 The Victron system monitor, the [[https://www.victronenergy.com/panel-systems-remote-monitoring/color-control|Color Control GX]] includes [[ccgx:ccgx_fronius|built-in Fronius monitoring]]. The Victron system monitor, the [[https://www.victronenergy.com/panel-systems-remote-monitoring/color-control|Color Control GX]] includes [[ccgx:ccgx_fronius|built-in Fronius monitoring]].
 +
 +{{:ac_coupling:ccgx_devicelist_fronius.png?direct|}}
 +{{:ac_coupling:ccgx_hub4_overview_froniusicon.png?direct|}}
 +
  
 ===== Frequency shifting ===== ===== Frequency shifting =====
Line 9: Line 13:
 To make sure that the Fronius PV inverter works well with Victron inverter/chargers, both must be configured with the right 'frequency shift settings': To make sure that the Fronius PV inverter works well with Victron inverter/chargers, both must be configured with the right 'frequency shift settings':
   * The Fronius PV Inverter must be set to Setup MG, short for Micro-Grid.    * The Fronius PV Inverter must be set to Setup MG, short for Micro-Grid. 
-  * The Victron inverter/charger must be loaded with either the PV Inverter support Assistant or the Hub-2 v3 Assistant. +  * For off-grid systems, load the Multi or Quattro with the PV Inverter support Assistant 
 +  * For on-grid / energy-storage systems, load the Multi or Quattro with the ESS Assistant. Read information about ESS in the [[ess:design-installation-manual|]].
  
-And the [[ac_coupling:start|1:1 rule]] must be adhered to.+And the [[ac_coupling:start|1:limit rule]] must be adhered to.
  
 ===== Fronius / Victron specifics ===== ===== Fronius / Victron specifics =====
Line 18: Line 23:
    
 Compatible inverters are: Compatible inverters are:
-  * Fronius Symo (3~, 3 kW up to 20 kW) -> Software //fro27140.upd// or higher +  * Fronius Primo (1~, 3 kW up to 8.2 kW) -> Software //fro27140.upd// or higher (see FAQ Q5!) 
-  * Fronius Eco (3~, 25 kW or 27 kW) -> Software //fro27140.upd// or higher +  * Fronius Symo (3~, kW up to 20 kW) -> Software //fro27140.upd// or higher (see FAQ Q5!) 
-  * Fronius Primo (1~, kW up to 8.2 kW) -> Software //fro27140.upd// or higher+  * Fronius Eco (3~, 25 kW or 27 kW) -> Software //fro27140.upd// or higher (see FAQ Q5!)
   * Fronius Agilo (3~, 75 kW up to 100 kW) -> Software //update19.tl// or higher   * Fronius Agilo (3~, 75 kW up to 100 kW) -> Software //update19.tl// or higher
   * Fronius IG Plus V (1~, 2~, 3~, 2.5 kW up to 12 kW) -> from //IGF 5.0.66// on with settings according to the Victron recommendations   * Fronius IG Plus V (1~, 2~, 3~, 2.5 kW up to 12 kW) -> from //IGF 5.0.66// on with settings according to the Victron recommendations
Line 44: Line 49:
   - Go to the tab Assistants: \\ {{:ac_coupling:add_assistant.png?nolink&}}   - Go to the tab Assistants: \\ {{:ac_coupling:add_assistant.png?nolink&}}
   - Add one of the Assistants that regulate output frequency:   - Add one of the Assistants that regulate output frequency:
-      - Self-consumption Hub-2 v2 +      - [[ess:design-installation-manual|ESS Assistant]]
-      - Self-consumption Hub-2 v3+
       - PV Inverter support       - PV Inverter support
   - Note that it is not necessary to change the default settings in the Assistant. \\ {{:ac_coupling:8b249443cd6d2a5632b07998773a1e6d.png?nolink&}} \\   - Note that it is not necessary to change the default settings in the Assistant. \\ {{:ac_coupling:8b249443cd6d2a5632b07998773a1e6d.png?nolink&}} \\
Line 53: Line 57:
 Table for settings for 50Hz and 60Hz frequency Table for settings for 50Hz and 60Hz frequency
 | ** State ** | ** 50Hz ** | ** 60Hz ** |. | | ** State ** | ** 50Hz ** | ** 60Hz ** |. |
-| Start| 50.| 60.2|Hz|+| Start| 51.| 60.2|Hz|
 | Minimum| 52.7 | 62.7|Hz| | Minimum| 52.7 | 62.7|Hz|
 | Disconnect| 53.0 | 63.0|Hz| \\ | Disconnect| 53.0 | 63.0|Hz| \\
Line 71: Line 75:
 A video instruction how to set up the Datamanager 2.0 + Solar.web can be found [[https://youtu.be/u_DX7PmHPXQ|here]]. A video instruction how to set up the Datamanager 2.0 + Solar.web can be found [[https://youtu.be/u_DX7PmHPXQ|here]].
  
-===== Frequently asked questions =====+===== Zero Feed-in =====
  
-=== Why doesn't the frequency settings in the Multi and the Fronius need to be the same? ===+It is possible to make a Zero feed-in system with Victron & Fronius. The Venus device will the control the Fronius output power. See the [[ess:design-installation-manual|ESS manual]], chapter 4.3.11 Fronius Zero feed-in for details. 
 +===== Frequently Asked Questions ===== 
 + 
 +==== Q1 Why doesn't the frequency settings in the Multi and the Fronius need to be the same? ====
  
 The first two frequencies do not need to be the same since the Multi actively regulates.  The first two frequencies do not need to be the same since the Multi actively regulates. 
  
-=== I have an Fronius IG inverter (not Plus), can that work? ===+==== Q2 I have an Fronius IG inverter (not Plus), can that work? ====
 No, the IG inverters cannot be made to work in a MicroGrid system. The appropriate substitute for an IG 30 is the GALVO 2.5-1 or an IG Plus 25V-1 (depending on the desired DC voltage range). No, the IG inverters cannot be made to work in a MicroGrid system. The appropriate substitute for an IG 30 is the GALVO 2.5-1 or an IG Plus 25V-1 (depending on the desired DC voltage range).
  
 +==== Q3 The system is locked to 53 Hz and does not resume ====
 +See [[:assistants:pv-inverter-support#q1_the_system_is_locked_to_53_hz_and_does_not_resume|here]].
 +==== Q4 Can I use the Fronius Smart Meter? ====
 +
 +That depends on the type of system and software configuration.
 +
 +A Fronius Smart Meter can be used in these two situations:
 +
 +  - when used only for reporting to Solarweb
 +  - when used for limiting export, in a system where the Victron system is not configured as an ESS system.
 +
 +The Fronius Smart-Meter can not be used for the Fronius built-in export limiting feature when part of a Victron ESS system. Instead, use the Victron ESS Fronius Zero-feed in feature, see chapter 4.3.11, Fronius Zero Feed-in, in the [[ess:design-installation-manual|ESS manual]].
 +
 +
 +==== Q5 How can I get the Fronius firmware that improves flickering? ====
 +
 +Fronius has a special firmware available, on request, that fixes light flickering issues that occur on certain installations under certain circumstances.
 +
 +For Fronius PV inverters produced after 2018-week 16, contain the flicker-fix already straight from production.
 +
 +To update earlier and/or already installed PV Inverters, contact Fronius Tech Support for the file. The required file is fro29130.upd. Which works for all snap-inverter models (Primo, Symo and Eco). There is no, and will be no, fix available for Fronius Galvos.
 +