - | |||
| Note that although the MG50 for instance has a higher start frequency of 51Hz, there is no real drawback using the proposed value of 50.2Hz. The system will just increase the frequency until the PV inverter regulation kicks in. The value of 50.2Hz will work with a broader range of PV inverters/ | Note that although the MG50 for instance has a higher start frequency of 51Hz, there is no real drawback using the proposed value of 50.2Hz. The system will just increase the frequency until the PV inverter regulation kicks in. The value of 50.2Hz will work with a broader range of PV inverters/ | ||
| Line 84: | Line 77: | ||
| More information on adding Assistants is [[assistants: | More information on adding Assistants is [[assistants: | ||
| + | ===== 1.5 Known frequency exceptions ===== | ||
| + | * Fronius bundles between fro35020 and fro36120 (at time of writing) contains a change that holds the inverter relay closed up to 53Hz for grid code MG50, or 63Hz for MG60. This sometimes causes problems when reconnecting to the grid. Please set the Disconnect frequency to 53.1Hz/ | ||