===== 2.5 Zero Feed-in ===== | ===== 2.5 Zero Feed-in ===== | ||
- | It is possible to make a Zero feed-in system with Victron & Fronius. The Venus device will the control the Fronius output power. See the [[ess:design-installation-manual|ESS manual]], chapter 4.3.11 Fronius Zero feed-in for details. | + | It is possible to make a Zero feed-in system with Victron & Fronius. The Venus device will the control the Fronius output power. See the [[https:// |
Line 258: | Line 258: | ||
To update earlier and/or already installed PV Inverters, contact Fronius Tech Support for the file. The required file is fro29130.upd. Which works for all snap-inverter models (Primo, Symo and Eco). There is no, and will be no, fix available for Fronius Galvos. | To update earlier and/or already installed PV Inverters, contact Fronius Tech Support for the file. The required file is fro29130.upd. Which works for all snap-inverter models (Primo, Symo and Eco). There is no, and will be no, fix available for Fronius Galvos. | ||
+ | ==== Q6 What do I do if my Fronius PV-inverter is detected as Unknown PV-inverter and cannot be configured as 3-phase? ==== | ||
+ | Later Fronius PV-inverters support both the Fronius SolarAPI- as well as the industry standard SunSpec protocol. When SunSpec is not available the GX device cannot properly detect the properties of the PV-inverter unless it is one of a fixed list of known older models. Newer PV-inverters will then show up as Unknown, and you will not be able to configure them as 3-phase. | ||
+ | |||
+ | The solution is to configure SunSpec support on the PV-inverter. | ||
+ | * Log into the Fronius web interface. | ||
+ | * Go to the Modbus tab | ||
+ | * Set Data export via Modbus to tcp. | ||
+ | * set Sunspec Model Type to int + SF | ||