ac_coupling:fronius
Differences
This shows you the differences between two versions of the page.
Both sides previous revisionPrevious revisionNext revision | Previous revisionNext revisionBoth sides next revision | ||
ac_coupling:fronius [2016-10-14 10:48] – [AC-coupled PV with Fronius PV Inverters] jperez | ac_coupling:fronius [2019-01-21 10:33] – [DISQUS] ictbeheer | ||
---|---|---|---|
Line 13: | Line 13: | ||
To make sure that the Fronius PV inverter works well with Victron inverter/ | To make sure that the Fronius PV inverter works well with Victron inverter/ | ||
* The Fronius PV Inverter must be set to Setup MG, short for Micro-Grid. | * The Fronius PV Inverter must be set to Setup MG, short for Micro-Grid. | ||
- | * The Victron inverter/ | + | * For off-grid systems, load the Multi or Quattro |
+ | * For on-grid / energy-storage systems, load the Multi or Quattro with the ESS Assistant. Read information about ESS in the [[ess: | ||
- | And the [[ac_coupling: | + | And the [[ac_coupling: |
===== Fronius / Victron specifics ===== | ===== Fronius / Victron specifics ===== | ||
Line 22: | Line 23: | ||
Compatible inverters are: | Compatible inverters are: | ||
- | * Fronius | + | * Fronius |
- | * Fronius | + | * Fronius |
- | * Fronius | + | * Fronius |
* Fronius Agilo (3~, 75 kW up to 100 kW) -> Software // | * Fronius Agilo (3~, 75 kW up to 100 kW) -> Software // | ||
* Fronius IG Plus V (1~, 2~, 3~, 2.5 kW up to 12 kW) -> from //IGF 5.0.66// on with settings according to the Victron recommendations | * Fronius IG Plus V (1~, 2~, 3~, 2.5 kW up to 12 kW) -> from //IGF 5.0.66// on with settings according to the Victron recommendations | ||
Line 48: | Line 49: | ||
- Go to the tab Assistants: \\ {{: | - Go to the tab Assistants: \\ {{: | ||
- Add one of the Assistants that regulate output frequency: | - Add one of the Assistants that regulate output frequency: | ||
- | - Self-consumption Hub-2 v2 | + | - [[ess: |
- | - Self-consumption Hub-2 v3 | + | |
- PV Inverter support | - PV Inverter support | ||
- Note that it is not necessary to change the default settings in the Assistant. \\ {{: | - Note that it is not necessary to change the default settings in the Assistant. \\ {{: | ||
Line 57: | Line 57: | ||
Table for settings for 50Hz and 60Hz frequency | Table for settings for 50Hz and 60Hz frequency | ||
| ** State ** | ** 50Hz ** | ** 60Hz ** |. | | | ** State ** | ** 50Hz ** | ** 60Hz ** |. | | ||
- | | Start| | + | | Start| |
| Minimum| 52.7 | 62.7|Hz| | | Minimum| 52.7 | 62.7|Hz| | ||
| Disconnect| 53.0 | 63.0|Hz| \\ | | Disconnect| 53.0 | 63.0|Hz| \\ | ||
Line 75: | Line 75: | ||
A video instruction how to set up the Datamanager 2.0 + Solar.web can be found [[https:// | A video instruction how to set up the Datamanager 2.0 + Solar.web can be found [[https:// | ||
- | ===== Frequently asked questions | + | ===== Zero Feed-in |
- | === Why doesn' | + | It is possible to make a Zero feed-in system with Victron & Fronius. The Venus device will the control the Fronius output power. See the [[ess: |
+ | ===== Frequently Asked Questions ===== | ||
+ | |||
+ | ==== Q1 Why doesn' | ||
The first two frequencies do not need to be the same since the Multi actively regulates. | The first two frequencies do not need to be the same since the Multi actively regulates. | ||
- | === I have an Fronius IG inverter (not Plus), can that work? === | + | ==== Q2 I have an Fronius IG inverter (not Plus), can that work? ==== |
No, the IG inverters cannot be made to work in a MicroGrid system. The appropriate substitute for an IG 30 is the GALVO 2.5-1 or an IG Plus 25V-1 (depending on the desired DC voltage range). | No, the IG inverters cannot be made to work in a MicroGrid system. The appropriate substitute for an IG 30 is the GALVO 2.5-1 or an IG Plus 25V-1 (depending on the desired DC voltage range). | ||
+ | |||
+ | ==== Q3 The system is locked to 53 Hz and does not resume ==== | ||
+ | See [[: | ||
+ | ==== Q4 Can I use the Fronius Smart Meter? ==== | ||
+ | |||
+ | No, when using a Fronius PV Inverter in a Victron system it is not possible to use the Fronius Smart Meter. | ||
+ | |||
+ | Use any of the [[energy-meters: | ||
+ | |||
+ | ==== Q5 How can I get the Fronius firmware that improves flickering? ==== | ||
+ | |||
+ | Fronius has a special firmware available, on request, that fixes light flickering issues that occur on certain installations under certain circumstances. | ||
+ | |||
+ | For Fronius PV inverters produced after 2018-week 16, contain the flicker-fix already straight from production. | ||
+ | |||
+ | To update earlier and/or already installed PV Inverters, contact Fronius Tech Support for the file. The required file is fro29130.upd. Which works for all snap-inverter models (Primo, Symo and Eco). There is no, and will be no, fix available for Fronius Galvos. | ||
- | ~~DISQUS~~ |
ac_coupling/fronius.txt · Last modified: 2023-11-30 07:13 by guy_stewart